• 제목/요약/키워드: SF6-Filled Switchgear

검색결과 7건 처리시간 0.019초

Breakdown Characteristics of SF6 in Different State and Bubble Movements under AC High-Voltage

  • Choi, Eun-Hyeok;Lim, Chang-Ho;Yoon, Dae-Hee;Park, Kwang-Seo;Kim, Lee-Kook;Lee, Kwang-Sik
    • Journal of Electrical Engineering and Technology
    • /
    • 제2권2호
    • /
    • pp.257-262
    • /
    • 2007
  • In this paper the experiments of breakdown characteristics by temperature change of $SF_6$ gas($GSF_6$), and $SF_6$ liquid ($LSF_6$) in model GIS (Gas Insulated Switchgear) are described. From the experiment's results, the breakdown characteristics classify the vapor stage of $SF_6$ according to Paschen's law, in which the gas & liquid coexisted stage of voltage value increases, resulting in much deviation and the breakdown of voltage ($V_B$) low stage as the interior of the chamber gets filled with a mixture of $SF_6$ that is not liquefacted and remaining air that cannot be ventilated. The ability of $LSF_6$ insulation is higher than the high-pressurized $SF_6$ gas. The breakdown characteristics of $LSF_6$ were produced by bubble formed evaporation of $LSF_6$ and bubbles caused by high electric emission. It is considered in this paper that the results are fundamental data for electric insulation design of superconductor and cryogenic equipments machinery that will be studied and developed in the future.

Breakdown characteristics of SF6 and Imitation Air in Temperature Decline

  • Lim, Chang-Ho;Choi, Eun-Hyeok;Kim, Do-Seok;Kim, Young-Su;Park, Won-Zoo;Lee, Kwang-Sik
    • 조명전기설비학회논문지
    • /
    • 제21권4호
    • /
    • pp.115-121
    • /
    • 2007
  • This paper describes experiments of the breakdown characteristics by temperature change of $SF_6$ gas and Imitation Air(I-Air) in model GIS(Gas Insulated Switchgear). From the results of the experiments, the breakdown characteristics classify the vapor stage of $SF_6$ according to Paschen's law, in which the stage of coexistence for gas & liquid of the voltage value increases. This results in large deviation and the breakdown of the voltage(VB) low stage as the interior of the chamber is filled with a mixture of $SF_6$ that is not liquefacted and remaining air that can not be ventilated. The ability of $SF_6$ liquid($LSF_6$) insulation is higher than high-pressurize $SF_6$ gas. The VB of the I-Air decreases as the temperature drops and the VB also drops. It is considered that the results of this paper are fundamental data for the electric insulation design of superconductor and cryogenic equipment that will be studied and developed in the future.

Comparison of Partial Discharge Characteristics in SF6 Gas Under AC and DC

  • Jo, Hyang-Eun;Wang, Guoming;Kim, Sun-Jae;Kil, Gyung-Suk
    • Transactions on Electrical and Electronic Materials
    • /
    • 제16권6호
    • /
    • pp.323-327
    • /
    • 2015
  • In this paper, parameters related with partial discharge (PD) were analyzed in SF6 gas under AC and DC voltages. Three electrode systems (protrusion on conductor, protrusion on enclosure, and free particle) were fabricated to simulate PD defects in a gas-insulated switchgear (GIS). All electrode systems were filled with SF6 gas at 0.5 MPa. PD pulses were detected using an oscilloscope and a data acquisition (DAQ) based on IEC 60270. To analyze the PD characteristics under AC and DC voltages, parameters such as discharge inception voltage (DIV), discharge extinction voltage (DEV), pulse magnitude, repetition rate, and T-F map were compared. From the experimental results, PD was revealed to have different characteristics under AC and DC, and these results may be useful for diagnosis of power facilities operated under HVDC.

광대역 및 협대역을 동시에 사용하는 부분방전 측정 시스템 모듈 개발 (Development of Partial Discharge Measuring System Module by use of Wide and Narrow Band)

  • 이종오;유경국;신인권;장덕진;안창환
    • 조명전기설비학회논문지
    • /
    • 제29권8호
    • /
    • pp.98-103
    • /
    • 2015
  • Power plant is that very high reliability when industrial and economic impact on the overall electric power system is required, it is essential to improve the reliability, especially the fault prediction diagnosis. Since an accident caused by the partial discharge in the power plant is above state has a faster response characteristic than the other indications in the case of any, the partial discharge generated in the power plant immediately detect the deterioration of insulation due to the accident of the power plant and the non-drawn It should prevent or reduce. Partial Discharge Measuring Systems for UHV SF6 Gas Insulated Switchgear and power transformer on site installed has some probability of abnormal recognition in case of non-flexible deal with on site noise. Many methode to eliminate these kinds of noises, UHF Detection System is chosen as purchase description in Korea, but this system having a bandwidth between 500MHz 1.5GHz wide band. Initial install periods(about 20 years ago), this band had no strong signal source, but in these days this wide band have strong signals, such as LTE. So, module described in this paper is designed as simultaneously use with wide and narrow band for solve this noise problem, and introduce this system.

