Electric Safety Protection Device of High Speed for Incapable Operation of ELB and MCCB Using the Low Voltage Distribution Line (저압 배전선로의 누전 및 배선용 차단기의 오동작 방지를 위한 고속형 전기안전 보호장치)

  • Kwak, Dong-Kurl;Jung, Do-Young
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.56 no.11
    • /
    • pp.1925-1929
    • /
    • 2007
  • This paper is studied on a novel Electric Safety Protection Device (ESPD) of high speed for incapable operation of Earth Leakage Circuit Breaker (ELB) and Molded_case Circuit Breaker (MCCB) using the low voltage distribution line. The major causes of electrical fire are classified to short circuit fault, overload fault, electric leakage and electric contact failure. The occurrence factor of the fire is electric arc or spark accompanied with electrical faults. Residual Current Protective Device (RCD), that is ELB and MCCB, of high sensitivity type used at low voltage wiring cuts off earth leakage and overload, but the RCD can't cut off electric arc or spark to be a major factor of electrical fire. As the RCDs which are applied low voltage distribution panel are prescribed to rated breaking time about 30[ms] (KS C 4613), the RCDs can't perceive to the periodic electric arc or spark of more short wavelength level. To be improved on such problem, this research development is proposed to a novel ESPD of high speed to trip of distribution line on electric arc or spark due to electrical fire. Some experimental results of the proposed ESPD are confirmed to the validity of the analytical results.

A Study on Electrical Fire Disaster Prevention Device used in Double Circuit Break (고정밀 전류센서를 이용한 이중 차단용 전기화재 방재장치에 관한 연구)

  • Park, Dong-Pil;Kwak, Dong-Kurl;Jung, Do-Young;Kim, Choon-Sam;Shin, Ho-Joon
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.2102-2103
    • /
    • 2008
  • The major causes of electrical fire are classified to short circuit fault, overload fault, electric leakage and electric contact failure. The occurrence factor of the fire is electric arc or spark accompanied with electrical faults. Residual Current Protective Device(RCD) of high sensitivity type used at low voltage wiring cuts off earth leakage and overload, but the RCD can't cut off electric arc or spark to be a major factor of electrical fire. As the RCDs which are applied low voltage distribution panel are prescribed to rated breaking time about 30[ms](KS C 4613), the RCDs can't perceive to the periodic electric arc or spark of more short wavelength level. To be improved on such problem, this paper is proposed to a electrical fire disaster prevention device(EFDPD) for a RCD trip or a self circuit-breaking function on electric arc or spark due to electrical fire. Some experimental results of the proposed apparatus is confirmed to the validity of the analytical results.

  • PDF

A Study on Auxiliary Control Safety Apparatus for RCD Trip on Electric Arc and Spark Disasters - Using by Power Semiconductor Switching Device - (아크 및 스파크 재해에 대한 누전차단기 트립을 위한 보조제어 전기안전장치에 관한 연구 - 전력용 반도체 스위칭 소자 적용 및 응용 -)

  • Kwak, Dong-Kurl;Shin, Mi-Young;Jung, Do-Young
    • Fire Science and Engineering
    • /
    • v.20 no.1 s.61
    • /
    • pp.71-76
    • /
    • 2006
  • The major causes of electrical fire are classified to short circuit fault, overload fault, electric leakage and electric contact failure. The occurrence factor of the fire is electric arc or spark accompanied with electrical faults. Residual Current Protective Device(RCD) of high sensitivity type used at low voltage wiring cuts off earth leakage and overload, but the RCD can't cut off electric arc or spark to be a major factor of electrical fire. As the RCDs which are applied low voltage distribution panel are prescribed to rated breaking time about 30[ms](KS C 4613), the RCDs can't perceive to the periodic electric arc or spark of more short wavelength level. To be improved on such problem, this paper is proposed to a auxiliary control apparatus for RCD trip on electric arc or spark due to electrical fire. Some experimental results of the proposed apparatus is confirmed to the validity of the analytical results.

