• Title/Summary/Keyword: Ventilation mode

Search Result 114, Processing Time 0.402 seconds

Effect of Contaminant Source Location on Indoor Air Quality

  • Lee, Hee-Kwan;Kim, Shin-Do
    • Journal of Korean Society for Atmospheric Environment
    • /
    • 제14권E호
    • /
    • pp.1-7
    • /
    • 1998
  • This paper presents an experimental study for understanding the indoor air quality in a room. A model room, which had a ceiling-mounted supply and a sidewall-mounted exhaust, was used to examine the effect of air exchange rate (AER) and contaminant source location (CSL) as a function of the elapsed time. A tracer gas method, using carbon monoxide tracer, gas analyzers, and a data acquisition system, was applied to study the ventilation air distribution and the tracer removal efficiency, so-called pollutant removal efficiency, in the model room. The experiment was composed of two parts; firstly the AER was varied to examine its effect on the ventilation air distribution and the ventilation effectiveness and secondly both AER and CSL were considered to determine their effect on the pollutant removal efficiency. It was found that the ventilation effectiveness in the model was proportional to AER but not linearly. It was also found that changing the CSL can improve the pollutant removal efficiency. In some cases, the efficiency improvement by increasing AER was achieved by simply changing CSL.

  • PDF

유조선 화물취급구역내 동력환기특성에 관한 연구 (A Study on Mechanical Ventilation Characteristics in Cargo Handling Area of Tanker)

  • 조대환
    • 해양환경안전학회지
    • /
    • 제7권1호
    • /
    • pp.15-23
    • /
    • 2001
  • In regulation of IGC code 12.1 mechanical ventilation should be arranged to ensure sufficient air movement through the space to avoid the accumulation of flammable or toxic vapours and ensure a safe working environment, but in no case should the ventilation system have a capacity of less than 30 changes of air per hour baed upon the total volume of the space. In this study, a scaled mode chamber was constructed to investigate the ventilation characteristics and stagnation area in the hood room of LNG carrier and pump room in tanker. An experimental study was performed on the model by using visualization equipment with a laser apparatus and an image intensifier CCD camera. Twelve different kinds of measuring areas were selected as the experimental condition. Instant simultaneous velocity vectors in the whole fields were measured by a 2-D PIV system A three-dimensional numerical simulation was also carried out for three different Reynolds numbers. Then the CFD predictions were discussed with the experimental results. The results show the spiral L-shape flow that moves from the opening on the left wall diagonally to the upper right part dominates the ventilation structure. The stationary area of hood room in the velcoity distributions was located in the upper left stern part.

  • PDF

스크린도어가 설치된 대심도 지하역사의 제연 실험 - 터널 송풍기에 의한 제연의 효과 분석 (Smoke Control Experiment of a Very Deep Underground Station Where Platform Screens Doors are Installed - Analysis on Smoke Control Performance by Fans equipped in Tunnel)

  • 박원희;김창용;조영민
    • 예술인문사회 융합 멀티미디어 논문지
    • /
    • 제9권9호
    • /
    • pp.721-736
    • /
    • 2019
  • 본 논문에서는 대심도에 위치한 지하역사(지하 6층) 및 터널에서 화재가 발생했을 경우 제연설비 작동에 따른 연기의 거동을 측정하였다. 열풍기를 이용하여 열부력 효과를 구현한 연기발생장치를 이용하여 화재연기를 생성하였다. 화재발생 위치는 승강장 위 및 스크린도어 외부에 위치한 터널부의 승강장 위의 2가지 위치를 선정하였다. 승강장 화재발생시 승강장에 설치된 환기구를 통하여 연기가 배출되도록 하는 제연모드가 일반적인데 본 연구에서는 승강장 양단에 위치한 터널부의 환기구를 통한 배기도 같이 동작되도록 설정하여 실험을 수행하였다. 다양한 위치에서 연기농도 및 풍향풍속을 측정하였고 화면을 취득하여 연기의 이동 및 제연을 분석하였다. 승강장 내부에서 화재가 발생하였을 경우와 선로부에서 화재가 발생하였을 경우 승강장의 송풍기의 제연모드 동작과 터널의 송풍기의 배연 동작으로 인하여 연기배출이 원활하였고 화재 발생 인근 구역으로의 연기전파가 억제되었다. 본 연구에서 제시한 승강장 및 승강장 양단부의 터널에 적용되는 송풍기를 같이 운전하는 제연모드를 통하여 승강장 화재 및 화재열차 정차시 화재 연기로부터 승객들에게 보다 안전한 대피환경을 제공할 수 있을 것이다.

