• 제목/요약/키워드: Telecommunication system cooling

검색결과 19건 처리시간 0.023초

교환기실의 급배기방식에 따른 통신 시스템의 냉각 특성 (Cooling characteristics of the telecommunication system in a switching room for various air supply and return flow system)

  • 노홍구;이재헌;고철균
    • 설비공학논문집
    • /
    • 제11권5호
    • /
    • pp.669-683
    • /
    • 1999
  • Heat dissipation in the domestic switching room has been gradually increased. Therefore, numerical study on the cooling characteristics of the telecommunication system in a switching room for three kinds of the air supply and return flow system was investigated to develop effective flow system. As a result, the cooling performance of the under floor air supply and overhead return flow system was the best.

  • PDF

잠열재를 이용한 통신 캐비넷용 Passive 냉각시스템 개발 (Development of Passive Cooling System for Communication Cabinet by Latent Heat Material.)

  • 정동열;박승상;백종현
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2009년도 하계학술발표대회 논문집
    • /
    • pp.1385-1390
    • /
    • 2009
  • In this study the purpose is development of passive cooling system for telecommunication cabinet used by latent heat material. This cooling system is not required for electronic power. It was tested for the performance of the telecommunication combined latent heat material with $48^{\circ}C$ of phase changed temperature and heat pipe. At $45^{\circ}C$ of outside temperature, when heater power was 1,000 W and 1,500 W, the inside temperature of the cabinet was $55^{\circ}C$ and $62^{\circ}C$. This system was showed better performance than the other systems.

  • PDF

통신장비용 공냉형 냉각시스템의 성능 특성에 대한 실험적 연구 (Experimental Study on the Performance of an Air-Cooling System for Telecommunication Equipment)

  • 전종욱;최종민;허재혁;김용찬
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2005년도 동계학술발표대회 논문집
    • /
    • pp.323-328
    • /
    • 2005
  • The objective of this study is to analyze the cooling performance of an air- cooling system for telecommunication equipment. Temperature variation and capacity were measured in an actual unit for telecommunication equipment. In addition, the cooling performance was measured by installing a silicon rubber heater as a heat source in a cabinet. The standard thermal load for telecommunication equipment was approximately 293 W, and the maximum temperature of the heated surface was $64.5^{\circ}C$. The average and maximum temperatures of the heated surface were proportional to the inlet air temperature. When the heat load increased from 293 W to 400 W, the maximum temperature of the heated surface was higher than $64.5^{\circ}C$ even though the inlet air temperature decreased from 25 to $11^{\circ}C$.

  • PDF

통신기기 냉각용 하이브리드 냉방시스템의 성능특성 (Cooling Performance of a Hybrid Refrigeration System for Telecommunication Equipment)

  • 전종욱;김용찬;최종민
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2006년도 하계학술발표대회 논문집
    • /
    • pp.489-494
    • /
    • 2006
  • Electronic and telecommunication industries are constantly trying to develop compact components having high power density. Therefore, a proper heat dissipation method is very important to allow reliable operation of the telecommunication equipment. In this study, a hybrid refrigeration system for a telecommunication equipment room was designed to save energy consumption and improve reliability of the compressor In addition, the performance of the hybrid refrigeration system was measured with a variation of outdoor load. The designed hybrid refrigeration system for the telecommunication equipment shelter saved the energy approximately 50%e at the mode switch temperature of $8.3^{\circ}C$.

  • PDF

MPCM을 적용한 액냉형 냉각기의 성능 특성에 관한 연구 (Performance Characteristics of Liquid-Cooling Heat Exchangers with MPCM Slurry Designed for Telecommunication Equipment)

  • 전종욱;김용찬;최종민;현동수;윤린
    • 설비공학논문집
    • /
    • 제19권10호
    • /
    • pp.710-717
    • /
    • 2007
  • Electric and telecommunication industries are constantly striving towards miniaturization of electronic devices. Miniaturization of chips creates extra space on PCBs that can be populated with additional components, which decreases the heat transfer surface area and generates very high heat flux. Even though an air-cooling technology for telecommunication equipment has been developed in accordance with rapid growth in electrical industry, it is confronted with the limitation of cooling capacity due to the rapid increase of heat density. In this study, liquid-cooling heat exchangers with MPCM slurries were designed and tested by varying geometry and operating conditions. The liquid-cooling heat exchangers with 4-paths showed higher cooling performance than the others. The cooling performance of liquid cooling heat exchanger with MPCM slurries was more enhanced than that of the air cooling system. It's performance was also slightly superior to that of the water cooling system at the inlet temperature of $19^{\circ}C$.

