Browse > Article
http://dx.doi.org/10.5370/JEET.2017.12.5.1805

A Study on SFCL with IGBT Based DC Circuit Breaker in Electric Power Grid  

Bae, SunHo (School of Electrical and Electronic Engineering, Yonsei University)
Kim, Hongrae (Dept. of Electronic Information Engineering, Soonchunhyang University)
Park, Jung-Wook (School of Electrical and Electronic Engineering, Yonsei University)
Lee, Soo Hyoung (Korea Electrotechnology Research Institute (KERI))
Publication Information
Journal of Electrical Engineering and Technology / v.12, no.5, 2017 , pp. 1805-1811 More about this Journal
Abstract
Recently, DC systems are considered as efficient electric power systems for renewable energy based clean power generators. This discloses several critical issues that are required to be considered before the installation of the DC systems. First of all, voltage/current switching stress, which is aggravated by large fault current, might damage DC circuit breakers. This problem can be simply solved by applying a superconducting fault current limiter (SFCL) as proposed in this study. It allows a simple use of insulated-gate bipolar transistors (IGBTs) as a DC circuit breaker. To evaluate the proposed resistive type SFCL application to the DC circuit breaker, a DC distribution system is composed of the practical line impedances from the real distribution system in Do-gok area, Korea. Also, to reflect the distributed generation (DG) effects, several DC-to-DC converters are applied. The locations and sizes of the DGs are optimally selected according to the results of previous studies on DG optimization. The performance of the resistive type SFCL applied DC circuit breaker is verified by a time-domain simulation based case study using the power systems computer aided design/electromagnetic transients including DC (PSCAD/ EMTDC(R)).
Keywords
DC circuit breaker; DC distribution system; Insulated-gate bipolar transistor (IGBT); Non-zero-crossing switching; Superconducting fault current limiter (SFCL);
Citations & Related Records
연도 인용수 순위
  • Reference
1 B. C. Sung, D. K. Park, J. W. Park, and T. K. Ko, "Study on a Series Resistive SFCL to Improve Power System Transient Stability: Modeling, Simulation, and Experimental Verification," IEEE Trans. Ind. Electron., vol. 56, no. 7, pp. 2412-2419, Jul. 2009.   DOI
2 A. Mokhberdoran, A. Carvalho, H. Leite, and N. Silva, "A Review on HVDC Circuit Breakers," in proc. of Renewable Power Generation Conf. (RPG 2014), 3rd, pp. 1-6, Sep. 2014.
3 R. Derakhshanfar, T.U. Jonsson, U. Steiger, and M. Habert, "Hybrid HVDC breaker-Technology and applications in point-to-point connections and DC grids," in proc. of CIGRE 2014, pp. 1-11, Aug. 2014.
4 M. Callavik, A. Blomberg, J. Hafner, and B. Jacobson, "The Hybrid HVDC Breaker-An innovation breakthrough enabling reliable HVDC grids," ABB Grid Systems, Technical Paper, pp. 1-10, Nov. 2012.
5 C. Meyer, M. Kowal, and R. W. De Doncker, "Circuit breaker concepts for future high-power DC-applications," in Proc. of 40th IEEE IAS Annu.Meet. Conf., vol. 2, pp. 860-866, Oct. 2005.
6 High Voltage IGBT Modules (HV-IGBT), Mitsubishi Electric Inc., Available: http://www.hy-line.de/fileadmin/hy-line/power/hersteller/mitsubishi/dokumente/HVModule_hy.pdf
7 HVDC LightO It's time to connect, ABB Inc., Available: http://www05.abb.com/global/scot/scot221.nsf/veritydisplay/2742b98db321b5bfc1257b26003e7835/$file/Pow0038%20R7%20LR.pdf
8 S. H. Lee and J. W. Park, "Selection of Optimal Location and Size of Multiple Distributed Generations by Using Kalman Filter Algorithm," IEEE Trans. on Power Systems, vol. 24, no. 3, pp. 1393-1400, Aug. 2009.   DOI
9 S. H. Lee and J. W. Park, "Optimal Placement and Sizing of Multiple DGs in a Practical Distribution System by Considering Power Loss," IEEE Trans. on Industry Applications, vol. 49, no. 5, pp. 2262-2270, Sep. 2013.   DOI
10 D. Salomonsson and A. Sannino, "Low-Voltage DC Distribution System for Commercial Power Systems with Sensitive Electronic Loads," IEEE Trans. on Power Delivery, vol. 22, no. 3, pp. 1620-1627, Jul. 2007.   DOI
11 L. Varnado, M. Sheehan, Connecting to the Grid, A Guide to Distributed Generation Interconnection Issues, 6th ed., Interstate Renewable Energy Council (IREC) Connecting to the Grid Project, p. 27, 2009.
12 A. Sannino, G. Postiglione, and M. H. J. Bollen, "Feasibility of a DC network for commercial facilities," IEEE Trans. on Industry Applications, vol. 39, no. 5, pp. 1499-1507, Sep. 2003.   DOI
13 H. Kakigano, Y. Miura, and T. Ise, "Low-Voltage Bipolar-Type DC Microgrid for Super High Quality Distribution," IEEE Trans. on Power Electronics, vol. 25, no. 12, pp. 3066-3075, Dec. 2010.   DOI
14 Y. Morishita, T. Ishikawa, I. Yamaguchi, S. Okabe, G. Ueta, and S. Yanabu, "Applications of DC Breakers and Concepts for Superconducting Fault-Current Limiter for a DC Distribution Network," IEEE Trans. on Applied Superconductivity, vol. 19, no. 4, Aug. 2009.
15 G. S. Seo, J. Baek, K. Choi, H. Bae, and B. Cho, "Modeling and Analysis of DC Distribution Systems," in proc. of IEEE 8th International Conference on Power Electronics and ECCE Asia, pp. 223-227, May 2011.
16 H. S. Ruiz, X. Zhang and T. A. Coombs, "Resistive-Type Superconducting Fault Current Limiters: Concepts, Materials, and Numerical Modeling," IEEE Trans. on Applied Superconductivity, vol. 25, no. 3, Jun. 2015.
17 D. Sharma and K. B. Sahay, "Basic concepts of superconducting fault current," IEEE International Conference on Power Electronics, Intelligent Control and Energy Systems (ICPEICES), no. 16673229, Jul. 2016.
18 O. B. Hyun, S. D. Cha, H. R. Kim, H. S. Choi, and S. D. Hwang, "Shunt-Assisted Simultaneous Quenches in Series-Connected Resistive SFCL Components," IEEE Trans. Ind. Electron., vol. 13, no. 2, pp. 2060-2063, Jun. 2003.
19 W. J. Park, B. C. Sung, K. B. Song, and J. W. Park, "Parameter Optimization of SFCL With Wind-Turbine Generation System Based on Its Protective Coordination," IEEE Trans. on Applied Superconductivity, vol. 21, no. 3, Jun. 2011.