Fault Current Limiting Characteristics of Resistive Type SFCL using Transformer

변압기를 이용한 저항형 고온초전도 전류제한기의 한류 특성

  • 임성훈 (전북대학교 공학연구원) ;
  • 최효상 (조선대학교 전기공학) ;
  • 고석철 (전북대학교 전자정보공학) ;
  • 이종화 (전북대학교 전자정보공학) ;
  • 강형곤 (전북대학교 반도체물성센) ;
  • 한병성 (전북대학교 전자정보공학부)
  • Published : 2003.10.01

Abstract

The transformer is expected to be an essential component of resistive type superconducting fault current limiter (SFCL) for both the increase of voltage ratings in SFCL and the simultaneous quench due to different critical current between HTSC elements. However, for the design to prevent the saturation of iron core and the effective fault current limitation, the analysis for operation of SFCL with consideration for the magnetization characteristics are required. In this paper, the fault current limiting characteristics related with the magnetization ones were investigated through the variation of the ratio of the number of turns in the 1st and the 2nd windings. The proper design condition with variation of the number of turns to make the effective fault current limiting operation could be determined.

Keywords