• Title/Summary/Keyword: Transformer Oils

Search Result 75, Processing Time 0.025 seconds

Investigations on PD Characteristics of Thermal aged Palm and Corn Oil for Power Transformer Insulation Applications

  • Senthilkumar, S.;Karthik, B.;Chandrasekar, S.
    • Journal of Electrical Engineering and Technology
    • /
    • v.9 no.5
    • /
    • pp.1660-1669
    • /
    • 2014
  • Partial discharge (PD) detection plays a major role in the life time assessment of liquid insulation in power transformers. Many research works are being carried out to replace conventional mineral oil insulation in transformers by vegetable oils. It is necessary to understand the PD characteristics of vegetable oils before recommending them as an alternate for mineral oil. In this paper, the breakdown strength and PD characteristics of palm and corn oil were investigated in both unaged and thermally aged conditions. Laboratory experiments were performed as per IEC test procedures. PD signals were measured using wide band detection system. Phase resolved PD pattern of vegetable oils and mineral oil were compared. Effect of increase in voltage stress on the PD pattern of palm and corn oil were studied. Time and frequency domain analysis of PD pulses at needle-plane electrode configuration was carried out. Statistical analysis of PD pattern i.e. skewness and shape parameter variations with respect to applied thermal stress were also carried out. From the results, it is observed that palm and corn oils have better breakdown strength and PD characteristics even under long-term thermal stress and hence they can be used for power transformer applications.

A Comparative Study on the Non-Destructive Diagnostic Methods of the insulation Oils in Power Transformer (전력용 변압기 절연유희 비파괴 진단 시험법 비교연구)

  • 이준호;이동영;최종갑;김재철;곽희로;권태원;한민구
    • The Transactions of the Korean Institute of Electrical Engineers
    • /
    • v.40 no.8
    • /
    • pp.799-807
    • /
    • 1991
  • The various degradation phenomena, such as the evolution of gases, tan e, moisture content and total acid number in insulation oils of power transformer have been measured and analyzed as a function of aging temperatures and periods. The insulation oils have been degraded at laboratory in the period of 17, 34, and 72 days. We have also extracted the insulation oils from the working power transformers. The dissolved gases (such as CO, CO2, H2, CH4 C2H2---), tane, moisture content and total acid number in laboratory samples and field samples have been measured and characterized. It has been found that gases increase with degradation temperature and tane increases with total acid number while the moisture content does not increase with tane.

  • PDF

Synthesis and Characterization of Soybean-based Ester Insulation Oils (대두유 에스테르계 절연유의 합성과 분석)

  • Han Dong-Hee;Cho Han-Goo;Han Se-Won;Oh Dae-Hee
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.19 no.1
    • /
    • pp.40-45
    • /
    • 2006
  • Electrical insulation is one of the most important parts in a high voltage apparatus. Traditionally mineral oils and synthetic esters have been widely used as dielectric coolants for power transformers. Recently, researchers are interested in the environmentally friendly vegetable oil from the environmental viewpoint. This paper reports on the synthesis and characterization of soybean based ester oils. Two different types of soybean based transformer oils, named as methyl ester and isopropyl ester were synthesized. The synthesis of these esters was achieved by transesterification reactions between soybean oil and alcohol in the presence of catalyst. The GC and NMR spectroscopic analysis of the esters have been performed. It was observed that isopropyl ester has better thermal resistance than methyl ester by TGA. Also, two esters have a good breakdown voltage and electrical resistance.

Electrical Breakdown Properties of Insulating Oils for oil-immersed transformer (유입변압기용 절연유의 절연파괴특성)

  • Lee, I.S.;Shin, H.T.;Lee, J.P.;Lee, S.W.;Hong, J.W.
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2001.11b
    • /
    • pp.605-608
    • /
    • 2001
  • With the intention of investigating the breakdown properties of oil-immersed transformer oils in temperature range of $20\sim100[^{\circ}C]$, we are made researches AC breakdown in the gap of $500\sim2500[{\mu}m]$. The classification for the physical properties of oil for oil-immersed transformer by FTIR and H-NMR experiments was confirmed to type of mineral oils. As the dependance of breakdown properties due to electrode gap length variation, breakdown voltage was found increasing according to the increase of gap, while dielectric strength was decreasing. As a result the characteristics for AC breakdown, It goes to prove that the breakdown voltage was increased to $90[^{\circ}C]$ but decreased over $90[^{\circ}C]$ in the temperature range. Also, breakdown voltage was found increasing in the increase of gap and the rising of temperature according to Weibull distribution.

  • PDF

Effect of Dispersion Technique on Heat Transfer Properties of Transformer Oil with Nanoparticles (변압기 나노절연유의 열전달특성에 미치는 분산기술의 영향)

  • Song, Hyun-Woo;Choi, Cheol;Oh, Je-Myung
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2005.11a
    • /
    • pp.151-152
    • /
    • 2005
  • Both $Al_2O_3$ and AlN nanopowders with diameters from ${\mu}m$ to mm were bead-milled and surface-modified by stabilizing agent. The size of bead-milled nanoparticles compared with the primary powder was effectively decreased and was dependent on milling time and bead size. The results of dispersion stability analysis indicated that chemical bonding between nanoparticles and surfactant is more effective than chemical adsorption to prepare the stable transformer oils containing nanoparticles. In this study, the thermal conductivity of the transformer oils containing nanoparticles was measured by transient hot-wire and laser flash methods.

