• 제목/요약/키워드: Sea water heat exchanger

검색결과 50건 처리시간 0.029초

Performance evaluation of sea water heat exchanger installed in the submerged bottom-structure of floating architecture

  • Sim, Young-Hoon;Hwang, Kwang-Il
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제39권10호
    • /
    • pp.1062-1067
    • /
    • 2015
  • Floating architecture is a type of building that is geographically located on a sea or a river. It floats under the influence of buoyancy, and does not have an engine for moving it. Korea is a peninsula surrounded by sea except on the north side, so floating architectures have been mainly focused on two points: solving the issue of small territory and providing various leisure & cultural spaces. Floating architectures are expected to save energy effectively, if they use sea water heat, which is known to be clean energy with infinite reserves. To use sea water heat as the heat source and/or heat sink, this study proposes a model in which a sea water heat exchanger is embedded in the concrete structure in the lower part of the floating architecture that is submerged under the sea. Based on the results of performance evaluations of the sea water heat exchanger using CFD (computational fluid dynamics) analysis and mock-up experiments under various conditions, it is found out that the temperature difference between the inlet and outlet of the heat exchanger is in the range of $3.06{\sim}9.57^{\circ}C$, and that the quantity of heat transfer measured is in the range of 3,812~7,180 W. The CFD evaluation results shows a difference of 5% with respect to the results of mock-up experiment.

Design and Analysis of Heat Exchanger Using Sea Water Heat Source for Cooling

  • Kim, MyungRae;Lee, JuHee;Yoon, JaeOck
    • KIEAE Journal
    • /
    • 제16권3호
    • /
    • pp.25-34
    • /
    • 2016
  • Purpose: The temperature in Seoul has risen 3 times more than the average global temperature increase for the past 100 years. Today, summer starts 15 days earlier than the early 20th century and is 32 days longer. This tendency causes rapid increase of cooling energy demand. Following this effect, seawater heat resources are to be used as an countermeasure for global warming. Incheon Port near the Western Sea has the lowest water temperature in the winter in South Korea in which it is suitable to use seawater cold heat resources. Method: The cold heat resource is gained from seawater when the water temperature is the lowest in the winter time and saved in a seasonal thermal storage. This can be used as cold heat resource in the summer time. A heat exchanger is essential to gain seawater cold energy. Due to this necessity, sea water heat resource heat exchangers are modeled by heat transfer equations and the fluid characteristics are analyzed. Also, a CFD (computational fluid dynamics) program is used to conduct simulation on the fluid characteristics of heat exchangers. The analyzed data of deducted from this process are comprehensively analyzed and discussed. Result: Regarding the performance of the heat exchanger, the heat exchanger was operated following the prediction within the range of heat transfer rate of minimum 3.3KW to maximum 33.6KW per device. In the temperature change analysis of the heat exchanger, fluid analysis by heat transfer equations almost corresponded to the temperature change by CFD simulation. Therefore, it is considered that the results of this study can be used as design data of heat exchangers.

해수온도차에너지이용 냉난방시스템 운전특성에 관한 연구 (A Study on Operating Characteristics of Heat Pump System Using Sea Water Sources)

  • 장기창;백영진;윤형기;나호상
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 한국신재생에너지학회 2009년도 춘계학술대회 논문집
    • /
    • pp.422-425
    • /
    • 2009
  • A sea water source cascade heat pump was designed and tested in this study. The system was designed to perform a single stage operation in summer, as well as a cascade operation in winter to ensure the high temperature lift. A steady-state simulation model was developed to analyze and optimize its performance. The simulation results show that the R717 exhibits best performance among combinations considered in this study. A R410A also exhibits the highest performance among HFCs with the smallest compressor displacement. A 15-RT R410A-R134a pilot system was installed in the 5-story commercial building at Samcheok City by the East Sea. A scroll type R410A compressor, a reciprocating type R134a compressor, plate type condenser/evaporator/ cascade heat exchanger and two electronic expansion valves were used to build a pilot. A titanium plate type heat exchanger is also used for the heat exchanging with a sea water. The heat source/sink water is supplied from the well below the seashore in the depth of 5 m. In the initial test of the system, supply water temperature was rising up to $67^{\circ}C$ using a sea water heat source of $9^{\circ}C$, while an ambient temperature was $4.5^{\circ}C$.