지하철 터널부로의 열 및 연기배출에 관한 연구 (A Study of Heat and Smoke Exhaust to Subway Tunnel Direction)

  • 이동호
    • 한국안전학회지
    • /
    • 제19권3호
    • /
    • pp.1-8
    • /
    • 2004
  • This study aims to derive the operation method of a comprehensive ventilation system which is capable of providing passengers with safe exit paths from platforms in onboard fire situations. To accomplish this, the airflow distributions in subway platforms under 6 types of tunnel vent system were calculated in addition to having analyzed diffusion behaviors of smoke and heat exhaust in such states by performing 6 kinds of different ventilation scenarios in a 3-D Fire Dynamic Simulation (FDS) simulation model. In order to recommend the mechanical smoke exhaust operation mode, Subway Environmental Simulation(SES) is used to predict the airflow of the inlet and outlet tunnel for the subway station to clarify the safety evaluation fir the heat and smoke exhaust on subway fire events.

고속전철용 추진제어장치의 냉각용 인버터를 위한 제동초퍼 회로 설계 및 제어 (Design and Control of Braking Chopper Circuit for Ventilation Inverter of Traction Control System)

  • 조성준
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2011년도 전력전자학술대회
    • /
    • pp.314-315
    • /
    • 2011
  • This paper introduces the design and control method of braking chopper circuit which can supply input power to ventilation inverter of traction control system. The DC input voltage from auxiliary block (static inverter) is normally used as an input of ventilation inverter. It converts DC input to AC output voltage to drive cooling fans for traction control system and traction motors. The electrical braking force is very important for high speed train to guarantee safety even though the train is running in the dead section where the pantograph voltage is not supplied. When the high speed train decelerate speed in dead section, the regenerative energy is dissipated by braking resistor. This paper proposed the braking chopper control method to implement rheostatic braking function and the appropriate chopper circuit for supplying voltage source to ventilation inverter during rheostatic braking mode. The proposed chopper circuit makes it possible for traction control system to regenerate power continuously regardless of the existence of pantograph voltage. The feasibility of proposed braking chopper control and circuit were proven by inertia load test and actual train field test.

  • PDF

장대 터널 내 구난역의 열차 화재 시 제연을 위한 1D-3D 연계 해석 (The 1D-3D Simulation for Smoke Ventilation in a Rescue Station of a Railroad Tunnel under the Fire)

  • 정재혁;허남건;이정표;김진곤
    • 설비공학논문집
    • /
    • 제22권10호
    • /
    • pp.665-671
    • /
    • 2010
  • In the present study a 1D-3D numerical simulation was performed to analyze the fire safety in a rescue station of a long railroad tunnel equipped with a mechanical ventilation. The behavior of hot air was studied for the emergency operation mode of ventilation system in case of fire in the rescue station. The 1D simulation was carried out for entire tunnel region. Detailed 3D CFD simulation was performed for the rescue station area in the central region of the tunnel by using the result of the 1D simulation as the boundary condition of the 3D simulation. Various type of cross passage installation were evaluated for the prevention of smoke diffusion to suggest the optimized interval of the cross passages in the rescue tunnel.

강제환기가 적용된 시험공간에서 냉난방부하의 시뮬레이션 및 실증실험 (Simulation and Verification Experiment of Cooling and Heating Load for a Test Space with Forced Ventilation)

  • 김동혁;홍희기;유호선;김욱중
    • 설비공학논문집
    • /
    • 제18권12호
    • /
    • pp.947-954
    • /
    • 2006
  • Building energy consumption according to the ventilation has been considered to be an important subject. The purpose of this study is to investigate the cooling and heating loads in a test space with a forced ventilating system. In the test space, on/off controlled air-conditioning and forced ventilating facility were operated between 8 : 30 to 21 : 00 during 4 days and some important data like temperatures and energy consumption were measured to obtain actual thermal loads. The simulation was carried out in a mode of temperature level control using a TRNSYS 15.3 with a precisely measured air change amount and performance data of air-conditioner. Heating load and cooling load including sensible and latent were compared between by experiment and by simulation. Both of thermal loads associated with ventilation show a close agreement within an engineering tolerance.

기계적 호흡 치료로부터의 이탈방법으로서 Intermittent Mandatory Ventilation 단독 사용과 Pressure Support를 병용한 Intermittent Mandatory Ventilation의 비교 (A Comparison of Clinical Efficacy of Weaning Method Between the Mode of Intermittent Mandatory Ventilation and Intermittent Mandatory Ventilation Plus Pressure Support)