  • PDF

A Study on Corona Inception Voltage and Dielectric Characteristics of Thermally Aged Mineral and Vegetable Insulation Oil in Medium Voltage Power Transformer (식물유 및 광유를 사용한 배전변압기의 열열화에 따른 절연유의 코로나 개시전압 및 전기적 특성에 대한 연구)

  • Jeong, Jung-Il;Huh, Chang-Su
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.66 no.12
    • /
    • pp.1745-1750
    • /
    • 2017
  • Starting from the distribution transformer, the insulation oil for the oil immersed power transformer is being used to convert the vegetable oil from the existing mineral oil. Vegetable oil is better in temperature characteristics and insulation performance, is not toxic, and has better biodegradable characteristic than that of mineral oil. In order to investigate the corona inception voltage and dieclectic charateristics of the two insulating oils, three oil immersed transformers using mineral oil and vegetable oil were made and thermal cyclic aged. In this paper, the changes in the corona discharge inception voltage, chemical and electrical properties of the two sampled insulating oils from the transformers had been studied.

Analysis of the polychlorinated biphenyls in transformer oils using peak matching method (피크패턴법을 이용한 절연유 중 PCBs 분석)

  • Shin, Sun Kyoung;Kim, Hye-Jin;Chung, David;Jeon, Tae Wan;Kim, Jin Kyoung;Park, Seok Un;Chung, Young Hee;Chung, Il Rok
    • Analytical Science and Technology
    • /
    • v.18 no.5
    • /
    • pp.410-418
    • /
    • 2005
  • PCBs had numerous uses such as hydraulic fluid, heat exchange fluid, sealant, lubricant, and carbonless copy paper. They are most likely found in electric utilities, power stations, industrial facilities, electronic manufacturing plants, petrochemical plants, railroad systems, electric equipment repair facilities, mining sites (active or abandoned), and military camps. Due to its outstanding chemical and thermal stabilities and electrical insulation properties, the commercial and industrial products of PCBs, such as Aroclors, Kaneclors, Clophens, Phenaclors etc., had been widely used as thermal oil and transformer oil from 1930s until the 1970s. The transformer oils were analyzed as a main source of polychlorinated biphenyls (PCBs) emission into the environment. Qualitative estimation of oil extracts as carried out with Aroclor 1242, 1248, 1254, 1260. The transformer oils contained the pure and mixed of Aroclor 1242, Aroclor 1254, and Aroclor 1260. Also, commercial screening kit of 20 ppm and 50 ppm were applied to the transformer oil samples.

Comparison the quantification method of PCBs in waste transformer oils (절연유 중 폴리염화비페닐류의 정량법 비교)

  • Kim, Kyeo-Keun
    • Analytical Science and Technology
    • /
    • v.18 no.3
    • /
    • pp.206-215
    • /
    • 2005
  • Polychlorinated biphenyls (PCBs) were commercially produced as complex mixtures beginning in 1929. The PCBs manufactured commercially are known by a variety of trade names including; Aroclor (USA), Phenoclor (France), Kaneclor (Japan), Sovol (USSR) and so on. PCBs are a class of 209 congeners that were widely used in a wide variety of applications, including dielectric fluid in transformers and large capacitors; heat transfer fluids; hydraulic fluids; lubricating and cutting oils; and as additives in pesticides, paints, adhesives, sealants, and plastics. The quantification methods of peak matching and coefficient comparison were compared using the Aroclor 1242, 1248, 1254, 1260 standards. Also, six transformer oils were analyzed as a main source of polychlorinated biphenyls (PCBs) emission into the environment. The transformer oils contained the pure and mixed of Aroclor 1242, Aroclor 1254, and Aroclor 1260. The analytical results using two quantification methods showed the little difference between the measured results.

Research of Flow Electrification Phenomena of the used Environment-Friendly Vegetable Insulating Oils (친환경 식물성절연유의 유동대전현상 연구)

  • Choi, Sun-Ho;Huh, Chang-Su
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.61 no.4
    • /
    • pp.580-584
    • /
    • 2012
  • The insulating oils perform a cooling and insulation action in electric power transformer. The mineral oil has immanent fire dangerousness and environmental contamination problem. Vegetable insulating oil has higher ignition point, flash point and more excellent biodegradability than conventional mineral oil. In a real oil-filled transformers, some of the power is dissipated in the form of heat. And transformer require the heat to be removed from the winding and insulator by forced convection of the insulating oil. The flow electrification occurs when insulating oil was forced to be circulated. In this paper, influence of temperature, velocity of flow, and insulating pipe and diameter on streaming electrification of vegetable insulating oil was investigated using forced circulation apparatus. Temperature effects were most significant, and it showed a peak in the temperature $30^{\circ}C$ to $35^{\circ}C$ at insulating and copper pipe. The change of flow electrification according to area variety could be checked by change of diameter.

The Effect on the Streaming Electrification of Insulating Oils with Impurity (변압기유의 불순물에 따른 유동대전 영향)

  • 이용우;이광석;송병기;김왕곤;홍진웅
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 1996.11a
    • /
    • pp.329-333
    • /
    • 1996
  • In this Paper, the streaming electrification of transformer oils generated at the interface of transformer oils and the AC breakdown with impurity is studied. The electrification current is measured by the electrometer connected the faraday cage. And a oil velocity is maintained equally. In case of the AC breakdown test, the temperature are 30[$^{\circ}C$], 50[$^{\circ}C$], 80[$^{\circ}C$] and 90[$^{\circ}C$], repetitively. As a result of breakdown experiment, the dielectric breakdown strength is decreased in low temperature region and is increased in high temperature region according to increase of contained sodium. In case of streaming electrification experiment, the streaming current is more increased with the specimen contained sodium than the original specimen.

  • PDF