• Title/Summary/Keyword: Smoke control system

Search Result 234, Processing Time 0.026 seconds

A Study On Effectiveness of Prevent Smoke Backflow in Apartment (계단식 공동주택 방연풍속 실효성에 대한 연구)

  • Lee, Kwang­Soo;Yoon, Myong­O;Lee, Jun
    • Journal of the Society of Disaster Information
    • /
    • v.17 no.1
    • /
    • pp.1-9
    • /
    • 2021
  • Purpose: The purpose of this study is to analyze the differential pressure and velocity to prevent smoke backflow of Stairways Apartment House fire, and verified the effectiveness of smoke velocity standards proposed by NFSC 501A. Method: The smoke control design of the stairways apartment house of the real model and the performance of the velocity to prevent smoke backflow according to the window opening conditions of the living room were analyzed using the CONTAM program. Result: Although the differential pressure performance of the apartment's smoke control system was satisfactory, it was found that Performance of velocity to prevent smoke backflow did not come out according to the opening condition of the living room window. Conclusion: In the case of Stairways Apartment House, it is necessary to review the method of making exceptions to the 'velocity to prevent smoke backflow' standard required by the National Fire Safety Codes(NFSC 501A)

A study on the application of improved IoT- based smoke control system to lodging facilities fires (개선된 IoT기반 제연시스템의 숙박시설 적용에 관한 연구)

  • Kim, Suyong;Lee, Sangsoo;Lee, Sung-Hwa;Kim, Jin-Tae
    • The Journal of the Institute of Internet, Broadcasting and Communication
    • /
    • v.21 no.5
    • /
    • pp.113-118
    • /
    • 2021
  • The study is to provide safety to the occupants from smoke generated by fire occurring at midnight, and to provide a method for providing evacuation safety for a certain period of time even if the occupants are not aware of the fire. The goal of this study is to occur in small accommodation (floor area less than 1,000m2)It is to design a system that can provide ASET for more than 1 hour even if the occupant does not recognize the fire in late-night fire. The basic structure of the smoke-control system applicable to accommodation facilities was designed, and the expected effect was suggested when applied to small-scale domestic accommodation facilities through evacuation scenarios in accommodation facilities to which the system was applied.

ATRIUM SMOKE FILLING PROCESS BY COMPUTATIONAL FLUID DYNAMICS

  • Chow, W.K.;Yin, R.
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 1997.11a
    • /
    • pp.456-463
    • /
    • 1997
  • Atrium buildings are commonly found in Hong Kong since 1980. Those spaces are usually crowded with people and so fire protection systems have to be installed for providing a safe environment. Smoke control system was identified to be important but no clear design guidelines are available because the smoke filling process was not well-understood. In this paper., Computational Fluid Dynamics(CFD) or fire field model is applied to study the smoke filling pattern in atrium. Two common cases on smoke spreading out from a shop adjacent to the atrium; and with a fire located at the atrium floor itself were considered. Simulations with a modified form of the CFD package TEAM were performed. Application of the predicted results Is illustrated.

  • PDF

The Experimental Study on the Leakage of Automatic Pressure Differential·Overpressure Control Dampers by Increasing the Number of Damper Operation (자동차압·과압조절형댐퍼의 개폐동작횟수 증가에 따른 누설량 실험 연구)

  • Shin, Pyung-Shik;Kim, Hak-Joong
    • Fire Science and Engineering
    • /
    • v.30 no.2
    • /
    • pp.56-61
    • /
    • 2016
  • Recently, Since buildings are bigger and higher, the damage of human life can be increased by fire flame and smoke in fire. Smoke control system is necessary to decrease this damage. Therefore, Air supply pressurization smoke control system is applied to vestibule of escape stairway. NFSC requires pressure differential of above 40 Pa, but pressure differential is excessively overpressure in the field. It is known that the cause of this over pressure differential is much leakage of damper. Over pressure differential can bad effect to escaper by pressurizing the door. Analyze the real leakage of damper by increasing the number of dampers operation for identifying this problems. The result of testing, the leakage has difference between new dampers and increased the number of operation dampers. As the static preassure increase, the leakage difference increase. Comparison with preceding study, this result has similar linear tendency.

The Experimental Study on the Leakage of Automatic Pressure Differential · Overpressure Control Dampers (자동차압 · 과압조절형댐퍼의 누설량 실험 연구)

  • Shin, Pyung-Shik;Kim, Hak-Joong
    • Fire Science and Engineering
    • /
    • v.29 no.6
    • /
    • pp.71-75
    • /
    • 2015
  • Recently, Since buildings are bigger and higher, the damage of human life can be increased by fire flame and smoke in fire. Smoke control system is necessary to decrease this damage. Therefore, Air supply pressurization smoke control system is applied to vestibule of escape stairway. NFSC requires pressure differential of 40 Pa~60 Pa, but pressure differential is over 60 Pa in the field. It is known that the cause of this over pressure differential is much leakage of damper. Over pressure differential can bad effect to escaper by pressurizing the door. Analyze the real leakage of damper by testing for identifying this problems. The result of testing, leakage is $0.090m^3/s{\sim}0.154m^3/s$. It is necessary to limit the leakage of dampers for safe of escapers.

