• 제목/요약/키워드: Tunnel pollutants

검색결과 49건 처리시간 0.027초

터널내 열차 화재시 효과적인 구난역 제연 설비를 위한 수치 해석 연구 (A Numerical Study on Effective Smoke-Control System of a Rescue Station in a Tunnel Fire)

  • 양성진;원찬식;허남건;차철현
    • 유체기계공업학회:학술대회논문집
    • /
    • 유체기계공업학회 2006년 제4회 한국유체공학학술대회 논문집
    • /
    • pp.575-578
    • /
    • 2006
  • In designing smoke-control system of rescue station in train tunnel, a purpose is to prevent a disaster by proposing the jet fan operation together with smoke-control curtain in tunnel fire. This study has investigated the relationship of the Heat Release Rate(HRR) and a adequate ventilation velocity to control the fire propagation in tunnel fire, and has improved the effect of the smoke-control curtain on preventing the flow of pollutants. In this study, Computational Fluid Dynamics(CFD) simulations with ST AR-CD(ver 3.24) were carried out on predicting the fire spreading and the flow of pollutants, considering jet fan operations and effect of smoke-control curtain. Our simulation domain is the full scale model of the 'DAEGWALLYEONG' 1st tunnel. The results represent that ventilation operation can control the fire spreading and pollutants effectively to prevent a disaster.

  • PDF

터널환기제어를 위한 차종별 오염물 배출량 추정 (Estimation of Pollutants Exhausted :From vehicles for Tunnel ventilation Control)

  • 홍대희;김우동;김태형;민원
    • 대한기계학회논문집B
    • /
    • 제26권1호
    • /
    • pp.110-115
    • /
    • 2002
  • The tunnels built in recent years are equipped with traffic counters and pollution sensors (mostly, CO and Vl sensors). Utilizing these built-in sensors, it is possible to develop an algorithm to estimate the amount of pollutants exhausted from the each class of cars passing through the tunnel. These estimated data can be effectively utilized not only for ventilation control but also for designing ventilation facilities. The diffusion of pollutants in a tunnel can be described with one-dimensional diffusion-convection equation. This equation is approximated with interpolation functions and weighted residual method converting to adequate form for standard state estimate algorithms. With this converted equations, a least square optimization based algorithm is developed, whose outputs are the estimated amounts of pollutants emitted from each class of cars. In order to verify the feasibility of the developed algorithms, simulations are performed with the real data acquisitioned from the Tunnae tunnel located in Young-Dong highway in Korea.

서울시 주요 터널내 기체상 오염물질 농도 측정 (Measurements of Gaseous Pollutants in Major Tunnels in Seoul)

  • 김영성;경남호;손재익;문길주;김용표;백남준;김태오
    • 한국대기환경학회지
    • /
    • 제9권4호
    • /
    • pp.320-328
    • /
    • 1993
  • Gaseous pollutants in Namsan Nos. 1, 2, and 3 tunnels and Pukak tunnel were measured along the road by an air-monitoring van from the evening of February 9 to the morning of February 12 in 1993. Average concentrations of pollutants in Namsan tunnels were 9.2-13.5 ppm CO and 0.037-0.047 ppm SO$_{2}$. Average concentrations of SO$_{2}$ in Pukak tunnel was 0.79 ppm, higher than those in Namsan tunnels, due to the traffic of heavy-duty buses and trucks. The pollutant concentrations in Namsan tunnesl could be explained by emission of passenger cars using unleaded gasolin and LPG taxies. Average concentration of NO$_{x}$ in Namsan tunnels was at least 1.1 ppm, estimated from the emission factor of pasenger cars using unleaded gasoline. Pollutant concentrations in Namsan No. 3 tunnel were higher at the exit because of the piston action of air mass in the tunnel provided by the traffic. Fans installed at Namsan and Pukak tunnes could be useful, but their flushing action of ambient air in the tunnel was not clearly observed.d.

