Analysis of System Impact of the Distributed Generation Using EMTP with Particular Reference to Voltage Sag

  • Yeo, Sang-Min;Kim, Chul-Hwan
    • KIEE International Transactions on Power Engineering
    • /
    • 제4A권3호
    • /
    • pp.122-128
    • /
    • 2004
  • With the advent of distributed generation, power systems are fundamentally impacted in regards to stability and power quality. Distributed generation has a positive impact on system restoration following a fault, higher reliability, and mitigation of effect due to voltage sag. However, distributed generation also has a negative impact on decrease of reliability such as changes of protective device setting and mal-operation. Because bulk power systems consist of various sources and loads, it becomes complicated to analyze a power system with distributed generation. The types of distributed generation are usually classified by both rotating machinery and the inverter-based system. In this paper, distributed generation is designed by rotating machinery, and the distributed system having a model of the distributed generation is simulated using EMTP. In addition, this paper presents the simulation results according to the types of distributed generation.

Enhanced Reactive Power Sharing and Voltage Restoration in Islanded Microgrid

  • Pham, Minh-Duc;Lee, Hong-Hee
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2016년도 추계학술대회 논문집
    • /
    • pp.47-48
    • /
    • 2016
  • Parallel distributed generators (DGs) in the islanded micro-grid are normally controlled with the aid of the droop control scheme. However, the traditional droop control methods which use the P-${\omega}$ and Q-E curve to share power between DGs are still concerned to improve the accurate of reactive power sharing and variation of frequency and voltage at the point of common coupling (PCC). This paper proposes a control scheme to solve the limitation of microgrid in islanded operation such as reactive power sharing accuracy and PCC voltage and frequency restoring. In order to achieve the control objective, a secondary control is implemented with both central controller and local controller by using the low bandwidth communications. The effectiveness of the proposed control scheme is analyzed through the simulation.

  • PDF

마이크로그리드에서의 데드 밴드와 회복 제어를 적용한 배터리 에너지저장시스템 주파수 제어 (Frequency Control of Battery Energy Storage System with a Deadband and Restoration Control in Microgrid)

  • 이학주;최진영;최종찬;원동준;채우규;박중성
    • 전기학회논문지
    • /
    • 제61권11호
    • /
    • pp.1584-1589
    • /
    • 2012
  • The grid-interconnected microgrid can be able to operate with and without the utility microgrid to supply electricity. when the microgrid operates in grid-connected mode, the frequency of the microgrid synchronizes with the system frequency. In this case, the frequency of the microgrid has small variation which is able to change the output of distributed generation with a droop controller. Thus, the small variation of frequency can make the distributed generation generate unnecessary electricity consistently. In this paper, we propose a frequency droop control with a dead band so as to prevent the distributed generations from generating unnecessary output while in grid-interconnected mode. In addition, a distributed generation can have a restoration control to restore the frequency changed by a droop control as a rated frequency. Also, we state the problem of restoration control with a dead band, and propose its solution when the microgrid operates in stand alone mode. We simulate the proposed droop control using PSCAD/EMTDC to verify the validity of the control.

아말감과 금합금의 Galvanic 전류 측정에 관한 실험적 연구 (A STUDY ON THE GALVANIC CURRENT BETWEEN GOLD AND AMALGAM)

  • 김영남;엄정문
    • Restorative Dentistry and Endodontics
    • /
    • 제10권1호
    • /
    • pp.63-70
    • /
    • 1984
  • It was the purpose of this study to determine the galvanic current between a gold alloy inlay and four types of amalgam using the circuit through pulp chambers when the freshly extracted teeth with those restorations were brought into contact in a physiologic saline solution, and to investigate the effectiveness of cavity varnish or ammonated silver-nitrate on the surface of amalgam restoration in reducing galvanic current. The current was measured with current-to-voltage converter and recored on a physiograph 6630-257. The following results were obtained. 1. Generally, galvanic current decreased as the time elapsed. 2. Galvainc current decreased significantly in the first day and after then minimal change was observed until 30th day. 3. Initial galvanic current was 29.6 ${\mu}A$ in the cut amalgam and 24.5 ${\mu}A$ in Dispersalloy amalgam and after then the current was significantly decreased. 4. Initial galvanic current was 12.6 ${\mu}A$ in spherical amalgam (low copper amalgam) and 13.8 ${\mu}A$ in Tytin amalgam and the amount of change was lower in sperical amalgam and Tytin amalgam than that in lathe cut amalgam and Dispersalloy amalgam. 5. Painting ammoniated silver-nitrate or Copalite on the surface of amalgam resotration decreased initial galvanic current and ammoniated silver-nitrate is more effective in decreasing galvanic current than Copalite. 6. Galvanic current by contact between amalgam restoration and gold restoration increased abruptly and dropped rapidly becoming almost.