  • PDF

심층수 이용 열교환기 개발을 위한 기초연구: 열교환기 부식이 열교환기 성능에 미치는 영향 (A Fundamentals study on Heat Exchanger using Deep Ocean Water: Effects of Corrosion on Heat Transfer Performance)

  • 권영철;이석현;허철;조맹익;이창경;권정태
    • 한국산학기술학회논문지
    • /
    • 제14권11호
    • /
    • pp.5377-5384
    • /
    • 2013
  • 본 논문은 심층수용 열교환기 재질로 티타늄, 알루미늄, 스테인리스, 구리와 알루미늄을 코팅하여 재질의 특성 및 부식이 미치는 영향을 조사하기 위하여 이중관 열교환 실험장치를 활용하였다. 열교환기 재질은 티타늄, 스테인레스, 구리, 알루미늄, 카본 코팅된 알루미늄 등 6종이 비부식관과 부식관에 대하여 해석과 실험이 수행되었다. 해석은 EES 프로그램을 사용하였다. 부식의 영향을 살펴보기 위하여 부식 제조장치를 제작하고, 3.5%의 염수를 $70^{\circ}C$의 온도로 약 6주간 담가서 가속부식을 실시하였다. 부식된 관으로 이중관 열교환기의 성능실험을 실시하여 비부식관과 비교하였다. 실험결과로부터 티타늄을 대체용으로 알루미늄 코팅관(카본 블랙 $150{\mu}m$)의 가능성을 확인하였다.

플로팅 건축에서 해수열 이용을 위한 수중 열교환기 모델 개발과 성능 평가 (Performance evaluation of types of sea water heat exchanger for floating architecture)

  • 김별;이창훈;구재혁;황광일
    • 한국항해항만학회:학술대회논문집
    • /
    • 한국항해항만학회 2013년도 추계학술대회
    • /
    • pp.287-288
    • /
    • 2013
  • 삼면이 바다인 우리나라에서는 지구 온난화에 따른 해수면 상승과 같은 환경 문제 와 국민소득 증가에 따른 해양공간에 대한 수요의 증가로 플로팅 건축물의 발전 가능성이 크다. 하지만 아직까지 플로팅건축물 주변에 존재하는 해수열에너지를 이용을 위한 수중 열교환기에 대한 기초 연구가 부족하다. 이에 본 연구에서는 플로팅 건축물에서 해수 열 이용을 위한 수중 열교환기 모델 개발 및 실험을 통하여 성능을 평가하였다.

  • PDF

해수열원 히트펌프 시스템의 운전특성 (The Operation Characteristics of a Sea Water Source Heat Pump System)

  • 장기창;백영진;나호상;김지영;이재훈
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2008년도 하계학술발표대회 논문집
    • /
    • pp.1353-1357
    • /
    • 2008
  • A sea water source cascade heat pump was designed and tested in this study. The system was designed to perform a single stage operation in summer, as well as a cascade operation in winter to ensure the high temperature lift. A steady-state simulation model was developed to analyze and optimize its performance. The simulation results show that the R717 exhibits best performance among combinations considered in this study. A R410A also exhibits the highest performance among HFCs with the smallest compressor displacement. A 15-RT R410A-R134a pilot system was installed in the 5-story commercial building at Samcheok City by the East Sea. A scroll type R410A compressor, a reciprocating type R134a compressor, plate type condenser/ evaporator/ cascade heat exchanger and two electronic expansion valves were used to build a pilot. A titanium plate type heat exchanger is also used for the heat exchanging with a sea water. The heat source/sink water is supplied from the well below the seashore in the depth of 5 m. In the initial test of the system, supply water temperature was rising up to $67^{\circ}C$ using a sea water heat source of $9^{\circ}C$, while an ambient temperature was $4.5^{\circ}C$.

