• 제목/요약/키워드: Telecommunication equipment

검색결과 168건 처리시간 0.042초

5ESS-2000 통신장비실의 열환경특성과에너지성능 개선방안에 관한 연구 (A Study on the Characteristics of Thermal Environment and Improvement of Energy Performance in 5ESS-2000 Telecommunication Equipment Room)

  • 이승복;조춘식
    • KIEAE Journal
    • /
    • 제4권4호
    • /
    • pp.19-26
    • /
    • 2004
  • The purpose of this study was to evaluate the thermal environment of present state and energy consumption and to verify the improvement of energy performance applying free cooling in 5ESS-2000 telecommunication equipment room. Analysis program is used the DOE-2.1E and commercial CFD code, Star-CD. The results of the simulation show that free cooling could reduce 42.1% of cooling energy, increase 48.5% of heating energy because introduced outdoor air must heating and humidification. Therefore free cooling could reduce yearly 34,609.9 kWh of heating and cooling energy and this is reaching to 21.6% of total energy.

Performance Comparison of Liquid-Cooling with Air-Cooling Heat Exchangers Designed for Telecommunication Equipment

  • Jeon, Jong-Ug;Choi, Jong-Min;Heo, Jae-Hyeok;Kang, Hoon;Kim, Yong-Chan
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • 제16권2호
    • /
    • pp.64-69
    • /
    • 2008
  • Electronic and telecommunication industries are constantly striving towards miniaturization of electronic devices. Miniaturization of chips creates extra space on PCBs that can be populated with additional components, which decreases the heat transfer surface area and generates very high heat flux. Even though an air-cooling technology for telecommunication equipment has been developed in accordance with rapid growth in electrical industry, it is confronted with the limitation of cooling capacity due to the rapid increase of heat density. In this study, liquid-cooling heat exchangers were designed and tested by varying geometry and operating conditions. In addition, air-cooling heat exchangers were tested to provide performance data for the comparison with the liquid-cooling heat exchangers. The liquid-cooling heat exchangers had twelve rectangular channels with different flow paths of 1, 2, and 12. Silicon rubber heaters were used to control the heat load to the heat exchangers. Heat input ranged from 293 to 800W, and inlet temperatures of working fluid varied from 15 to $27^{\circ}C$. The heat transfer coefficients were strongly affected by flow conditions. All liquid-cooling heat exchangers showed higher cooling performance than the air-cooling heat exchanger. The heat exchanger with 2-paths could provide more controllability on the maximum temperature than the others.

GPS 및 무선통신을 이용한 철도신호설비 기능향상 (Improvement of the Railroad Signalling Equipment using GPS and Wireless Telecommunication)

  • 최규형;최대섭
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2004년도 춘계학술대회 논문집
    • /
    • pp.460-462
    • /
    • 2004
  • This paper gives a basic data of improving the performance of railroad signalling equipment by adopting GPS and wireless telecommunication technologies. These approach enable the moving block control of train, which can optimize train operation by reducing the distance between trains and maximize the railroad capacity. These method of detecting train position and controling train movement can also improve the train route control at stations.

  • PDF

통신용 전원 집중관리 시스팀 (Centralized Management System for Telecommunication Power Equipment)

  • 조일권;민병록;박경규;안치홍
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1997년도 하계학술대회 논문집 B
    • /
    • pp.603-605
    • /
    • 1997
  • The systematic and efficient operation of telecommunication power equipments is very important to the safe operation of telecommunication system. To achive that, Korea Telecom has developed a new centralized management system for telecommunication power equipments. The system configuration and main functions for the new developed system are described in this paper.

