• Title/Summary/Keyword: Time-frequency domain reflectometry

Search Result 70, Processing Time 0.022 seconds

Measurement of the Propagation Constant of a Power Cable Using a Two-Port Time-Domain Reflectometry Technique (Two-Port Time Domain Reflectometry 방법을 이용한 XLPE 전력용 케이블의 전파 특성 측정)

  • Shin, Dong Sik;Cho, Hyeon Dong;Park, Wee Sang;Yi, Sang-Hwa;Sun, Jong-Ho
    • The Journal of Korean Institute of Electromagnetic Engineering and Science
    • /
    • v.24 no.3
    • /
    • pp.310-315
    • /
    • 2013
  • This paper presents a two-port time-domain reflectometry(TDR) measurement technique for extracting the complex propagation constant of a cross-linked polyethylene(XLPE) cable. For the extraction, a short pulse transmitted through the cable is measured in the time domain and analyzed in the frequency domain. The propagation constant of a 22.9 kV XLPE cable with a conductor area of 325 $mm^2$ is extracted up to a frequency of approximately 2.14 GHz. The $S_{21}$ measured using a network analyzer and the two-port TDR technique are compared for verification. As a result compared with previous TDR method, the upper possible frequency limit for extracting the propagation constant increases and the measurement error decreases.

Reconstruction of the Electron Density Profile in O-mode Ultrashort Pulse Reflectometry using a Two-dimensional Finite Difference Time Domain

  • Roh, Young-Su
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.27 no.7
    • /
    • pp.52-58
    • /
    • 2013
  • The two-dimensional finite difference time domain algorithm is used to numerically reconstruct the electron density profile in O-mode ultrashort pulse reflectometry. A Gaussian pulse is employed as the source of a probing electromagnetic wave. The Gaussian pulse duration is chosen in such a manner as to have its frequency spectrum cover the whole range of the plasma frequency. By using a number of numerical band-pass filters, it is possible to compute the time delays of the frequency components of the reflected signal from the plasma. The electron density profile is reconstructed by substituting the time delays into the Abel integral equation. As a result of simulation, the reconstructed electron density profile agrees well with the assumed profile.

Wavelet Transform Based Time-Frequency Domain Reflectometry for Underground Power Cable (지중 전력 케이블에 대한 웨이블릿 변환 기반 시간-주파수 영역 반사파 계측법 개발)

  • Lee, Sin-Ho;Choi, Yoon-Ho;Park, Jin-Bae
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.60 no.12
    • /
    • pp.2333-2338
    • /
    • 2011
  • In this paper, we develope a wavelet transform based time-frequency domain reflectometry (WTFDR) for the fault localization of underground power cable. The conventional TFDR (CTFDR) is more accurate than other reflectometries to localize the cable fault. However, the CTFDR has some weak points such as long computation time and hard implementation because of the nonlinearity of the Wigner-Ville distribution used in the CTFDR. To solve the problem, we use the complex wavelet transform (CWT) because the CWT has the linearity and the reference signal in the TFDR has a complex form. To confirm the effectiveness and accuracy of the proposed method, the actual experiments are carried out for various fault types of the underground power cable.

Image Processing Based Time-Frequency Domain Reflectometry for Estimating the Fault Location Close to the Applied Signal Point (케이블 내 근접 결함 추정을 위한 영상 처리 기반의 시간 주파수 영역 반사파 계측법)

  • Jeong, Jong Min;Lee, Chun Ku;Yoon, Tae Sung;Park, Jin Bae
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.63 no.12
    • /
    • pp.1683-1689
    • /
    • 2014
  • In this paper, we propose an image processing based time-frequency domain reflectometry(TFDR) in order to estimate the fault location of a cable. The Wigner-Ville distribution is used for analysis in both the time domain and the frequency domain when the conventional TFDR estimates the fault location in a cable. However, the Winger-Ville distribution is a bi-linear function, and hence the cross-term is occurred. The conventional TFDR cannot estimate the accurate fault location due to the cross-term in case the fault location is close to the position where the reference signal is applied to the cable. The proposed method can reduce the cross-term effectively using binarization and morphological image processing, and can estimate the fault location more accurately using the template matching based cross correlation compared to the conventional TFDR. To prove the performance of the proposed method, the actual experiments are carried out in some cases.

Measurement on the permittivity and propagation velocity of used insulation oil at UHF Band using time domain reflectometry (TDR을 이용한 극초단파 대역에서 사용 절연유의 유전율과 전파속도 측정)

  • Goo, Sun-Geun;Ju, Hyoung-Jun;Park, Ki-Jun;Han, Ki-Seon;Yoon, Jin-Yul
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.57 no.11
    • /
    • pp.2011-2014
    • /
    • 2008
  • We measured the permittivity and electromagnetic wave propagation velocity of used insulation oil with wide frequency range including ultra-high frequency by time domain reflectometry. The permittivity or propagation velocity is essential for locating discharge faults of oil filled power transformer. We derived 2.21 as a permittivity and $2.03{\times}10^8 m/s$ as a velocity from the measurement of pulse travelling time along a coaxial line filled with used insulation oil or air. The permittivity measurement system we designed shows high measurement accuracy and the convenience for field use.