  • PDF

터널 내 대기오염물질의 공간분포 예측 (Prediction of spatial distribution of air pollutants within tunnel)

  • 박일건;홍민선;김범석;강호근
    • 한국터널지하공간학회 논문집
    • /
    • 제14권6호
    • /
    • pp.607-616
    • /
    • 2012
  • 지속적인 터널 건설의 증가는 터널 내 대기질 관리에 대한 필요성을 점증시키고 있어 측정 및 모델 모사를 통한 터널 내 대기질 거동에 대한 연구를 수행하였다. 남산1호 터널 입구와 출구의 $CO_2$ 농도차는 250 ppm~400 ppm으로 출구쪽이 높았으며 환기를 안 하는 차량 내부의 농도는 외부에 비해 200 ppm~300 ppm 낮게 측정되었다. 교통량이 적을 시 터널 내 유속은 빨라지며 일정한 농도 구배를 나타내고, 교통량이 증가하면 일정치 않은 농도 구배를 나타내는 것으로 나타났다.

터널 세척 폐수 특성 및 분리.흡착 방식에 따른 오염물질 저감 연구 (Study on Pollutant Characteristics of Tunnel Cleaning Wastewater and Removal Characteristics of the Pollutants via Settling and Adsorption)

  • 박상우;최영화;오재일
    • 한국도로학회논문집
    • /
    • 제9권3호
    • /
    • pp.75-82
    • /
    • 2007
  • 터널 내 축적된 다양한 오염원들은 간헐적으로 수행되는 세척과정 중에 폐수로 배출되게 되며, 서울 시내 3개 터널 지점에서 수행된 수질분석결과 SS, $COD_{Cr}$, T-N, $NH_3-N$, $NO_3-N$, Zn, Cu, Cr(+6). Mn, Mg, Phenol. $CN^-$, E-Coli 등이 고농도 형태로 배출되는 것으로 나타났다. 한편, 이러한 오염수질의 배출농도 특성은 터널 세척 폐수의 채취 방법, 세척횟수, 세척수량, 터널내벽 특성, 통행량, 배수 특성 등에 따라 다양한 농도범위를 보여주는 것으로 나타났다. 한편, 수집된 터널 세척폐수를 단순 중력침전을 이용하여 저감실험을 수행한 결과, $COD_{Cr}$는 80%, T-N, T-P는 각각 30, 90% 제거됨을 확인하였고, 중력침전 분리를 통하여 제거되지 않은 잔여 오염물질에 대하여 GAC 소재를 통한 흡착실험(터널 세척폐수 $1{\ell}$에 대하여 GAC를 50g을 투입) 결과, $COD_{Cr}$, T-N, Zn, Cu, Mn, Phenol, CN 항목에서 80% 이상 제거됨을 확인하였다.

  • PDF

도로터널 환기시스템 설계 프로그램 개발 (Study on Optimization Technique for Design of the Road Tunnel Ventilation System)

  • 유지오;이동호;신현주
    • 한국안전학회지
    • /
    • 제14권4호
    • /
    • pp.60-70
    • /
    • 1999
  • In this study, the computer code for the optimal design of road tunnel ventilation system based on one-dimensional analysis of the air flow was developed. The control volume method was used to calculate the air velocities and the concentration distribution of pollutants(CO, NOx, Particulate) for various tunnel ventilation system. This code was validated by comparing the calculation results to the practical design data for the road tunnel ventilation system. The calculation results were in accord with the practical design data.