  • PDF

Bidirectional Alarm Equipment for Protection for Trackside Worker using Bone-anchored Speaker

  • Hwang, Jong-Gyu;Jo, Hyun-Jeong
    • International Journal of Safety
    • /
    • 제10권1호
    • /
    • pp.36-40
    • /
    • 2011
  • Personnel maintaining or repairing the railway tracks or signaling facilities around tracks may experience the sensory disorder when doing maintenance works at the trackside of railway for long time. In this case personnel maintaining at the trackside may collide with the train since they cannot recognize the approach of motor-car although it approaches to the vicinity of maintenance workplace because of the sensory block phenomenon occurred due to their long hours of continued monotonous maintenance work. In order to prevent such motor-car accidents that may occur because railway track workers are unable to recognize the approaching train, the safety alarm equipment is developed to make the approaching motor-car send radio signals and bidirectional detection mechanism between approaching train and trackside personnel. It shows the possibility of utilization in various forms of safety equipment for workers only to the safety helmet to be worn by the maintenance workers while using the configuration of transmitting/receiving sides. In the paper it is represented new alarm equipment, which is the bone-anchored speaker-based safety helmet to be worn by the maintenance workers.

  • PDF

PST측면에서의 과전류 보호용PTC 소자의 개념 정립 및 Failure-Mode 분석 (The Conception & Fail-Mode Analysis of PTC Thermistor for Over-Current Protection)

  • 박준호
    • 대한안전경영과학회:학술대회논문집
    • /
    • 대한안전경영과학회 2001년도 춘계학술대회
    • /
    • pp.67-75
    • /
    • 2001
  • Circuitry to be connected to a Telecommunication Network consists of SELV CIRCUITS or TNV CIRCUITS. So International Standards, like as ITU-T Recommendation K.11, UL 1950, CSA C22.2 950 have been taken to reduce the risk that the Overvoltages from the power lines and from electrictraction lines, that may be received from the telecommunication network. Legal requirements may exist regarding permission to connect equipment having PTC components to a telecommunication network. Surge suppressors that bridge the insulation shall have a minimum d.c. sparkover voltage of 1.6 times the rated voltage or 1.6 times the upper voltage of the tared voltage range of the equipment. If left in place during electric strength testing of insulation, they shall not be damaged. In this work, The Conception & Fail-Mode Analysis of PTC components for Over-Current Protection is proposed. It guarantees the protection for PL Claim about this Subject.

  • PDF

네트워크 프로세서를 사용한 고성능 IP-DiffServ/IP-MPLS 시스템 구조 (High Performance System Architecture for IP-DiffServ/IP-MPLS Using Network Processor)

  • 박준석;이광용
    • 한국정보통신설비학회:학술대회논문집
    • /
    • 한국정보통신설비학회 2003년도 하계학술대회
    • /
    • pp.240-243
    • /
    • 2003
  • 본 논문에서는 Agere Systems사의 네트워크 프로세서를 사용한 고성능 IP-DiffServ/IP-MPLS 시스템의 구조를 제안하고 성능을 분석한다. 제안한 시스템은 기가비트 이더넷 뿐만 아니라 ATM과 POS 등 다양한 인터페이스를 제공하며 코어 및 에지 라우터로서 MPLS LER 또는 LSR로의 역할을 수행한다. 성능분석은 OPNET을 사용하여 시스템을 모델링한 후 입력 트래픽에 대해서 DiffServ 클래스별 지연시간과 지연의 주된 원인을 분석한다. 그리고 이를 바탕으로 시스템의 성능을 극대화할수 있는 네트워크 프로세서의 최적 파라메터를 도출한다. 성능분석 결과, 시스템이 각 서비스 클래스에 대해서 원활한 서비스를 제공하기 위해서는 프리미엄 서비스에는 최고의 우선순위를 부여하여 큐에 데이터 블럭들이 찰 때 마다. 즉시 서비스해 주어야 한다는 것을 알 수 있었다. 그리고 트래픽이 특정 출구 라인카드로 몰리는 핫스팟이 발생할 경우 트래픽의 지연이 증가하게되는데 이 지연의 주요 원인은 출구 라인카드에서의 큐잉에 의한 것임을 알 수 있었다.