  • 최정은;고윤석;조원경;임채만;김우성;박평환;최종무;김원동
    • Tuberculosis and Respiratory Diseases
    • /
    • 제41권4호
    • /
    • pp.372-378
    • /
    • 1994
  • 연구배경 : PSV는 시술자가 정해준 만큼의 양압으로 기관 삽관 환자의 자발적 흡기 노력을 도울 수 있는 새로운 기계 호흡 방식으로서 5~10cm $H_2O$로 적용시 기관내 삽관으로 인한 기도 저항 및 인공 호흡기 회로에서 발생하는 저항을 극복할 수 있다. 저자들은 기계호흡 이탈시 IMV 단독적용과 IMV에 10cm $H_2O$ 압력의 PSV 병용시 이탈성공률 및 이탈과정 중 나타나는 생리적인 변화를 비교하고자 하였다. 방법 : 기계호흡을 받는 환자로 기저질환이 안정되고 활력징후 및 동맥혈 가스교환 지표가 안정된 환자에게 IMV와 IMV + PSV를 무작위 적용하였다. 각 환자의 임상적 특성, APACHE II score 및 영양상태를 조사하였고 이탈시도 후 48시간까지 맥박수, 평균혈압 및 호흡수를 측정하였다. 결과 : 총이탈시도는 37회였고 이중 IMV 단독적용군은 18회, IMV+PSV 동시적용군은 19회의 이탈시도가 있었다. 양 군간에 연령, 총 기계 호흡시간, 평균 APACHE II score, 영양 상태에 있어 통계적으로 유의한 차이는 없었고, 이탈 성공률은 IMV군이 38.4%(7/18), IMV+PSV군이 42.1%(8/19)로 통계적으로 유의한 차이는 없었다(p value=0.84). 이탈 시도 중의 평균 혈압, 맥박수, 호흡수의 이탈 시도전 기저치에 대한 변동량 역시 양군간에 유의한 차이는 없었다. 결론 : IMV에 PSV 10cm $H_2O$를 병용하는 것은 IMV 단독 이탈 방법에 비하여 이탈 성공률에 있어 더 나은 점은 없었으며 10cm $H_2O$ PSV는 이탈과정 중 유의한 생리적 변화는 일으키지 않았다.

  • PDF

폐열회수형 환기장치의 휘발성유기화함물 배출 특성에 관한 연구 (A Study on the Release Characteristics of VOCs from Heat Recovery Ventilation System)

  • 곽경민;배철호;김지용;주의성
    • 청정기술
    • /
    • 제13권4호
    • /
    • pp.281-286
    • /
    • 2007
  • 본 연구에서는 폐열회수형 환기장치(전열교환기)로부터의 휘발성 유기화합물이 측정되었다. KS 냉방 및 난방표준조건하에서 휘발성유기화합물의 초기 배출특성을 연구하기 위하여 폐열회수 환기장치로부터 2종류의 열교환소자(L형과 M형)가 평가되었다. 휘발성 유기화합물은 다양한 풍량 변화와 운전시간 변화에 대하여 측정되었다. 본 연구의 분석방법 및 기기상의 한계로 인하여 농도가 비교적 큰 물질만을 살펴보니 페열회수 환기장치에서는 acetic acid, 2-butanone (MEK), 2-(methylthio)ethylamine, toluene, styrene 및 x-acids (Ion 57) 등의 6종의 휘발성 유기화합물이 배출됨을 확인하였다. 배출된 휘발성 유기화합물의 농도는 운전조건에 대해서는 크게 영향을 받지 않았다. 높은 작동온도 때문에 휘발성 유기화합물의 농도는 난방조건보다는 냉방조건에서 더 크게 나타났다.

  • PDF

대심도 지하역사에서의 화재시 급 배기 동작유무에 따른 열 연기 거동 분석 (Numerical Study on the characteristics of fire driven flow for smoke ventilation system operating in the deeply underground subway station)

  • 장용준;김학범;이창현;정우성
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 2008년도 추계학술대회 논문집
    • /
    • pp.66-72
    • /
    • 2008
  • 본 연구에서는 대심도 지하역사에서 화재가 발생할 시 급/배기 팬의 동작 유무에 따른 승강장에서의 열 및 연기의 거시적인 거동을 화재시뮬레이션을 통하여 분석하였다. 시뮬레이션 분석결과를 토대로 현재 설치된 급/배기 팬에 대한 제연/배연능력에 대하여 고찰하였다. 본 연구의 대상은 숭실대 입구 역사(7호선, 도시철도공사운영)이며, 숭실대 역사의 승강장은 길이 165m, 폭 23.5m, 깊이 47m 이다. 본 연구에서 전산수치해석을 위한 모델은 선로부 지하터널를 감안하여 전후 각 100m를 추가하였다. 따라서 모델링의 크기는 길이 365m, 폭23.5m, 깊이 47m 이다. 격자는 육면체 정렬격자계를 사용하였으며, 격자의 수는 대략 10,000,000 개가 사용되었다. 빠른 수치전산처리를 위하여, 병렬처리기법을 적용하였다. 본 전산수치해석에 사용된 CPU자원에 Intel 3.0GHZ Dual CPU 6개(core 12개)가 사용되었다.

  • PDF