Modification of Coupling Algorithm between Mass and Enthalpy Conservation for Modified CAU_ESCAP (제연해석 프로그램의 질량 및 엔탈피 보존식의 연계알고리즘 개선연구)

  • Bae, Sung-Ryong;Ko, Gwon-Hyun;Hong, Ki-Bae;Ryou, Hong-Sun
    • Journal of the Korean Society of Safety
    • /
    • v.26 no.4
    • /
    • pp.102-110
    • /
    • 2011
  • For decreasing of the casualties and designing of the smoke control systems in the ultra high-rise building, the programs for analysis of smoke control were developed for prediction of smoke spread and distributions of pressure and temperature in building fire situation. In this study, coupling algorithm between mass and enthalpy conservations was modified for improving the applicability of the CAU_ESCAP which program can consider the energy transfer. The fire situation in ultra high-rise building was applied by using the modified CAU_ESCAP. Results of pressure difference predicted by modified CAU_ESCAP are higher than results of ASCOS as stack effect is generated due to the increasing of stairway temperature. Moreover, theoretically, the result of the neutral plane is more accurate than the result of ASCOS, in fire situation of ultra high-rise building.

A Study on the Conditions of Injection Pressurization in the Smoke-Control Zone II. Analysis of the Conditions for Closing Force of Fire Door with Variation of Angular Velocity (제연구역 방화문의 각속도 변화와 폐쇄 조건 분석)

  • Lee, Chang-Wook;Kim, Hong-Jin;Choi, Young-Ki;Youm, Moon Cheon;Ryou, Hong-Sun
    • Fire Science and Engineering
    • /
    • v.27 no.2
    • /
    • pp.6-10
    • /
    • 2013
  • This study aims to construct the performance data for smoke-control zone and realize the safety of injection and pressurization room which is composed of supply air pressure zone, vestibule, smoke-control zone and stairwell. To obtain this, smoke-control system and the device of the opening-closing force of fire door are manufactured. This subject is the analysis of the closing force, angular velocity and fire door size in the case of fixed volume flow rate. Based on the results, closing force increased as fire door size and closing angular velocity increases. Also, it is remark that there exists a critical angular velocity, which maintains constant maximum closing force even though the angular velocity increases more.

Numerical Study on the Effect of Damper Position on Characteristics of Thermal Flow at the Vestibules and Fire Door (댐퍼의 위치가 부속실 및 방화문에서의 열 유동 특성에 미치는 영향에 관한 수치해석 연구)

  • Moon, Hyo-Jun;Ko, Gwon-Hyun;Ryou, Hong-Sun
    • Fire Science and Engineering
    • /
    • v.27 no.1
    • /
    • pp.31-38
    • /
    • 2013
  • The pressurized smoke control system is important for fire safety in building because it is directly concerned with egress time of people. Even though the damper plays an essential role in the pressurized smoke control system, the phenomena of backflow smoke occurs for a certain the damper position. The research for a position of damper effects on distribution of air flow at the fire door is not performed. In this study, numerical simulation using FDS 5.5 was carried out to analyze the effect of the position of damper on flow distribution at the fire door. To simulate real situation, effects of opening and closing of fire door was considered. As a result, when HRR was between 200 kW and 400 kW, in the case which the damper was on the opposite wall of the fire door, the back flow to the vestibules was large compared to the two other cases of damper position. But when HRR was above 400 kW, Effect on damper position was not occurred.

Effect of the HVAC Conditions on the Smoke Ventilation Performance and Habitability for a Main Control Room Fire in Nuclear Power Plant (원자력발전소 주제어실 화재 시 공조모드가 배연성능 및 거주성에 미치는 영향 분석)

  • Kim, Beom-Gyu;Lim, Heok-Soon;Lee, Young-Seung;Kim, Myung-Su
    • Fire Science and Engineering
    • /
    • v.30 no.5
    • /
    • pp.74-81
    • /
    • 2016
  • This study evaluated the habitability of operators for main control room fires in nuclear power plants. Fire modeling (FDS v.6.0) was utilized for a fire safety assessment so that it could determine the performance of the smoke ventilation and operator habitability with the main control room. For this study, it categorized fire scenarios into three cases depending on the conditions in the HVAC system. As a result of fire modelling, it showed that Case 1 (with HVAC) would give rise to the worst situation associated with the absolute temperature, radiative heat flux, optical density, and smoke layer height as deliberating the habitability and smoke ventilation. On the other hand, it showed that Cases 2 (w/o HVAC) and 3 can maintain much safer situations than Case 1. In the case of temperature at 820 s, Cases 2 and 3 were up to approximately 63% greater than Case 1 in the wake of ignition. In addition, the influence of radiative heat flux of Case 1 was even larger than Cases 2 and 3. That is, the radiative heat fluxes of Cases 2 and 3 were approximately 68% higher than Case 1. Furthermore, when it comes to considering the optical density, Case 1 was approximately 93% greater than Cases 2 and 3. Accordingly, it expected that the HVAC system can influence a the performance on the smoke ventilation that can be sustainable for operator habitability. On the other hand, it revealed an inconsecutive pattern for the smoke layer height of Cases 2 and 3 because supply vents and exhaust vents were installed within the same surface.