  • PDF

2.3Ghz 대역 휴대 인터넷 서비스의 특징 및 전망 (Features and Prospects of 2.3GHz Portable Internet Service)

  • 조원상;김상구;김희동
    • 한국정보통신설비학회:학술대회논문집
    • /
    • 한국정보통신설비학회 2003년도 하계학술대회
    • /
    • pp.249-252
    • /
    • 2003
  • 2.3GHz 대역을 활용하는 초고속 무선 인터넷 서비스는 국가적으로 미래 통신인프라의 방향을 제시한다는 점에서 현재 크게 관심을 갖게 하는 서비스이다. 휴대 인터넷 서비스는 무선랜과 이동통신 무선 서비스를 보완하는 서비스로써 높은 주파수 효율을 가지고 있으며 저렴한 가격으로, 이동 중에도 $1{\sim}4Mbps$의 빠른 속도를 지원할 수가 있는 서비스를 제공한다. 또한 간단한 망 구조로 투자비를 낮출 수 있다. 이에 본 논문에서는 초고속 휴대인터넷 서비스에 대하여 개괄하고, 휴대인터넷 서비스의 종류와 현재 동향 그리고 LG 전자에서 설치한 어레이콤사의 i-Burst시스템의 특징 및 장점을 고찰하고 향후 발전 방향을 알아본다.

  • PDF

통신 시설물의 상면 및 배선 설계관리 방안에 관한 연구 (The research on the design and management on space and wiring of telecommunication equipment)

  • 정현호;민경선;이용기;이영욱;김병재
    • 한국정보통신설비학회:학술대회논문집
    • /
    • 한국정보통신설비학회 2004년도 하계학술대회
    • /
    • pp.234-236
    • /
    • 2004
  • 현재 전화국 통신 시설물에 대한 상면 배치 및 배선의 설계와 공사 업무의 관리는 2차원 도면 설계 툴과 별도의 물자 산출 툴에 의해 수행되고 있다. 사용자 편의를 고려한 3차원 도면 설계 툴이 있기는 하지만 통신 시설물 공사에 최적화된 툴은 없으며 주로 기계 설계나 금형 설계 작업에서 부분적으로 사용되고 있는 실정이다. 본 논문에서는 실제 환경에 가까운 3차원 그래픽 사용자 인터페이스에 의한 도면 설계 기능, 설계된 도면 DB와 물자 단가 DB의 연동을 통한 소요 물자의 자동 산출 기능 등을 수행하는 시스템 모델의 개념을 제시하고 개발 현황을 소개하고자 한다. 본 논문에서 소개된 시스템을 통해 전화국 통신 시설물에 대한 설계와 공사 업무의 편리화, 자동화, 일원화를 이룰 수 있을 것이다.

  • PDF

Development of Safety Equipment using Laser Radar Sensor for Railway Platform

  • Hwang, Jong-Gyu;Kim, You-Ho;Jo, Hyun-Jeong;Choi, Kwon-Hee;Ko, Tae-Kuk
    • International Journal of Safety
    • /
    • 제9권2호
    • /
    • pp.35-40
    • /
    • 2010
  • Many casualties are being occurred due to many misses the railway platform, and the accident occurrence is being increased. Recently in Korea, efforts to prevent casualties fundamentally are being made by installing and operating the PSD(Passenger Screen Door) as to prevent these casualties of passengers. However, in case of the PSD system, although it can solve the problem of public casualties at platform fundamentally, it is impossible to install it at whole railway platforms. This paper proposes the safety equipment using LaserRadar sensor for the prevention against casualties of passengers at platform. The safety equipment using novel sensor is the safety equipment making an approaching train stopped if the falling object is a person by detecting the obstacle at platform, and it has the merit possible to apply it to platform since it may detect accurately under ambient environmental elements such as the snow, rain and yellow dust, etc. also. We manufactured a prototype of the safety equipment to reduce public casualties at platform by using LaserRadar sensor and carried out its performance test, and the result is presented in this paper.