전자장비 캐비넷의 냉각특성에 관한 실험적 연구 (An experimental study on the cooling characteristics of electronic cabinet)

  • 박종흥;이재헌
    • 대한기계학회논문집B
    • /
    • 제20권7호
    • /
    • pp.2356-2366
    • /
    • 1996
  • High-power electronic chips have been advanced to such an extent that the heat dissipation capability of a system design has become one of the primary limiting factors. Therefore, thermal design must be considered in the early stage of the electronic system development. In present paper, the results of an experimental study on the forced convection cooling are presented to evaluate cooling performance of an electronic cabinet which in generally used for telecommunication system. Temperatures and thermal resistances are applied to compare the heat transfer characteristics for various locations of a fan unit as well as various configuration of non-uniform powering modules. As a result, the optimal configuration of a fan unit and powering configuration is suggested for the effective thermal design of telecommunication system.

열전소자를 이용한 전자 통신장비 냉각에 관한 연구 (A Study on the Application of Thermoelectric Module to the Electric Telecommunication Equipment Cooling)

  • 김종수;임용빈;공상운
    • 수산해양교육연구
    • /
    • 제16권2호
    • /
    • pp.210-217
    • /
    • 2004
  • Cooling technology has been a vital prerequisite for the rapid, if not explosive, growth of the electronic equipment industry. This has been especially true during the last 20 years with the advent of intergrated circuit chips and their applications in computers and related electronic products. The purpose of this study is to develop a telecommunication equipment cooling system using a thermoelectric module combined with cooling fan. Thermoelectric module is a device that can perform cooling only by input of electric power. In the present study, the cooling package using the thermoeletric module has been developed to improve the thermal performance. The cooling characteristics of the electronic chip was placed into the subrack and it can be rapidly assembled or disassembled in the equipment rack. As a preliminary experiment, the cooling performances between a conventional way using a cooling fin and a proposed method applying the thermoelectric module was comosed and analyzyed. The cooling performance at a simulated electronic component packaging a thermomodule operated well.

히트파이프 열교환기를 이용한 전자통신 시스템의 냉각 설계기술 개발 (Development of Cooling Design Technique for an Electronic Telecommunication System Using HPHE)

  • 이정환;유성열;전지환;김종만;김현준;김철주;서명원
    • 대한기계학회논문집B
    • /
    • 제31권4호
    • /
    • pp.367-375
    • /
    • 2007
  • The purpose of this study is to investigate the cooling performance of Heat Pipe Heat Exchanger(HPHE) for an electronic telecommunication system by adequate convection condition. Heat generation rates of electronic components, the temperature distributions of HPHE and surrounding air are analyzed experimentally and numerically. In order to perform the heat transfer analysis for the thermal design of telecommunication system, a program is developed. The program is useful to a user who is not familiar with an electronic telecommunication system. The simulation results showed that the HPHE were able to achieve a cooling capacity of up to 230W at the maximum temperature difference of $17.4^{\circ}C$. To verify the results from the numerical simulation, an experiment was conducted under the same condition as the numerical simulation, and their results were compared.

통신기지국용 하이브리드 냉방기의 성능특성 연구 (Performance Characteristics of a Hybrid Air-Conditioner for Telecommunication Equipment Rooms)

  • 김용찬;최종민;강훈;윤준상;김영배;최광민;이호성
    • 설비공학논문집
    • /
    • 제18권11호
    • /
    • pp.874-880
    • /
    • 2006
  • The power density and heat dissipation rate per unit area of the telecommunication equipment have been increased with the technology development in the footprint of telecommunication hardware. A proper heat dissipation method from the PCB module is very important to allow reliable operation of its electronic component. In this study, a hybrid air-conditioner for the telecommunication equipment room was designed to save energy and obtain system reliability. For high outdoor temperatures, the hybrid system operates in the vapor compression cycle, while, for low outdoor temperatures, the hybrid system works in the secondary fluid cooling cycle with no operation of the compressor. The performance of the hybrid air-conditioner was measured by varying outdoor and indoor temperatures. The hybrid air-conditioner yielded 50% energy saving compared with the conventional refrigeration system when the mode switch temperature was $8.3^{\circ}C$.

진동 세관형 히트파이프를 이용한 통신 기기용 마이크로 냉각시스템의 개발 (Development of Micro Cooling System for Telecommunication System using Oscillating Heat Pipe)

  • 하수정;배내수;박철민;김종수
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2003년도 춘계학술대회
    • /
    • pp.1499-1505
    • /
    • 2003
  • Rapid development of electronic technology requires small size, high density packaging and high power of electronic devices. So, in this paper, characteristics on oscillating heat pipe according to operating conditions(environment temperature, charging ratio of working fluid, inclination) based on experimental study was investigated. From the experimental results, $25^{\circ}C$environment temperature), R-141b(working fluid)40%(charging ratio) was best performace at others of inclination angle and The top heating mode of OCHP performed 80% efficiency of the bottom heating mode.

  • PDF