• 제목/요약/키워드: Underground Transmission Systems

검색결과 98건 처리시간 0.032초

지중송전 편단접지개소에서의 병행지선 설치효과 검토 (Study on the Effect of Parallel Ground Conductor at the Single Point Bonding in Underground Transmission System)

  • 강지원;박흥석;윤형희;윤종건;배주호;석광현;오장만;김재승
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2007년도 제38회 하계학술대회
    • /
    • pp.736-737
    • /
    • 2007
  • The single point bonding in underground transmission system can induce high voltage on the sheath when ground fault, lightning serge and switching serge occurs, at that time underground cable systems cannot offer a return path of fault current. Accordingly if fault current, which cannot return to ground, flows at the single point bonding, high voltage can be induced in SVL and that voltage can cause aging and breakdown of SVL. Therefore this paper study on the effect of parallel ground conductor at the single point bonding when ground fault and lightning serge occurs by using ATPDraw.

  • PDF

345kV CV케이블의 절연두께 산정 (Estimate of Insulation thickness for EHV XLPE power cable)

  • 최봉남;윤덕환
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2001년도 하계학술대회 논문집 C
    • /
    • pp.1801-1803
    • /
    • 2001
  • At present the under ground power transmission systems have installed until 154KV XLPE power cable in Korea But, the large capacity underground power transmission systems have been required gradually with the increasing demand of electric power. Therefore, our company has developed 345KV XLPE cable. This paper describes the estimate details of the insulation thickness according to weibull plotting for 345KV XLPE power cable.

  • PDF

국내 지중 케이블 고장현황 분석 (Failure Analysis of Underground Transmission Cable Systems)

  • 강연욱;조성배;곽방명;임헌의;윤형희
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 E
    • /
    • pp.2377-2379
    • /
    • 1999
  • In order to analyze failure rates of underground transmission power cable systems in Korea, the survey has been performed for the failure cases of cables, joints, and terminations in CV, OF and POF cable systems which occurred from 1983 to 1998. During 16 years, the failure cases due to trips of the systems were 47 among the total 108 cases, These 47 cases could be divided into internal reasons(manufacture/installation, corrosion and degradation) of 16 cases and external reasons (external mechanical damages, lightning, fire. etc.) of 31 cases. For the 154 kV cable systems during 12 years from 1987 to 1998, total failure rate was 0.0057 [case/100C-km/year] and internal reason failure rate was 0.0020 [case/100C-km/Year], which is similar to those of foreign countries. Also, the many cases of internal reason failures occurred in the early stage after the operations due to incorrect installations. This implies that the installation process is very important and some diagnostic tests such as PD measurement are needed besides after laying test.

  • PDF

혼합송전계통에서 웨이브렛 변환을 이용한 고장점 탐색 알고리즘에 관한 연구 (A Study on a Fault Location Algorithm Using Wavelet Transform in Combined Transmission Systems)

  • 정채균;이종범;윤양웅
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제51권5호
    • /
    • pp.247-254
    • /
    • 2002
  • This paper describes a fault location algorithm in real combined transmission systems with underground power cable. The algorithm to calculate the fault location was developed using DWT wavelet transform and travelling wave occurred at fault point. And the proposed algorithm is also used the transient signal of one end in stead of the signal information of two ends. On the other hand, in this papers, the method to discriminate fault point between overhead line and cable section is also Proposed. Variety simulations were carried out to verify the accuracy and effectiveness of the proposed algorithm using EMTP/ATFDraw and Matlab. Simulation results show that the proposed method has the excellent ability for discrimination of fault section and fault location in combined transmission systems with power cables.

초고압 CABLE 감시시스템 연구 (Surveillance System For Extra High Voltage Cable)

  • 한기만;이광철;전승익;김충식
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1992년도 하계학술대회 논문집 B
    • /
    • pp.789-793
    • /
    • 1992
  • For improving the power supply reliability and minimizing maintenance work of E.H.V. underground transmission line, new surveillance systems are strongly desired for use in the field of electric power transmission. For underground installation, high system reliability is required because E.H.V. cables, if an accident happen, can have a serious impact on social activities and human life. In answer to this requirement, applications of optical fiber transmission system have been widely developed in a variety of field. The main function of this system are cable fault location, oil leak detection, and surveillance of the cable circuit and tunnel condition.

  • PDF

광응용 자계센서를 이용한 지중송전선 사고구간 검출에 관한 연구 (A Study on Fault Detecting for Underground Power Transmission Lines using Optical Field Sensors)

  • 이광중;김석구;박해수;김요희
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1994년도 하계학술대회 논문집 A
    • /
    • pp.91-93
    • /
    • 1994
  • Recently, for improving the power supply reliability and for rationslizing maintenance, new maintenance and monitoring systems are stornagly desired for use in the field of electric power transmission. In this paper, we describes the optical fault detecting method of underground power transmission lines using bareearth doped YIG Faraday sensors which are very light, small size and fast response. As regarding, we use the zero phase current detecting algorithm at insulated joints.