Development of Coupler for Live Cable Fault Detection Based on Reflectometry (반사파 계측법 기반의 활선 케이블 고장 검출을 위한 커플러의 개발)

  • Jeon, Jeong-Chay;Oh, Hun
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.17 no.9
    • /
    • pp.401-406
    • /
    • 2016
  • When measuring live cable faults and their location based on reflectometry, a coupler is placed between the cable and the test system. This coupler prevents damage to the test circuits by indirectly measuring the live voltage of the cable using reflectometry. It also provides a coupling path that allows the transmission and receive signal to pass into the cable. In this study, we design and construct a contact coupler to locate faults in both dead and live cables using reflectometry. The proposed coupler is of the inductive coupling type and is constructed after the calculation of the signal transmission loss by simulation. The performance of the developed coupler is tested by measuring the transmission loss and frequency flatness. The results showed that the transmission signal loss is less than -1.98dB in the frequency bandwidth above 1 Mhz. The reflectometry system was designed based on sequence time domain reflectometry (STDR) and spread spectrum time domain reflectometry (SSTDR) in order to apply it to the detection of faults and their location in live cables and tests on live cables were performed. The test results showed that the proposed coupler can be used in a reflectometry system for live cable fault detection.

A Study on the Determination of Dielectric Constant of Saturated Porous Media Using Frequency Domain Reflectometry System (Frequency Domain Reflectometry System을 이용한 포화 다공질매질의 유전율 측정을 위한 연구)

  • 김만일;정교철
    • The Journal of Engineering Geology
    • /
    • v.14 no.2
    • /
    • pp.179-187
    • /
    • 2004
  • This study conducted a laboratory work to determine the change of dielectric constant of saturated soil porous media, which is injecting EML to use Frequency Domain Reflectometry(FDR) system and length 7cm-length measurement sensor. It is purpose of study that estimate a movement path through pore of soil for an ethanol mixing liquid(EML) which have the same specific gravity of water at $20{\;}^{\circ}C$, and determine to a dielectric measuring range for the measurement sensor. As an outflow point of saturated soil column upper part recedes from an EML inject point in EML diffusion test, the diffusion extent of EML through pore of saturated soil was expanded. And results of ail EML flow experiment were measured the change of dielectric constant at all measurement sensors which are placed to constant interval at the same travel time for saturated soil column. Therefore, the displace process of water that exist in pore of saturated soil by EML injection is enough available and confirm together mobility through pores.

Multi-Impedance Change Localization of the On-Voltage Power Cable Using Wavelet Transform Based Time-Frequency Domain Reflectometry (웨이블릿 변환 기반 시간-주파수 영역 반사파 계측법을 이용한 활선 상태 전력 케이블의 중복 임피던스 변화 지점 추정)

  • Lee, Sin Ho;Choi, Yoon Ho;Park, Jin Bae
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.62 no.5
    • /
    • pp.667-672
    • /
    • 2013
  • In this paper, we propose a multi-impedance changes localization method of on-voltage underground power cable using the wavelet transform based time-frequency domain reflectometry (WTFDR). To localize the impedance change in on-voltage power cable, the TFDR is the most suitable among reflectometries because the inductive coupler is used to inject the reference signal to the live cable. At this time, the actual on-voltage power cable has multi-impedance changes such as the automatic section switches and the auto load transfer switches. However, when the multi-impedance changes are generated in the close range, the conventional TFDR has the cross term interference problem because of the nonlinear characteristics of the Wigner-Ville distribution. To solve the problem, the wavelet transform (WT) is used because it has the linearity. That is, using WTFDR, the cross term interference is not generated in multi-impedance changes due to the linearity of the WT. To confirm the effectiveness and accuracy of the proposed method, the actual experiments are carried out for the on-voltage underground power cable.

A Study on the Measurement of Dispersion Characteristic of Microwave Transmisson Line using FM Reflectometry (FM Reflectometry를 이용한 마이크로파 대역 전송선로의 분산특성 측정에 관한 연구)

  • 박용현;이정해
    • Proceedings of the Korea Electromagnetic Engineering Society Conference
    • /
    • 2000.11a
    • /
    • pp.99-103
    • /
    • 2000
  • 본 논문에서는 FM Reflectometry를 이용하여 마이크로파 대역에서 다양한 전송선로의 분산특성을 측정하였다. 실험에 사용된 전송선로는 도파관에 금속봉이 주기적으로 위치한 구조로서 Gyro-TWT의 iinteractio circuit으로 사용되기 위해서 설계되었다. 도파관에 금속봉이 주기적으로 위치한 구조의 group velocity를 측정하기 위해서 FM Reflectometry와 기존의 Network Analyzer Time Domain 기능이 사용되어졌으며, phase velocity를 측정하기위해 서 short metal plate를 이용한 방법과 High Frequency Structure Simulator (HFSS)가 이용되었다 측정된 결과는 이론치, 시뮬레이션과 비교했으며 각각의 비교는 잘 일치함을 보여 FM Reflectometry기법이 분산특성 측정에 사용되어질 수 있음을 보였다.

  • PDF

Intelligent Diagnosis System Based on Fuzzy Classifier (퍼지 분류기 기반 지능형 차단 시스템)

  • Sung, Hwa-Chang;Park, Jin-Bae;So, Jea-Yun;Joo, Young-Hoon
    • Journal of the Korean Institute of Intelligent Systems
    • /
    • v.17 no.4
    • /
    • pp.534-539
    • /
    • 2007
  • In this paper, we present the development of an intelligent diagnosis system for detecting faults of the low voltage wires. The wire detecting system based on the Time-Frequency Domain Reflectometry (TFDR) algorithm shows the condition of the wires. We analyze the reflected signal which is sent from the wire detecting system and classify the fault type of the wires by using the intelligent diagnosis system. Through the TFDR, generally, the conditions of the wires are classified into the three types - damage, open and short. In order to classify the fault type efficiently, we use the fuzzy classifier which is represented as IF-THEN rules. Finally, we show the utility of the proposed algorithm by performing the simulation which is based on the data of the coaxial cable.