Browse > Article
http://dx.doi.org/10.5370/KIEE.2017.66.12.1745

A Study on Corona Inception Voltage and Dielectric Characteristics of Thermally Aged Mineral and Vegetable Insulation Oil in Medium Voltage Power Transformer  

Jeong, Jung-Il (Dept. of Electrical Engineering, Inha University)
Huh, Chang-Su (Dept. of Electrical Engineering, Inha University)
Publication Information
The Transactions of The Korean Institute of Electrical Engineers / v.66, no.12, 2017 , pp. 1745-1750 More about this Journal
Abstract
Starting from the distribution transformer, the insulation oil for the oil immersed power transformer is being used to convert the vegetable oil from the existing mineral oil. Vegetable oil is better in temperature characteristics and insulation performance, is not toxic, and has better biodegradable characteristic than that of mineral oil. In order to investigate the corona inception voltage and dieclectic charateristics of the two insulating oils, three oil immersed transformers using mineral oil and vegetable oil were made and thermal cyclic aged. In this paper, the changes in the corona discharge inception voltage, chemical and electrical properties of the two sampled insulating oils from the transformers had been studied.
Keywords
Oil immersed transformer; Vegetable oil; Mineral oil; Corona inception voltage; AC breakdown voltage;
Citations & Related Records
연도 인용수 순위
  • Reference
1 L. Szepes, K. Torkos, R. Dobo, A. Szekely, "A New Analytical Method for the Determination of the Water Content of Transformer Oils", IEEE Trans. Elec. Insul., Vol. EI- 17, pp. 345-349, 1982.   DOI
2 H. Kawada, M. Honda, T. Inoue, T. Amemiya, "Partial Discharge Automatic Monitor for Oil-Filled Power Transformer", IEEE Trans. on Power Apparutus and System, Vol. PAS-103, pp 422-428, Feb. 2, 1984.   DOI
3 K. Rethmeier, M. Krvger, A. Kraetge, R. Plath, W. Koltunowicz, Obralic, Prof. W. Kalkner, "Experiences in On-site Partial Discharge Measurements and Prospects for PD Monitoring", CMD2008.
4 IEEE Standard C57.91:1995 "IEEE Guide for Loading Mineral-Oil-Immersed Transformers".
5 Dongnam Petroleum Ind. Co., Ltd., DONGNAM TRANS.
6 Dongnam Petroleum Ind. Co., Biotran-35.
7 JEC(Japanese Electrical Committee)-2200:1995 "Transformers".
8 J. H. Mason, "In Progress in Dielectrics", vol. 1. J. S. Birks, and J. H. Shulman, editors, London: Heywood and Co., 1959.
9 E. Kuffel, W.S. Zaengl, J. Kuffel, High Voltage Engineering Fundamentals, Newnes, Oxford,Ch.5, 2000.
10 IEC 60296 : 2012 "Fluids for electrotechnical applications - Unused mineral insulating oils for transformers and switchgear".
11 C. P. McShane, K. J. Rapp, J. L. Corkran, A. G. Gauger, J. Luksich, "Aging of Kraft Paper in Natural Ester Dielectric Fluid", Proceedings of 14th International Conference on Dielectric Liquids, Graz, Austria, pp. 173- 177, July 7-12, 2002.
12 M. Shirai, T. Ishii, M. Makino, "Evolution of Hydrogen from Insulating Oil in Transformers", IEEE Trans. Electr. Insul., Vol. 12, pp. 266-272, 1977.
13 C. P. McShane, G. A. Gauger, J. Luksich, CIRED 15th International conference on Electricity Distribution(Nice, France, Jung 1-4, 1999).