  • PDF

Sheath Circulating Current Analysis of a Crossbonded Power Cable Systems

  • Jung, Chae-Kyun;Lee, Jong-Beom;Kang, Ji-Won
    • Journal of Electrical Engineering and Technology
    • /
    • 제2권3호
    • /
    • pp.320-328
    • /
    • 2007
  • The sheath in underground power cables serves as a layer to prevent moisture ingress into the insulation layer and provide a path for earth return current. Nowadays, owing to the maturity of manufacturing technologies, there are normally no problems for the quality of the sheath itself. However, after the cable is laid in the cable tunnel and is operating as part of the transmission network, due to network construction and some unexpected factors, some problems may be caused to the sheath. One of them is the high sheath circulating current. In a power cable system, the uniform configuration of the cables between sections is sometimes difficult to achieve because of the geometrical limitation. This will cause the increase of sheath circulating current, which results in the increase of sheath loss and the decrease of permissible current. This paper will study the various characteristics and effects of sheath circulating current, and then will prove why the sheath current rises on the underground power cable system. A newly designed device known as the Power Cable Current Analyser, as well as ATP simulation and calculation equation are used for this analysis.

지중송전계통에서 저감장치를 이용한 시스 순환전류 저감방안에 관한 연구 (A Study on the Reduction Methods of Sheath Circulating Current using the Reduction Equipment in Underground Transmission Systems)

  • 강지원;양해원
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제51권9호
    • /
    • pp.474-481
    • /
    • 2002
  • Sheath circulating current is increased in the change of sheath mutual impedance which is caused by unbalanced cable system, and different section length between joint boxes. If excessive current flows in sheath, sheath loss which is reduced the transmission capacity is produced. Recently, excessive sheath circulating current was partially measured in underground cable systems of KEPCO. Accordingly, actual schemes to reduce excessive sheath circulating current are urgently required for installed cable system as well as newly-installing cable systems. This paper describes the relation analysis of sheath circulating current and burying types. And also, various schemes to reduce excessive circulating current using EMTP/ATPDraw and applicable schemes are proposed through a detailed analysis regarding cable systems by considering various electrical and environmental factors. It is evaluated that the proposed reduction schemes can be effectively applied to reduce the excessive sheath circulating current with the minimized electrical problems. And reduction effect is Proved with sheath circulating current reduction equipment.

지중 송전선로 대칭분 임피던스 해석을 위한 EMTP 전후처리기 개발과 활용 (Development and Application of Pre/Post-processor to EMTP for Sequence Impedance Analysis of Underground Transmission Cables)

  • 최종기;장병태;안용호;최상규;이명희
    • 전기학회논문지
    • /
    • 제63권10호
    • /
    • pp.1364-1370
    • /
    • 2014
  • Power system fault analysis has been based on symmetrical component method, which describes power system elements by positive, negative and zero sequence impedance. Obtaining accurate line impedances as possible are very important for estimating fault current magnitude and setting distance relay accurately. Especially, accurate calculation of zero sequence impedance is important because most of transmission line faults are line-to-ground faults, not balanced three-phase fault. Since KEPCO has started measuring of transmission line impedance at 2005, it has been revealed that the measured and calculated line impedances are well agreed within reasonable accuracy. In case of underground transmission lines, however, large discrepancies in zero sequence impedance were observed occasionally. Since zero sequence impedance is an important input data for distance relay to locate faulted point correctly, it is urgently required to analyze, detect and consider countermeasures to the source of these discrepancies. In this paper, development of pre/post processor to ATP (Alternative Transient Program) version of EMTP (Electro-Magnetic Transient Program) for sequence impedance calculation was described. With the developed processor ATP-cable, effects of ground resistance and ECC (Earth Continuity Conductor) on sequence impedance were analyzed.

국내외 지중송전시스템의 과도상태 해석 (Analysis of transient state between Korea and Japan in Underground Transmission Cable System)

  • 강지원;장태인;홍동석;이동일;정채균;이종범
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 제36회 하계학술대회 논문집 A
    • /
    • pp.462-464
    • /
    • 2005
  • This paper analyses the transient phenomena against single line to ground fault and lightning surge between Korea and Japan on underground power cable systems. For analysis, find proper earthing resistance of neutral grounding system adopted in Japan. This paper is expected to contribute the establishment of proper protection methods against transients on underground power cable systems.

  • PDF