• 제목/요약/키워드: Rogowski coil

검색결과 57건 처리시간 0.029초

로고우스키코일을 이용한 과도전류의 측정 (Measurement of Transient Current by using the Rogowski Coil)

  • 이복희;길경석;정승수;정상진
    • 대한전기학회논문지
    • /
    • 제43권7호
    • /
    • pp.1206-1213
    • /
    • 1994
  • This paper presents the operation principle and design rule of the Rogowski coil which can measure the transient current and describes the calibration and application experimental results for performance evaluation. It is obtained that the response curves of the Robowski coil with the turns of 300 and the passive integrator to sinusoidal input give a good linearity up to the frequency of 500 [kHz] and the current measurement system gaving the Rogowski coil is the frequency bandwidth of 40 [Hz]~700 [kHz]. As an application experiment for the fabricated modeling power transmission line, the impulse current, which limitates the direct lightning return stroke to overhead ground wire, is measured by the Rogowski coil and its fast Fourier transformation is carried out. The equivalent circuit of the Rogowski coil considering the stray capacitances is proposed, and the theoretical analysis is in good agreement with the measurement results. Also, it is found that for high frequency domain the stray capacitance such as a distributed capacitance to the shield and the capacitance between windings of coil should be considered in designing the Rogowski coils since the resonance originates from the stray capacitance and the self-inductance of the Rogowski coil.

  • PDF

Flexible Rogowski 코일을 이용한 클램프형 전류 센서의 개발 (Development of Clamp Current Meter using a Flexible Rogowski Coil)

  • 장용무;김성일
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2002년도 추계학술대회 논문집 Vol.15
    • /
    • pp.472-475
    • /
    • 2002
  • A Rogowski coil can measure alternating currents from a few amps to over 1 million amps in a frequency range from less than 0.1 Hz to about lMhz. A Rogowski coil provides an induced output voltage which is proportional to the rate of change of the primary current enclosed by the flexible or the rigid coil-loop. Therefore, it is necessary to integrate the output voltage in order to produce a voltage proportional to the current. Also. it can reproduce the current waveform on an oscilloscope or any type of data acquisition device. This paper describes the practical design of the combination of a Rogowski coil and an integrator which provides a versatile current measuring system to accommodate a wide range of frequencies, current levels and conductor sizes.

  • PDF

전류측정감도 개선을 위한 로고우스키 코일의 설계 (Design of Rogowski coil to improve of current measurement sensitivity)

  • 박정남;이청;장용무;강성화;임기조;나동희
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2001년도 추계학술대회 논문집 Vol.14 No.1
    • /
    • pp.609-612
    • /
    • 2001
  • Rogowski coil is made having no ferromagnetic material in a core. So the coil cannot be driven into saturation. This result in that Rogowski coils may be calibrated at relatively low currents. and used with confidence at very high currents. However the lowest level of current that can be measured is limited by the sensitivity of the voltage measuring instrument and system noise. Therefore. geometrical effects were investigated in order to measure high sensitivity of low level current and the significant source of error was examined as well. In the results, the source of error was associated with coil designs. i.e. shape and uniformity of coil and a geometrical location of current source inside and outside of the Rogowski coil.

  • PDF

전류측정감도 개선을 위한 로고우스키 코일의 설계 (Design of Rogowski coil to improve of current measurement sensitivity)

  • 박정남;이청;장용무;강성화;임기조;나동희
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2001년도 추계학술대회 논문집
    • /
    • pp.609-612
    • /
    • 2001
  • Rogowski coil is made having no ferromagnetic material in a core. So the coil cannot be driven into saturation. This result in that Rogowski coils may be calibrated at relatively low currents, and used with confidence at very high currents. However the lowest level of current that can be measured is limited by the sensitivity of the voltage measuring instrument and system noise. Therefore, geometrical effects were investigated in order to measure high sensitivity of low level current and the significant source of error wa examined as well. n the results, the source of error was associated with coil designs, i.e. shape and uniformity of coil and a geometrical location of current source inside and outside of the Rogowski coil.

  • PDF

부분방전전류측정을 위한 로고스키코일의 적용에 관한 연구 (Study about the Application of Rogowski Coil for measuring Partial Discharge Current)

  • 이강원;윤성철;김명룡;백광선;나동희
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 2004년도 추계학술대회 논문집
    • /
    • pp.1378-1383
    • /
    • 2004
  • Rogowski coil is a kind of sensor for high amplitude and very short period current and suitable for the measurement of PD pulse. This paper have simulated the relations between PD signals and Rogowski coil which has its own equivalent circuit and investigated signals of Rogowski coil induced by PD pulse current. and compared with the PD signal obtained from conventional PD measuring system in accordance with IEC60270.

