• 제목/요약/키워드: Resistive type superconducting fault current limiter

검색결과 77건 처리시간 0.03초

전압증가 시 재폐로 동작에 따른 변압기형 초전도 한류기의 특성 분석 (Characteristics on the Transformer-Type SFCL According to Reclosing Operation the Voltage Increase)

  • 최수근;최효상
    • 전기학회논문지P
    • /
    • 제59권4호
    • /
    • pp.477-480
    • /
    • 2010
  • Fault current in power system is expected to increase by demand of power capacity. Therefore, when the fault occurred, fault current was increased in the power system. Many studies have been progressed to limit the fault current. Superconducting fault current limiter (SFCL) is one of them which has been studied in worldwide. In this paper, we will analyze characteristics of a transformer-type SFCL by reclosing operation when the voltage increases. Twice opening times in the reclosing of circuit breaker were set as the 0.5 and 15 seconds, respectively. Turn's number of primary and secondary coils set 4:2 and we increased voltages from 120V to 280V for each experiment. By the current waveform, maximum fault current in second and third cycles was lowered when the voltage was increased. In the recovery waveform, recovery time was increased as the voltage was increased. The reason was that power burden of the SFCL increased when consumption power was increased, so the time to get back to SFCL took longer. We compared the characteristics of a resistive-type and transformer-type SFCL. As a result, we found that the fault current of a transformer-type was lower than resistive-type and recovery time of the SFCL was shorter. Consequently, transformer-type SFCL was more profitable for limitation of fault current and recovery time under the same condition for reclosing operation.

배전계통 초전도 한류기 동작특성에 따른 계통 영향 분석 (System Effects by Operation Characteristics of Superconducting Fault Current Limiters in Distribution Systems)

  • 이상봉;김철환;김규호;김재철;현옥배
    • 전기학회논문지
    • /
    • 제57권7호
    • /
    • pp.1135-1140
    • /
    • 2008
  • Superconducting fault current limiters (SFCL) have been progressing due to the development of superconducting technology. The resistor type SFCL is one of the promising current limiting devices in power system for its effective operation. For proper application and operation of a SFCL, the prior investigation of fundamental characteristics and its effects to the distribution systems are needed. The most important current limiting behavior of a SFCL is dominated by quenching and recovery characteristics. In this paper, the resistive type SFCL was developed by using EMTP/ATPDraw and MODELS language. The operating characteristics and current limiting behaviors of the SFCL in distribution systems have been simulated and investigated.

Brief review of the field test and application of a superconducting fault current limiter

  • Hyun, Ok-Bae
    • 한국초전도ㆍ저온공학회논문지
    • /
    • 제19권4호
    • /
    • pp.1-11
    • /
    • 2017
  • This article reviews the recent activities of field testing and application of superconducting fault current limiters (SFCL) based on high-temperature superconductors (HTS). The review particularly focuses on the trends in the field tests in terms of the technical aspects and commercial activities of the SFCLs. Stimulated by the discovery of HTS, numerous research and development activities have been conducted worldwide for SFCLs operating from distribution voltages to transmission voltages. Different types of SFCLs have been developed and field-tested. Consequently, more than 20 field tests and applications have been performed on real grids worldwide while supplying electric power to the customers. These field tests have not only provided the track records of the operation experiences including the problems and maintenance during operation, but also proved their current limiting capabilities against real faults, rendering this new technology highly viable. Through these activities, the following trends in the status of field testing and application are observed. Resistive-type SFCLs with HTS-coated conductors were dominantly used in the most recent field tests. This implies that the resistive type is technically more mature than the other types. Bus-bar coupling and transformer feeders were the major application locations. It is of importance that most of the field applications were conducted as R&D projects. A relevant change from the R&D stage to the application stage is shown as recently deployed SFCLs are expected to be under long-term operation and commercial service. Here, we review the installation of these SFCLs by substation. This review also discusses the recent activities for their commercial applications.