  • PDF

해수열원 히트펌프 시스템의 설계 및 운전 (A Design and Test of a Sea Water Source Heat Pump System)

  • 이재훈;김지영;백영진;장기창;나호상;신광호
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2008년도 하계학술발표대회 논문집
    • /
    • pp.1273-1278
    • /
    • 2008
  • A sea water source cascade heat pump was designed and tested in this study. The system was designed to perform a single stage operation in summer, as well as a cascade operation in winter to ensure the high temperature lift. A steady-state simulation model was developed to analyze and optimize its performance. The simulation results show that the R717 exhibits best performance among combinations considered in this study. A R410A also exhibits the highest performance among HFCs with the smallest compressor displacement. A 15-RT R410A-R134a pilot system was installed in the 5-story commercial building at Samcheok City by the East Sea. A scroll type R410A compressor, a reciprocating type R134a compressor, plate type condenser/ evaporator/ cascade heat exchanger and two electronic expansion valves were used to build a pilot. A titanium plate type heat exchanger is also used for the heat exchanging with a sea water. The heat source/sink water is supplied from the well below the seashore in the depth of 5 m. In the initial test of the system, supply water temperature was rising up to $67^{\circ}C$ using a sea water heat source of $9^{\circ}C$, while an ambient temperature was $4.5^{\circ}C$.

  • PDF

LNG 개방래크 기화기의 해석 및 설계 (Analysis and design of LNG open rack vaporizer)

  • 박정수;장호명
    • 설비공학논문집
    • /
    • 제9권2호
    • /
    • pp.189-197
    • /
    • 1997
  • The vaporizing characteristics of LNG(liquefied natural gas) via heat exchanger with sea water are analytically studied for an open rack vaporizer(ORV). This study is intended to supply the design data for the domestic fabrication of the corrosion-resistant vaporizer tube. A computational program is developed to predict the exit temperature of LNG for various conditions. In the program, thesimple and justifiable heat transfer models are selected for fully-developed internal flow of LNG, the star-shaped finned-tube, and the external falling films of sea water, as well as the possible ice formation and the fouling on the tube walls. It is found that the enongh corrugation inside of the tube wall is the most significant in the vaporizer performance for the current operating conditions. the effects of other design parameters on the heat exchanger between LNG and sea water are quantitatively presented.

  • PDF

플로팅 건축에서 해수열 이용을 위한 수중 열교환기의 봄철 성능평가 (Performance Evaluation of Sea Water Heat Exchanger in the Springtime for Floating Architecture)

  • 황광일;김별;이현인;김익현;도근영
    • 한국항해항만학회:학술대회논문집
    • /
    • 한국항해항만학회 2012년도 춘계학술대회
    • /
    • pp.442-443
    • /
    • 2012
  • 지구환경문제에 대응하기 위한 탄소배출량 저감 기술 개발과 같은 대응기술 개발이 시급한 가운데 수 해양공간에 대한 수요의 증가로 플로팅 건축물에 대한 관심 또한 증가하고 있다. 이에 본 연구에서는 플로팅 건축물 주변에 존재하는 신재생에너지 중 해수 열 이용을 위한 수중 열교환기를 기초연구를 바탕으로 제작하고 실험을 통하여 성능을 평가하였다.

  • PDF

함정용 패키지 에어콘 응축기 핀튜브(Cu-Ni 70/30) 누설파괴 원인 분석 (Failure Analysis of Condenser Fin Tubes of Package Type Air Conditioner for Navy Vessel)

  • 박형훈;황양진;이규환
    • 한국표면공학회지
    • /
    • 제49권5호
    • /
    • pp.439-446
    • /
    • 2016
  • In 2015, a fin tube (Cu-Ni 70/30 alloy) of package type heat exchanger for navy vessel was perforated through the wall which led to refrigerant leakage. This failure occurred after only one year since its installation. In this study, cause of the failure was determined based on available documents, metallographic studies and computational fluid dynamics simulation conducted on this fin tube. The results showed that dimensional gap between inserted plastic tube and inside wall of fin tube is the cause of the swirling turbulent stream of sea water. As a result of combination of swirling turbulence and continuing collision of hard solid particles in sea water, erosion corrosion has begun at the end of inserted plastic tube area. Crevice corrosion followed later in the crevice between the outer wall of plastic tube and inner wall of fin tube. It was found that other remaining tubes also showed the same corrosion phenomena. Thorough inspection and prompt replacement will have to be accomplished for the fin tubes of the same model heat exchanger.