  • PDF

제트 팬 가동위치에 따른 장대터널 내 CO 농도 변화율에 대한 전산해석 (Investigate on the rate of change of CO concentration in a tunnel under changed position of the jet fans by using numerical method)

  • 민재홍;김대현;정진택
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2008년도 추계학술대회B
    • /
    • pp.2765-2770
    • /
    • 2008
  • The purpose of tunnel ventilation system for long road tunnels is to keep certain levels of Visibility Index and the concentration of CO. Additional equipments such as jet fans are used in road tunnel to discharge pollutants in the road tunnel. The control algorism of tunnel ventilation system takes the value of sensors as input, and then gives the operation method of jet fans in tunnel as output. Information on the variation of CO concentration in tunnel when jet fans are running is needed to minimize their operation time. Numerical analysis is used in this paper because of the difficulty of conducting experiments under standard condition for ventilation of road tunnel. The concentration of CO has been calculated by using 3-dimensional CFD under transient condition with speed of cars, quantity of air ventilation, and the results for various operation position of jet fans are compared.

  • PDF

환기시스템 적용 도로터널의 국소환기 특성 시뮬레이션 및 해석 (Simulation and Analysis of Local Ventilation characteristic of Road Tunnel with Ventilation System)

  • 박기림;오명도;이재헌
    • 설비공학논문집
    • /
    • 제13권5호
    • /
    • pp.321-332
    • /
    • 2001
  • In this study, a design program for ventilation requirements of a longitudinal raod tunnel were developed and investigated. The control volume method was applied to calculate the local air velocity and the local concentration distribution of pollutants, CO, $NO_x$, soot along the tunnel for various tunnel ventilation system. This program was validated by comparing with the practical design data for the road tunnel ventilation system. The calculation results were in good agreement with the practical design data.

  • PDF

젯트팬 종류식 터널의 퍼지응용 제어로직에 관한 연구 (The Study of Jet Fan Control Logic for Longitudinal Ventilation in Road Tunnel)

  • 유지오;남창호;신현준
    • 설비공학논문집
    • /
    • 제12권8호
    • /
    • pp.763-770
    • /
    • 2000
  • In tunnel ventilation, the Purpose of ventilation control is to keep the required pollution level with minimum consumption of energy But tunnel ventilation has large disturbances caused by discharge of pollutants, traffic forces especially strong for longitudinal ventilation. Hence in this paper, the tunnel ventilation control logic applying fuzzy control theories is proposed and the simulation program of tunnel ventilation control is developed. The characteristics of longitudinal ventilation with jet fans are estimated and the effect of the proposed tunnel ventilation control is verified by the simulation program.

  • PDF

오염물질 현장측정 및 사례조사를 통한 도로터널 환기기준의 적정성에 관한 연구 (An appropriateness review on the road tunnel ventilation standards by pollutants site measurement and case study)

  • 김효규;백두산;유지오
    • 한국터널지하공간학회 논문집
    • /
    • 제22권3호
    • /
    • pp.323-335
    • /
    • 2020
  • 본연구에서는 현행 도로터널의 환기설계기준의 적정성을 검토하기 위하여 사례조사를 수행하고, 5개 터널을 대상으로 입자상 및 가스상 물질의 농도를 현장측정 하였다. 사례조사 결과는 설계기준 대비 TSP (가시도)는 27.9%, CO는 1.6%, NOx는 3.4% 수준으로 분석되었고, 현장측정 결과는 각각 2.6%, 0.8%, 0.2%의 수준에 불과하였다. 또한 5개 터널에 대한 입자상물질(TSP)의 입경분석 결과, 타이어 마모, 재부유 분진 등의 입자라 할 수 있는 PM10 이상의 입경의 영역은 20.4%로 나타났다. 따라서 현행 도로터널 환기설계 기준으로 제시된 입자상물질은 엔진배출량 외에 비엔진배출량에 대한 고려가 반드시 필요하며, 최근의 연구결과를 통한 제작차 오염물질 배출량 및 경사속도 보정계수 등을 적용하여 대상오염물질에 대한 설계기준의 합리적인 개정이 요구되며 WRA (PIARC)에서도 환기설계 기준의 개정 필요성을 권고하고 있다. 현행 터널 내 낮은 환기설비(제트팬) 가동율을 고려할 경우 향후 터널 내 운영상 관리기준의 신설에 대한 필요성이 제기된다.