Development of Arc Fault Circuit Interrupter Using the Distorted Voltage Wave in Electric Arc Faults (아크사고 발생 시 전압 왜형파를 이용한 아크차단기 개발)

  • Kwak, Dong-Kurl
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.62 no.6
    • /
    • pp.876-880
    • /
    • 2013
  • The major causes of electrical fire are classified to short circuit fault, overload fault, electric leakage and electric contact failure. The principal factor of the fire is electric arc or spark accompanied with such electric faults. Earth Leakage Circuit Breaker (ELB) and Molded_case Circuit Breaker (MCCB), that is, Residual Current Protective Devices (RCDs) used on low voltage distribution lines cut off earth leakage and overload, but the RCD can not cut off electric arc or spark to be a major factor of electrical fire. As the RCDs which are applied in low voltage distribution panel are prescribed to rated breaking time about 30[ms] (KS C 4613), the RCDs can't perceive to the periodic electric arc or spark of more short wavelength level. To improve such problems, this paper studies on an arc fault circuit interrupter (AFCI) using the distorted voltage wave in electric arc faults. The proposed voltage sensing type AFCI is an electrical fire prevention apparatus of new conception that operates a circuit breaker with sensing the instantaneous voltage drop of line voltage at electrical faults occurrence. The proposed AFCI is composed of control circuit topology using some semiconductor switching devices. Some experimental tests of the proposed AFCI confirm practicality and the validity of the analytical results.

A Study on Protection Device for Electrical Fire Prevention on Joint/Contact Badness Faults (접속·접촉불량 사고에 의한 전기화재 방지용 보호장치에 관한 연구)

  • Choi, Jung-Kyu;Kwak, Dong-Kurl;Lee, Seung-Chul;Lee, Bong-Seob;Park, Young-Jic
    • Proceedings of the KIPE Conference
    • /
    • 2014.07a
    • /
    • pp.5-6
    • /
    • 2014
  • According to 2013 fire statistical yearbook in the National Emergency Management Agency, the main cause of an electrical fire are classified to short circuit fault, overload fault, electric leakage, partial disconnection, and joint/contact badness. The occurrence factor of fire is electric arc or spark accompanied with electrical faults. Residual Current Protective Devices(RCDs) of high sensitivity type used at single phase (220V) cut off earth leakage and overload but the RCDs can not cut off electric arc or spark to be a main cause of electrical fire. To be improved on such problem, this thesis is proposed to a auxiliary control device for RCD cut off electric arc or spark.

  • PDF

Analysis of Characteristics of Electrical Arc Spark Detector (전기화재 아크.스파크검출기 특성평가에 관한 연구)

  • 정용기;신효섭;지철근;김영수
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2002.11a
    • /
    • pp.375-378
    • /
    • 2002
  • An arc/spark detector (ASD) was developed is to early detect wire failures and insecure connections that may lead to fire in residents and commercial and industrial facilities. A detailed circuit design for ASD implementation along with prototype product is reported. The tests of ASD, which were successful in phase identification, in many different arc/spark locations under different loadings, and in false alarm probability, showed the ability and capability of the state-of-the-art detector in the electric fire hazard prevention.

  • PDF

A Study on Dynamic Characteristics of EFPCD for Conductor Breaks in Low Voltage Wiring (저압배선 선로의 단선사고 발생시 전기화재예방 제어장치(EFPCD)의 동작 특성에 관한 연구)

  • 이상호;신미영;이경호
    • Fire Science and Engineering
    • /
    • v.18 no.3
    • /
    • pp.103-107
    • /
    • 2004
  • Recently. the spark and the overheat due to in the conductor breaks have been the major causes of electrical fire in low voltage wiring. Also, because in these cases the current is a surge one, the losses and faults of a communication, a home appliances, a computer and a measuring instrument may occur. Especially, in such cases, we are very difficult to detect the condition of the conductor breaks. In this paper, we have developed an auxiliary control device, the electrical fire prevention control device (EFPCD), of an earth leakage breaker (ELB). And we can prevent the electrical fire caused by the spark and the overheat occurring in the conductor breaks with the EFPCD.