SF6 가스 중 HVDC에서 금속 파티클의 부분방전 특성 (Partial Discharge Characteristics of Metallic Particles Under HVDC in SF6 Gas)

  • 김선재;조향은;왕국명;윤민영;길경석
    • 한국전기전자재료학회논문지
    • /
    • 제28권12호
    • /
    • pp.831-836
    • /
    • 2015
  • This paper dealt with the PD (partial discharge) characteristics produced by metallic particles presented in a gas insulated switchgear. Four types of metallic particles such as a ball, a trapezoid, a rectangle, and a twist were fabricated and placed in a PD cell filled with $SF_6$ gas. PD pulses were detected through a $50{\Omega}$ non-inductive resistor. Calibration was carried out according to IEC 60270 and the sensitivity was calculated as 4 mV/pC. Apparent charge, pulse count, DIV (discharge inception voltage), DEV (discharge extinction voltage), and TRPD (time resolved partial discharge) were analyzed. Among the metallic particle types, the twist frequently occurred PD pulse at the lowest DIV, while the rectangle showed the highest. DEV of the twist was about 2 times lower than that for the rectangle. Kurtosis of ball clustered at high value, and skewness of other three metallic particles distributed at low value. TRPD showed different distribution by metallic particle types.

SF6 압력에 따른 결함별 부분 방전 펄스의 분포 분석 (Analysis on PD Pulse Distribution by Defects Depending on SF6 Pressure)

  • 김선재;조향은;정기우;길경석;김성욱
    • 한국전기전자재료학회논문지
    • /
    • 제28권1호
    • /
    • pp.40-45
    • /
    • 2015
  • Electrode systems: a protrusion on conductor (POC), a protrusion on enclosure (POE), a crack in epoxy plate and a free particle (FP) were fabricated to simulate insulation defects in a gas insulated switchgear (GIS). $SF_6$ gas was filled in the electrode systems by 3 bar and/or 5 bar, respectively. Partial discharge (PD) pulses were detected through a $50{\Omega}$ non-inductive resistor. A calibration test was carried out according to IEC 60270, and the sensitivity was 0.25 pC/mV. PD pulses were distributed in the phase of $50^{\circ}{\sim}135^{\circ}$ and over 95% of them existed in the phase of $55^{\circ}{\sim}120^{\circ}$ for the POC. PD pulses were distributed in the phase of $230^{\circ}{\sim}310^{\circ}$ and over 90% of them existed in phase of $220^{\circ}{\sim}300^{\circ}$ for the POE. PD pulses occurred in the phase of $40^{\circ}{\sim}60^{\circ}$ and $220^{\circ}{\sim}300^{\circ}$ for the crack, and pulse counts were 25% higher in negative polarity than in positive polarity. PD pulses were distributed in every phase unlike to other three electrode systems and the peak magnitude was measured at $118^{\circ}$ and $260^{\circ}$ for the FP. As described above, PD pulses were observed in positive polarity for the POC, in negative one for the POE, in both one for the crack and the FP. In conclusion, it is expected that the identification rate of defect type can be improved by considering the polarity ratio of PD pulses on the PRPDA method.

72.5kV GIS 전력 장비의 KEPCO 기준 내진 및 응력 해석 (Seismic and Stress Analysis of 72.5kV GIS for Technical Specification of KEPCO)

  • 이재환;김영중;김소울;방명석
    • 한국전산구조공학회논문집
    • /
    • 제30권3호
    • /
    • pp.207-214
    • /
    • 2017
  • 국내의 72.5kV 이상, 주파수 60Hz의 송배전설비인 옥내 및 옥외용 가스절연개폐장치(GIS)는 내진 안전성에 대해 국가에서 정한 한전표준규격(ES-6110-0002)을 만족해야 한다. 이 규격에서 명시되지 않은 사항은 IEC 62271-203, 62271-207 등의 관련 기기 규격에 준한다. 한전표준규격에서 기기는 정상사용상태와 특수사용상태에서 건전성이 유지되어야 한다. 안전성 판단을 위해 ASME BPVC SEC.VIII 내압용기 설계 기준에 의해 A6061-T6 재질의 GIS에 대한 정상사용상태 기준과 국내 한전표준규격과 국외 IEC 62271-207에 의한 특수사용상태 기준(지진)에 대한 총체적 응력상태를 판단하였다. 한전표준규격 기준(0.22g) 적용시, 최종응력이 알루미늄인 Part A는 78.2MPa, Part D2의 경우 102.3MPa로, ASME 허용응력 값 181.5MPa를 만족하고 있다. IEC 62271-207 High 0.5g의 경우에도 최종응력은 Part A는 90.5MPa, Part D2는 103.8MPa이다. 본 연구 결과, 72.5kV GIS는 한전표준규격의 구조안전성과 내진성능을 충분히 만족함을 보이고 있다. 내진해석으로 내진시험을 수행할 수 없는 대형 전력기기의 내진성능 실증에 활용될 수 있을 것으로 기대된다.