  • PDF

양전원 송전선로의 고장점 표정 알고리즘 (Fault Location Algorithm in a Two-ended Sources Transmission Line)

  • 박철원
    • 전기학회논문지P
    • /
    • 제65권1호
    • /
    • pp.18-24
    • /
    • 2016
  • In order to service restoration and enhance power system reliability, a number of impedance based fault location algorithms have been developed for fault locating in a transmission line. This paper presents an advanced impedance-based fault location algorithms in a two-ended sources transmission line to reduce the DC offset error effects. This fault location algorithm uses of the GPS time synchronized voltage and current signals from the local and remote terminal. The algorithm uses an advanced DC offset removal filter. A series of test results using ATPdraw simulation data show the performance effectiveness of the proposed algorithm. The proposed algorithm is valid for a two-end sources transmission network.

초고압 지중 케이블 시스템에 대한 편단접지시의 보호대책 (A Protection Method with single-bonding system in EHV Underground Transmission Line)

  • 김장원;강덕환;박근룡;김영범
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1998년도 하계학술대회 논문집 E
    • /
    • pp.1620-1622
    • /
    • 1998
  • The failure occurs in the system of the underground transmission line, the time of restoration is very long, the damage from stopping power supply is very serious and the cost of restoration is very great. because of these problems, the system and equipment must be protected from every electrical failure by installing protection unit. This study is summarized and compared the effects of configuration method of cable protection device with respect to surges in EHV (Extra High Voltage) underground transmission system.

  • PDF

Classifier System and Co-evolutionary Hybrid Approach to Restoration Service of Electric Power Distribution Networks

  • Filipiak, Sylwester
    • Journal of Electrical Engineering and Technology
    • /
    • 제7권3호
    • /
    • pp.288-296
    • /
    • 2012
  • The method proposed by the author is intended for assistance in decision-making (concerning changes of connections) by operators of complex distribution systems during states of malfunction (particularly in the events of malfunctions, for which the consequences encompass extended parts of the network), through designation of connection action scenarios (creating substitute configurations). It is the use by the classifying system working with the co-evolution algorithm that enables the effective creation of substitute scenarios for the Medium Voltage electric power distribution network. The author also completed works concerning the possibility of using cooperation of the evolutionary algorithm and the co-evolutionary algorithm with local search algorithms. The method drawn up may be used in current systems managing the work of distribution networks to assist network operators in taking decisions concerning connection actions in supervised electric power systems.

EMTDC를 이용한 시송전계통의 고조파공진 분석 (Analysis of the Harmonic Resonance in Primary Restorative Transmission Systems Using EMTDC)

  • 이경섭;박성민;송인준;이남호;배주천;황봉환;이흥재
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제54권4호
    • /
    • pp.172-176
    • /
    • 2005
  • Power system restoration following a massive or complete blackout starts with energizing of primary restorative transmission lines. During this primary restoration, inexpected overvoltage may happen due to nonlinear interaction between the unloaded transformer and the transmission system. This is known as the harmonic resonance phenomenon that may cause burning out of transformer or other devices. By now the harmonic resonance is reported in the extra high voltage system. This paper reports the detection of the resonance in Korean power system. Basic analysis and simulation of the harmonic overvoltage is presented using EMTDC.

수중 음향센서용 전력증폭기를 위한 멀티레벨 가변전압출력 AC-DC 전원회로 설계 (Design of Multilevel Variable Output Voltage AC-DC Converter for Power Amplifier of Underwater Acoustic Sensor)

  • 이창열;김인동;노의철;문원규;김원호
    • 전력전자학회논문지
    • /
    • 제18권1호
    • /
    • pp.72-83
    • /
    • 2013
  • The paper proposes a new multilevel variable output voltage AC/DC Converter for power supply of power amplifiers used in underwater acoustic sensors. The proposed multilevel variable output voltage AC/DC Converter is composed of two parts. One as the input section is the high efficiency phase-shifted PWM full bridge DC-DC converter to get multiport power sources. The other as the output section is composed of two flying-capacitor 3-level DC-DC converters and a diode bridge circuit to get fast-response and multilevel variable output voltage for an envelope amplifier. Also the paper suggests the detailed circuit topology and design guideline of multilevel variable output voltage AC/DC converter. It also proposes the power balanced control method between 3-level converters and the voltage balanced algorithm for flying capacitors. Its characteristics should be verified by the detailed simulation results. It is anticipated that the proposed converter will be used very well for power amplifiers used in underwater acoustic sensors.

과도고전압 측정에서 측정값 보정에 관한 연구 (A study on the restoration of transient voltage deformed by the measuring system)

  • 이복희;이국중;전덕규;백승권;임동묵
    • E2M - 전기 전자와 첨단 소재
    • /
    • 제6권3호
    • /
    • pp.255-260
    • /
    • 1993
  • 본 논문은 과도고전압 측정시스템의 단위계단응답으로부터 구한 보정계수를 사용하여 수치계산에 의해 출력값을 보정하는 방법에 대하여 기술하였다. 또한 실규모 용량성분압기의 분압비와 상승시간을 갖는 모의등가회로를 구성하여 측정한 바, 본 연구에서 제안된 보정방법은 급준파 및 차단파 등의 어떠한 입력에도 유용하게 사용할 수 있다.

  • PDF