A Study on Dynamic Characteristics of EFPCD for Electrical Fire Prevention (전기화재 예방을 위한 EFPCD동작 특성에 관한 연구)

  • 이상호;오홍석
    • Fire Science and Engineering
    • /
    • v.16 no.3
    • /
    • pp.8-11
    • /
    • 2002
  • Recently, the spark and the overheat due to in the failure of pressure contacts on connecting points and the momentary short circuit have been the major causes of electrical fire because these may cause the deposition and the graphite of insulating materials in electrical wiring system. Also, because in these cases the current is a surge one, the losses and faults of a communication, a home appliances, a computer and a measuring instrument may occur. Especially, in such cases, we are very difficult to detect the failure of pressure contacts on connecting points and the momentary short circuit. In this paper, we have developed an auxiliary control device, the electrical fire prevention control device(EFPCD), of an earth leakage breaker(ELB). And we can pre-vent the electrical fire caused by the spark and the overheat occurring in the failure of pressure contacts in connecting points and the momentary short circuit with the EFPCD.

Development of Prevention Apparatus for Short-Circuit Faults Using the Line Voltage Drop of Neutral Wire (중성선 선로 전압강하를 이용한 단락사고 방지용 보호장치 개발)

  • Kwak, Dong-Kurl;Kim, Jin-Hwan;Lee, Bong-Seob
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.61 no.12
    • /
    • pp.1953-1958
    • /
    • 2012
  • The major causes of electrical fire are classified to short circuit fault, overload fault, electric leakage and electric contact failure. The occurrence factor of the fire is electric arc or spark accompanied with such electric faults, specially short circuit faults. Earth Leakage Circuit Breaker (ELB) and Molded_case Circuit Breaker (MCCB), that is, Residual Current Protective Devices (RCDs) used on low voltage distribution lines cut off earth leakage and overload, but the RCD can not cut off electric arc or spark to be a major factor of electrical fire. As the RCDs which are applied in low voltage distribution panel are prescribed to rated breaking time about 30ms(KS C 4613), the RCDs can't perceive to the periodic electric arc or spark of more short wavelength level. To improve such problem, this paper proposes a prevention apparatus using the line voltage drop of neutral wire and some semiconductor switching devices. Some experimental tests of the proposed apparatus confirm the validity of the analytical results.

Development of electric safety control system for incapable operation of ELB and MCB using the low voltage distribution line (저압 배전선로의 누전 및 배선용 차단기의 오동작 방지를 위한 전기안전 제어장치 개발)

  • Kwak, Dong-Kurl;Shin, Mi-Young;Jung, Do-Young;Kim, Hyo-Jin;Baek, Seong-Hyun;Choi, Byung-Seub
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.371-372
    • /
    • 2007
  • The major causes of electrical fire are classified to short circuit fault, overload fault, electric leakage and electric contact failure. The occurrence factor of the fire is electric arc or spark accompanied with electrical faults. Residual Current Protective Device (RCD), that is Earth Leakage Circuit Breaker(ELB) and Molded_case Circuit Breaker (MCB), of high sensitivity type used at low voltage wiring cuts off earth leakage and overload, but the RCD can't cut off electric arc or spark to be a major factor of electrical fire. As the RCDs which are applied low voltage distribution panel are prescribed to rated breaking time about 30[ms] (KS C 4613), the RCDs can't perceive to the periodic electric arc or spark of more short wavelength level. To be improved on such problem, this research development is proposed to a auxiliary control apparatus for RCD trip on electric arc or spark due to electrical fire. Some experimental results of the proposed apparatus is confirmed to the validity of the analytical results.

  • PDF