  • PDF

저전류 영역에서 로고우스키 코일 특성 (Characteristics of Rogowski coil at Low Cutrrent Region)

  • 박정남;이강원;이청;김길수;박영국;강성화;임기조
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2001년도 춘계학술대회 논문집 유기절연재료 전자세라믹 방전플라즈마 연구회
    • /
    • pp.47-50
    • /
    • 2001
  • Conventionally, air-cored Rogowski coil was designed for use as high alternating and transient current sensor without saturation caused by ferromagnetic material in its core. This paper investigated that Rogowski coil can be applied to low current measurement in 60Hz power line. Measured parameters R, L of coil were compared with theoretically calculated values. Output voltages crossed by Rogowski coil have shown some linearity according to input current(tens to thousands of amperes) passing through it. And also shielding effect for external noises was investigated for three cases.

  • PDF

Nano-sec rise time을 갖는 Rogowski 코일의 제작 (CONSTRUCTION OF MEASURING ROGOWSKI COIL NANO-SEC RISR TIME)

  • 이용우;이주희
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1988년도 전기.전자공학 학술대회 논문집
    • /
    • pp.399-401
    • /
    • 1988
  • This paper describes the experiment and design of Rogowski - wound coil used to measure a pulsed current with pulsewidth on the order of 100nsec in the kiloampere range. Radius of coil is 2.75cm, total number of turns are 26 and cross -sectional area is 1 cm. The coil have 3ns rise time, 0.2nsec transit time and sensitivity is 4v/kA.

  • PDF

사병렬 초전도코일의 전류분류 측정을 위한 Rogowski 코일의 제작 및 특성 실험 (Design and test results of a Rogowski coil for measurement of current distribution characteristics in 4-parallel superconducting coils)

  • 조대호;양성은;김민재;안민철;박동근;배덕권;석복렬;고태국
    • 한국초전도ㆍ저온공학회논문지
    • /
    • 제9권3호
    • /
    • pp.37-40
    • /
    • 2007
  • Large critical current is one of the prerequisites for the design of superconducting electrical equipments with large power capacity. To enlarge the critical current. multiple parallel connection is inevitable. In multiple parallel superconducting coils. the difference in normal resistance of each shunt leads to unequal current distribution. which may yield burnout. Therefore. uniform current distribution is required for a stable operation of multiple parallel superconducting coils. In this paper, Rogowski coils were fabricated to measure each shunt current of a 4-parallel superconducting coil. Four Rogowski coils were installed at the copper bars, which are used as current leads in superconducting coils. As a result, linearity of the Rogowski coils was ascertained and coefficients of each coil, the ratio of voltage and current, were derived. The coefficients were compared with theoretically calculated values. Based on the coefficients, each shunt current was calculated in a 4-parallel superconducting coil, where uniform current. distribution was confirmed. This paper verified the feasibility of the fabricated Rogowski coils as well as operational stability of the 4-parallel superconducting coil in 77K.

로고스키 코일을 이용한 액체 질소 내에서 전류측정 (Current measurement in LN2 using Rogowski coil)

  • 최용선;차상도;황시돌;최효상
    • 한국초전도저온공학회:학술대회논문집
    • /
    • 한국초전도저온공학회 2003년도 학술대회 논문집
    • /
    • pp.239-241
    • /
    • 2003
  • When superconductors are combined with normal conductor as a parallel electric circuit, imbalance of the applied current is happened. For the accurate parameters of the circuit, it is needed to measure the current of the circuit under LN2 condition. In this case, the measurement using Rogowski coil, which is not that affected by changing temperature, can be a method. In this study, using 2 Rogowski coil, the measurement of current was conducted under the condition that is room and LN2 temperature respectively.

  • PDF

Rogowski 코일을 이용한 과전류 폴트 차단 기법에 관한 연구 (A Study on Shortcircuit Fault Protection Method Using Rogowski Coil)

  • 윤한종;조영훈
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2018년도 전력전자학술대회
    • /
    • pp.108-110
    • /
    • 2018
  • This paper proposes shortcircuit fault protection method in a synchronous buck converter using the PCB pattern Rogowski coil. The PCB pattern Rogowski coils are embedded in the gate driver to measure the device currents of the top and bottom side. When shortcircuit occurs in the system, the gate signal is blocked by the proposed fault protection method using the device current. The simulation and experimental results show that the proposed fault protection method is verified in the shortcircuit system.

  • PDF