• Title/Summary/Keyword: Secondary winding

Search Result 213, Processing Time 0.025 seconds

Test of an High Temperature Superconducting Power Transformer (고온초전도변압기의 특성시험)

  • Lee, Hui-Jun;Cha, Gwi-Su;Lee, Ji-Gwang;Kim, U-Seok;Han, Song-Yeop;Ryu, Gyeong-U;Choe, Gyeong-Dal
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.49 no.9
    • /
    • pp.572-577
    • /
    • 2000
  • This paper describes the test results of a single phase 3kVA high temperature superconducting power transformer. The tapes are made with Bi-2223 and have silver alloy as the matrix. Four double pancake windings are used. Among them two double pancake windings are connected in series for high voltage winding and the others are connected in parallel for low voltage winding. The rated voltage and current of primary winding and secondary winding are 220/110V. 13.7/27.3A. Fundamental characteristics are obtained through short circuit and no load test. The over load capability and characteristics are investigated.

  • PDF

Analysis on Current Limiting Characteristics of Double Quench Flux-Lock Type SFCL Using Its Third Winding (삼차권선을 이용한 이중퀜치 자속구속형 초전도한류기의 전류제한 특성 분석)

  • Han, Tae-Hee;Lim, Sung-Hun
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.29 no.5
    • /
    • pp.289-293
    • /
    • 2016
  • The flux-lock type superconducting fault current limiter (SFCL) connects the two parallel windings in parallel with a ferromagnetic core. We suggest that the double quench flux-lock type SFCL should add a third winding. We analyzed characteristics of the fault current and the peak current using the quench of the high-Tc superconducting element. The proposed SFCL's inductances of a primary winding and the third winding were fixed and the amplitude of inductance of the secondary winding was changed. We found that the fault current can be more effectively controlled through the analysis of the equivalent circuit and the short-circuit tests.

Conceptual Design of a Single Phase 33 MVA HTS Transformer with a Tertiary Winding (3차 권선을 고려한 단상 33MVA 고온초전도 변압기의 개념설계)

  • Lee, S.W.;Kim, W.S.;Hahn, S.Y.;Hwang, Y.I.;Choi, K.D.
    • Progress in Superconductivity
    • /
    • v.7 no.2
    • /
    • pp.162-166
    • /
    • 2006
  • We have proposed a 3 phase, 100 MVA, 154 kV class HTS transformer substituting for a 60 MVA conventional transformer. The power transformer of 154 kV class has a tertiary winding besides primary and secondary windings. So the HTS transformer should have the 3rd superconducting winding. In this paper, we designed conceptually the structure of the superconducting windings of a single phase 33 MVA transformer. The electrical characteristics of the HTS transformer such as % impedance and AC loss vary with the arrangement of the windings and gaps between windings. We analyzed the effects of the winding parameters, evaluated the cost of each design, and proposed a suitable HTS transformer model for future power distribution system.

  • PDF

Study on manufacturing and operating characteristics of Magnetic cores for Flat TR (Flat TR용 핵심 쿄아의 제조와 동작 특성 안정화 연구)

  • Han, Se-Won;Cho, Han-Goo;Yu, Dong-Uk;Ryu, Mung-Ho;Choi, Kwang-Bo;Kim, Sung-Ba
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2003.05e
    • /
    • pp.23-26
    • /
    • 2003
  • The flat transformer, typically, has a number of parallel single turn secondary windings. Each secondary winding is coupled to the same primary winding. Therefore, the current in each secondary winding is equal to the ampere-turns in the primary winding, and to each other. These characteristics are particularly advantageous where parallel rectifiers are used. The windings share the current equally, with no need for ballast resistors or other added components. In this study, the ferrite magnetic core samples of Mn-Zn system for the Flat transformer are manufactured and the electrical and magnetic characteristics of its tested. The density of sample FO2-2 sintered at $1350^{\circ}C$ is $4.00kg/m^3$, which shows the good microstructural state. The initial permeability and saturation flux density of FO2 at room temperature is 2700 and 510mT, individually. The power loss of FO2 samples at 250kHz have been ranged $350kW/m^3$ to $80kW/m^3$ with temperature. And the minimum power loss of sample FO2-2 showed at $70^{\circ}C$, which property seems very positive to apply for a flat transformer.

  • PDF

Analysis on Current Limiting Characteristics of Flux-Lock Type SFCL Using a Transformer Winding (변압기 권선을 이용한 자속구속형 초전도 전류제한기의 전류제한 특성 분석)

  • Han, Tae-Hee;Lim, Sung-Hun
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.24 no.2
    • /
    • pp.136-140
    • /
    • 2011
  • The fault current limiting characteristics of the flux-lock type superconducting fault current limiter (SFCL) using a transformer winding were investigated. The suggested flux-lock type SFCL consists of two parallel connected coils on an iron core and the transformer winding connected in series with one of two coils. In this SFCL, the high-TC superconducting (HTSC) element was connected with the secondary side of the transformer. The short-circuit experimental devices to analyze the fault current limiting characteristics of the flux-lock type SFCL using the transformer winding were constructed. Through the short-circuit tests, the flux-lock type SFCL using transformer winding was shown to perform more effective fault current limiting operation compared to the previous flux-lock type SFCL without the transformer winding from the viewpoint of the quench occurrence and the recovery time of the HTSC element.

