• Title/Summary/Keyword: Transformer Grounding Resistance

Search Result 4, Processing Time 0.021 seconds

A Study on the Grounding Resistance Effects of Power Transformer in Electric Distribution Systems (배전계통에서 전력용 변압기의 접지저항 영향에 관한 연구)

  • Kim, Kyung-Chul;Jung, Ji-Won;Lee, Kyu-Jin;Lee, Kang-Soo;Choi, Sun-Kyu
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.24 no.2
    • /
    • pp.113-119
    • /
    • 2010
  • A safe grounding design is used for providing means to carry electric currents into the earth under fault conditions without exceeding any operating limits and for assuring that a person in the vicinity of grounded facilities is not exposed to danger of critical electrical shock. Transformer neutral point grounding is for the purpose of controlling the voltage to earth within tolerable limits under a line-to-ground fault. Transformer frame grounding is for the purpose of minimizing the hazardous potential within safety criteria appearing at the faulted equipment. ills paper deeply investigates the grounding resistance effects of distribution power transformers by analysing the neutral to eatth voltages and touch voltages when the fault occurs.

Voltage Quality Analysis in Power Distribution System with Superconducting Fault Current Limiter at Grounding Line (초전도 한류기를 주변압기 접지선에 설치시 배전계통의 순간전압품질 분석)

  • Moon, Jong-Fil
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.62 no.4
    • /
    • pp.159-163
    • /
    • 2013
  • In this paper, voltage quality improvement is analyzed in case of Superconducting Fault Current Limiter (SFCL) installed in grounding line of main transformer in power distribution system. First, a resistive-type SFCL model is used. Next, Korean power distribution system is modeled. Finally, when SFCL is installed in the starting point of feeder and grounding line of main transformer, voltage qualities are evaluated according to various fault locations and resistance values of SFCL using PSCAD/EMTDC. The voltage quality results in case of grounding line are compared with the voltage in case of feeder.

Analysis on the Protective Coordination with Hybrid Superconducting Fault Current Limiter (저항접지 시스템에서 지락사고시 CLR과열 소손방지를 위한 GPT 정격용량의 적정성 연구)

  • Shin, Ho-Jeon;Kim, Jin-Seok;Park, Yu-Hwan;Kim, Jae-Chul;Cho, Man-Young
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.61 no.4
    • /
    • pp.503-508
    • /
    • 2012
  • Among the high distribution voltage consumers, high-capacity consumers are often applying the grounding resistance method in order to overcome demerits such as erroneous operation of the ground reply or potential increase in the battery at the accident of the isolated neutral system. In this paper, to prevent damage to CLR and GPT in the delay to block the breakdown in the resistance grounded neutral system, this study aims to provide a proper suggestion for continuous rating capacity of GPT to check the appropriateness of CLR size and reduce GPT burden. Thereupon, this study comparatively analyzes CLR current applied in general GPT and the current gained when CLR demanded in the system is used and analyzes the simulated system through simulation using PSCAD/EMTDC in order to suggest GPT's proper continuous rating capacity.

Analysis of Differential Protection for $3{\Phi}$ V-Delta Transformer consist of Three $1{\Phi}$ Transformers (단상변압기로 구성된 삼상 주변압기 보호시스템 분석)

  • Lee, Jong-Hweon;Jung, Woo-Joong;Shin, Seong-Sik;Lee, Hyung;Shin, Chang-Gyun
    • Proceedings of the KIEE Conference
    • /
    • 2006.07a
    • /
    • pp.298-299
    • /
    • 2006
  • This paper analyzes operation sensitivity of a relay, a blind spot of differential protection relaying, and how to protect the blind spot in protective relying of $3{\Phi}$ Y-Delta transformer consisting of three $1{\Phi}$ transformers which Korean pumped storage power plants have been using. Each different protective relayings must be adopted because there are differences between $3{\Phi}$ trans-former and $3{\Phi}$ transformer consisting of three $1{\Phi}$ trans formers. Also, in the system using high resistance grounding for fault current restriction of delta side, protection for delta side faults have to be considered properly.

  • PDF