Diode를 이용한 저항형 초전도 한류기의 열발생 저감방안 (Generated heat decrease of resistive superconducting fault current limiter using diodes)

  • 최효상;현옥배;김혜림;황시돌;김상준
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 하계학술대회 논문집 B
    • /
    • pp.925-927
    • /
    • 2000
  • We fabricated a resistive superconducting fault current limiter of meander type based on a YBCO film. In order to disperse the heat generated at hot spots in the YBCO film the film was coated with a gold shunt layer. When diodes were inserted in the parallel circuit to restrict the temperature increase in the SFCL element by reducing power supply cycles, the voltage could be increased to $\sqrt{2}$ times with the same quench resistance at a half and full cycles.

  • PDF

A Study on SFCL with IGBT Based DC Circuit Breaker in Electric Power Grid

  • Bae, SunHo;Kim, Hongrae;Park, Jung-Wook;Lee, Soo Hyoung
    • Journal of Electrical Engineering and Technology
    • /
    • 제12권5호
    • /
    • pp.1805-1811
    • /
    • 2017
  • Recently, DC systems are considered as efficient electric power systems for renewable energy based clean power generators. This discloses several critical issues that are required to be considered before the installation of the DC systems. First of all, voltage/current switching stress, which is aggravated by large fault current, might damage DC circuit breakers. This problem can be simply solved by applying a superconducting fault current limiter (SFCL) as proposed in this study. It allows a simple use of insulated-gate bipolar transistors (IGBTs) as a DC circuit breaker. To evaluate the proposed resistive type SFCL application to the DC circuit breaker, a DC distribution system is composed of the practical line impedances from the real distribution system in Do-gok area, Korea. Also, to reflect the distributed generation (DG) effects, several DC-to-DC converters are applied. The locations and sizes of the DGs are optimally selected according to the results of previous studies on DG optimization. The performance of the resistive type SFCL applied DC circuit breaker is verified by a time-domain simulation based case study using the power systems computer aided design/electromagnetic transients including DC (PSCAD/ EMTDC(R)).

YBCO 박막의 저항형 초전도 한류기에 대한 동작 특성 (Operating Properties for a Resistive SFCL of YBCO Thin Films)

  • 최효상;현옥배;김혜림;황시돌;김상준;문승현;한병성
    • 대한전기학회논문지:전기기기및에너지변환시스템부문B
    • /
    • 제48권10호
    • /
    • pp.537-543
    • /
    • 1999
  • We fabricated a resistive superconducting fault current limiter (SFCL) of a meander type based on a YBCO film with the meander cross section of 5 $\times$ $10^{-6}$$cm^2$, and performed current limitation experiments. The film was coated quench current was 9.6 Apeak at 60 Hz, and the fast quench time was 0.63 msec. The resistance of the limiter continuously increased for three cycles dut to the temperature rise in the gold layer. The temperature of the current limiting element reached the room temperature in 11 msec, $150^{\circ}C$ in 54 msec after quench, and was saturated afterwards. For $45^{\circ}$and $90^{\circ}$faults the fast quench times were 0.56 msec and 0.26 msec, respectively. The quench time is believed to be reduced because the fault occurred when the current was either increasing or at the peak value. This limiter effectively limited the fault current to about 1/5 of the potential current with no SFCL right after the fault and to about 1/8.5 in three cycles. We confirmed that the gold layer effectively carried out the role of heat dissipation as the SFCL was quenched.

  • PDF

변압기를 이용한 저항형 고온초전도 전류제한기의 한류 특성 (Fault Current Limiting Characteristics of Resistive Type SFCL using Transformer)

  • 임성훈;최효상;고석철;이종화;강형곤;한병성
    • 한국초전도저온공학회:학술대회논문집
    • /
    • 한국초전도저온공학회 2003년도 추계학술대회 논문집
    • /
    • pp.288-290
    • /
    • 2003
  • The transformer is expected to be an essential component of resistive type superconducting fault current limiter (SFCL) for both the increase of voltage ratings in SFCL and the simultaneous quench due to different critical current between HTSC elements. However, for the design to prevent the saturation of iron core and the effective fault current limitation, the analysis for operation of SFCL with consideration for the magnetization characteristics are required. In this paper, the fault current limiting characteristics related with the magnetization ones were investigated through the variation of the ratio of the number of turns in the 1st and the 2nd windings. The proper design condition with variation of the number of turns to make the effective fault current limiting operation could be determined.