Operational Characteristics in integrated Three-Phase a Flux-Lock type SFCL according to Fault Conditions (3상 일체화된 자속구속형 전류제한기의 동작특성)

  • Lee, Na-Young;Choi, Hyo-Sang;Jeong, Soo-Bok;Lee, Sang-Il;Nam, Gueng-Hyun;Lim, Sung-Hun
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2006.05a
    • /
    • pp.467-470
    • /
    • 2006
  • Superconducting fault current(SFCLs) are expected to improve not only reliability but also stability of real power systems. The analysis on the single line-to-ground fault current of the integrated three phase flux-lock type SFCL, which consists of three flux-lock reactor wound on an iron core in each single phase and three YBCO thin films, was investigated in current limiting operating characteristics. We compared additive polarity winding with the subtractive one in the flux lock reactor. Its turns ratio each phase between the primary and the secondary coils is 63:42. When a single line-to-ground fault occurred in any phase, the peak value of line current in the fault phase of the additive polarity winding increased up to 31.44[A] during first-half cycle. On the other hand, the peak value in the subtractive polarity winding increased up to 81.77[A] under the same conditions. This is because the current flow between the primary and the secondary windings becomes to be additive or subtractive in each winding direction. We confirmed that the current limiting behavior in the additive polarity winding was more effective for a single-line-to ground fault.

  • PDF

Compensation Algorithm for the Secondary Voltage of a Coupling Capacitor Voltage Transformer by Considering the Hysteresis Characteristics of the Core (코어의 히스테리시스 특성을 고려한 CCVT 2차 전압 보상 알고리즘)

  • Kang, Yong-Cheol;Zheng, Tai-Ying;Kang, Hae-Gweon;Jang, Sung-Il;Kim, Yong-Gyun
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.58 no.8
    • /
    • pp.1457-1462
    • /
    • 2009
  • This paper proposes a compensating algorithm for the secondary voltage of a coupling capacitor voltage transformer (CCVT) in the time domain by considering the hysteresis characteristics of the core. The proposed algorithm estimates the three error terms i.e. the voltage across the secondary winding parameters, the voltage across the primary winding parameters, and the voltage across the capacitor and the tuning reactor. These three terms are added to the measured secondary voltage to obtain the correct voltage. The algorithm reduces the errors of the CCVT significantly both in the steady state and during a fault. The performance of the algorithm is verified under the various fault conditions by varying the fault distance, the fault inception angle, and the fault impedance with the EMTP generated data. Test results clearly indicate that the algorithm can increase the accuracy of a CCVT significantly under the fault conditions as well as in the steady state. The algorithm helps improve the performance of a protection relay or a metering device.

A analysis of frequency characteristics for the noise cut transformer (노이즈 차폐 변압기의 주파수 특성 분석)

  • Kim, Myoung-Seok;Oh, Joon-Sik;Cho, Hyun-Kil;Han, Gyu-Hwan;Park, Jong-Hwa
    • Proceedings of the KIEE Conference
    • /
    • 2005.07b
    • /
    • pp.957-959
    • /
    • 2005
  • A noise reduction equipment in power systems was device combined in a passive element such as the form of L, R and C. A analysis of frequency characteristics for the transformer models shall be considered the additional capacitance between the windings($C_{ps}$), terminals($C_s$), and winding-ground($C_g$). A noise in transformer is modeled by take account into the different frequency. In case of the high frequency, transformer windings with stray capacitance have lower impedance. Therefore a noise is transferred from primary winding to secondary winding. Noise Cut Transformer(NCT) was the noise reduction device and was normally single phase two-winding type transformer. We analyzed frequency characteristics using the nodal network analysis with the equivalent circuit and the simulation of the MATLAB.

  • PDF

Analysis of Cross-Regulation Characteristics for LLC Resonant Converter of Secondary Multi-winding Structure (2차측 Multiple-Winding 구조의 변압기를 갖는 LLC 공진형 컨버터의 Cross-regulation 특성 분석)

  • Kim, Sung-Jae;Kim, Yeong-Sam;Kim, Jong-Soo
    • Proceedings of the KIPE Conference
    • /
    • 2019.07a
    • /
    • pp.289-290
    • /
    • 2019
  • 2차측 Multi-winding구조의 LLC공진형 컨버터는 교차조절(Cross-regulation) 특성에 의해 각 출력의 부하의 변화에 따라 출력전압의 불균형 문제가 있다. 본 논문에서는 2차측 Multi-winding 구조의 LLC공진형 컨버터에서 나타나는 교차조절 특성을 이론적으로 분석하고 240W급 LLC공진형 컨버터를 이용하여 실험을 진행한다. 실험 결과를 통해 출력 채널 수의 증가에 따른 교차조절 특성에 대해 고찰한다.

  • PDF

Current Limiting Characteristics of flux-lock Type High-lc Superconducting Fault Current Limiter According to fault Angles (사고각에 따른 자속구속형 전류제한기의 전류제한특성)

  • Park, Hyoung-Min;Choi, Hyo-Sang;Cho, Yong-Sun;Lim, Sung-Hun;Park, Chung-Ryul;Han, Byoung-Sung
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.18 no.8
    • /
    • pp.747-753
    • /
    • 2005
  • We Investigated the current limiting characteristics of the flux-lock type superconducting fault current limiter(SFCL) by fault angles. The flux-lock type SFCL consists of the primary and the secondary copper coils wound in parallel through the iron core and YBCO thin film. In this paper, the current limiting characteristics of the flux-lock type SFCL by fault angles in case of the subtractive and the additive polarity windings were compared and analyzed. The flux-lock type SFCL limited fault current more quickly as the fault angles increased. On the other hand, the initial power burden of the superconducting element during the fault increased as the fault angles increased. In addition, we found that the resistance of the flux-lock type SFCL in case of the subtractive polarity winding was more increased than that of the additive polarity winding. The peak current of the fault current in case of the subtractive polarity winding was larger than that of the additive polarity winding.