A Study on Electrical Fire Disaster Prevention Device used in Double Circuit Break

고정밀 전류센서를 이용한 이중 차단용 전기화재 방재장치에 관한 연구

  • Published : 2008.07.16

Abstract

The major causes of electrical fire are classified to short circuit fault, overload fault, electric leakage and electric contact failure. The occurrence factor of the fire is electric arc or spark accompanied with electrical faults. Residual Current Protective Device(RCD) of high sensitivity type used at low voltage wiring cuts off earth leakage and overload, but the RCD can't cut off electric arc or spark to be a major factor of electrical fire. As the RCDs which are applied low voltage distribution panel are prescribed to rated breaking time about 30[ms](KS C 4613), the RCDs can't perceive to the periodic electric arc or spark of more short wavelength level. To be improved on such problem, this paper is proposed to a electrical fire disaster prevention device(EFDPD) for a RCD trip or a self circuit-breaking function on electric arc or spark due to electrical fire. Some experimental results of the proposed apparatus is confirmed to the validity of the analytical results.