  • PDF

YBCO film을 이용한 저항형 초전도 한류기의 전류제한 특성 (Current limiting characteristics of the resistive SFCL using YBCO film)

  • 최효삼;김혜림;황시돌;현옥배;김상준
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 A
    • /
    • pp.277-280
    • /
    • 1999
  • We fabricated a resistive superconducting fault current limiter of two stripe meander type based on a YBCO film, and performed current limitation experiments. In order to disperse the heat generated at hot spots in the YBCO film the film was coated with a gold shunt layer. At $0^{\circ}$ fault angle the minimum quench current was $9.6 A_{peak}$(meander line cross section: $5{\times}10^{-6}cm^2$) and the fast quench time was 0.63 msec. The resistance of the limiter continued to increase for three cycles due to heat generation in the gold layer and was stabilized afterwards. At $45^{\circ}$ and $90^{\circ}$ the fast quench time were 0.56 msec and 0.26 msec, respectively. The quench time is believed to be reduced because faults occurred when the current was increasing or was at the peak value. With the limiter we could effectively limit the fault current about 1/5 times right after the fault and about 1/8.5 times three cycles after.

  • PDF

Coated Conductor를 사용한 무유도 팬케이크형 한류 코일의 통전 손실 특성 (Transport Loss Characteristic of the Bifilar Pancake Type Fault Current Limiting Coil using Coated Conductor)

  • 박동근;방주석;양성은;안민철;심기덕;윤용수;남관우;석복렬;고태국
    • 한국초전도ㆍ저온공학회논문지
    • /
    • 제9권3호
    • /
    • pp.21-25
    • /
    • 2007
  • Superconducting fault current limiter (SFCL) is attractive apparatus to reduce fault current in power grid. Since it is applied to the alternating current (AC) power line, the SFCL has losses in the normal operation. Recently, coated conductor (CC) is noticeable material employed for resistive bifilar winding type SFCL in many research groups. Bifilar structure is expected to have low AC loss by magnetic field offset as compared with the single tape structure in the same length. This paper reports about characteristic of bifilar pancake type coil for SFCL application in AC loss aspect. The bifilar coil is wound using CC with facing on HTS sides each other. Transport AC loss measurement and characteristic analysis of the bifilar coil using CC have been performed at 77K. The test results are compared with the Norris equations and the test results of non-inductively wound paralleled solenoid type coil which is suggested and tested in this group at present.

고온초전도 한류기의 전력계통 적용에 관한 연구 (A Study on the Power System Application of High-Tc Superconducting Fault Current Limiter)

  • 배형택;유인근
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2006년도 제37회 하계학술대회 논문집 A
    • /
    • pp.115-116
    • /
    • 2006
  • Since the discovery of the high-temperature superconductors, many researches have been performed for the practical applications of superconductivity technologies in various fields. As results, significant progress has been achieved. Especially, Superconducting Fault Current Limiter (SFCL) offers an attractive means to limit fault current in power systems. The SFCLS, in contrast to current limiting reactors or high impedance transformers, are capable of limiting short circuit currents without adding considerable voltage drop and energy loss to power systems during normal operation. Under fault conditions, a resistance is automatically inserted into the power grid to limit the peak short-circuit current by transition from the superconducting state to the normal state, the quench. The advantages, like fail safe operation and quick recovery, make SFCL very attractive, especially for rapidly growing power systems with higher short-circuit capacities. In order to verify the effectiveness of the SFCL, in this paper, the analysis of fault current and voltage stability assessment in a sample distribution system and a transmission system are performed by the PSCAD/EMTDC based simulation method. Through the simulation, the advantage of SFCL application is shown, and the effective parameters of the SFCL are also recommended for both distribution and transmission systems. A resistive type component of SFCL is adopted in the analysis. The simulation results demonstrate not only the effectiveness of the proposed simulation scheme but also SFCL parameter assessment technique.

  • PDF