The Experimental Study on the Leakage of Automatic Pressure Differential · Overpressure Control Dampers  

Shin, Pyung-Shik (Fire Station of Suwon)
Kim, Hak-Joong (Dept. of Fire Service Administration, Chodang Univ.)
Publication Information
Fire Science and Engineering / v.29, no.6, 2015 , pp. 71-75 More about this Journal
Abstract
Recently, Since buildings are bigger and higher, the damage of human life can be increased by fire flame and smoke in fire. Smoke control system is necessary to decrease this damage. Therefore, Air supply pressurization smoke control system is applied to vestibule of escape stairway. NFSC requires pressure differential of 40 Pa~60 Pa, but pressure differential is over 60 Pa in the field. It is known that the cause of this over pressure differential is much leakage of damper. Over pressure differential can bad effect to escaper by pressurizing the door. Analyze the real leakage of damper by testing for identifying this problems. The result of testing, leakage is $0.090m^3/s{\sim}0.154m^3/s$. It is necessary to limit the leakage of dampers for safe of escapers.
Keywords
Automatic pressure differential; overpressure control damper; Leakage; Smoke control;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Nation Fire Safety Code, NFSC 501A (2015).
2 K. C. Choi, Y. S. Song and J. H. Cha, "A Study on Leaking amount Test of Control Damper", Fire Science and Engineering, Vol. 23, No. 3, pp. 131-137 (2009).
3 J. Y. Kim, D. H. Lee and H. Y. Kim, "Field Experiments on Performance Evaluation of Pressure Differential System for Smoke Management", Proceedings of 2008 Spring Annual Conference, Korean Institute of Fire Science & Engineering, pp. 251-254 (2008).
4 Korean Standard, KS A 0612 (1997).
5 Korean Standard, KS B 6311 (2010).
6 Air Movement and Control Association, AMCA 500-D-98 (1999).