• Title/Summary/Keyword: Resistive leakage current

Search Result 70, Processing Time 0.023 seconds

Development of Remote Supervision System for Guam Lamps by Way of Leakage Current(Igr) Detection Method (보안등 전거설비의 Igr 누설전류 검출 및 원격감시장치 개발)

  • Choi, Myeong-Il;Kim, Young-Seok;Kim, Chong-Min;Bang, Sun-Bae
    • Journal of the Korean Society of Safety
    • /
    • v.25 no.6
    • /
    • pp.75-80
    • /
    • 2010
  • The present study presented the implementation of a remote control/supervision system for guard lamps used in public illumination with little endeavor by far for safe management, which makes possible to supervise the state and to control the functions remotely including electric safety elements. Especially, the developed system adopts the measurement algorithm for detecting resistive leakage current(Igr) flowing based on the phase difference checkable for sensing at a monitor, being allowable for monitoring at MMI and transmitter for data transmittance. To verify reliability about the algorithm to accurately detect Igr leakage current, the laboratory-based functional test was performed.

Effects of Lightning Surges on the Life of ZnO Varistors (뇌서지가 ZnO바리스터에 미치는 영향)

  • Lee, Bong;Lee, Su-Bong;Kang, Sung-Man;Lee, Bok-Hee
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.55 no.5
    • /
    • pp.257-262
    • /
    • 2006
  • To evaluate the change in protective levels of zinc oxide (ZnO) varistors after the surge absorption, this paper investigated the effects of the number of injection and amplitude of lightning surges on the life of ZnO varistors for low voltages. Leakage currents flowing through ZnO varistors subjected to the $8/20{\mu}s$ impulse currents under 60 Hz AC voltages were measured. The surge simulator system ECAT that can generate $8/20{\mu}s$ impulse currents with a peak short-circuit of 5 $[kA_p]$ was used. The ZnO varistor leakage current increases with exposure to impulse current, and the number of injection of $8/20{\mu}s$ impulse currents to breakdown was inversely proportional to the amplitude of the test current. Behaviors of ZnO varistor leakage currents were strongly dependent on the number of injection and amplitude of $8/20{\mu}s$ impulse currents. ZnO varistors degrade gradually when subjected to impulse current, and the resistive leakage current flowing through ZnO varistors subjected to the $8/20{\mu}s$ impulse currents under 60 Hz AC voltages was significantly increased after a certain number of injection that is dependent on the amplitude of the test impulse current. As a result, the life of ZnO varistors mainly depends on the amplitude and occurrence frequency of lightning surges.

A Study on the Diagnostic Techniques of Leakage Current for Switch-Gear Based on LabVIEW (LabVIEW 기반의 수배전반 누설전류 진단기법 연구)

  • Kim, Yong-Seong;Jang, Sung-Il;Choi, Jung-Hwan;Kim, Kwang-Ho
    • Journal of Industrial Technology
    • /
    • v.34
    • /
    • pp.61-66
    • /
    • 2014
  • Recently, Because the consumption of electricity is increased, having stable electricity supply and diagnosis of the power device is important. In this paper, I propose a diagnostic techniques of the leakage current for switchgear based on LabVIEW NI's. Using the data obtained from the leakage current sensor installed in switchgear panels, in performed continuously diagnosis, notifications and warnings can be the administrator immediately results. It is expected accordingly, the administrator will be able to take prompt action. Using the virtual switchgear with a PXI NI's, war tested the proposed techniques.

  • PDF

Accelerating aging test of distribution lightning arresters (배전용 피뢰기의 가속열화시험)

  • 김주용;송일근;김찬영;이병성;문재덕
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2000.07a
    • /
    • pp.596-598
    • /
    • 2000
  • This paper presents a new accelerating aging test facility for distribution lightning arresters. Aging parameters of lightning arrester are moisture ingress, electrical stress and surge absorption and so on. In this system, we applied 13.2kV to 6 samples and controled temperature and humidity of chamber and measured leakage currents of the all samples. Also we developed accelerating aging cycle which consists of -35$^{\circ}C$∼90$^{\circ}C$ temperature and 40%∼90% humidity. Through the aging test we found out the leakage current of aged sample increases rapidly according to the temperature rising. Hereafter we can determine the replacement guide of leakage current for field operating arresters and condition assessment of aged samples through this aging test.

  • PDF

Temperature dependent characteristics of leakage currents of ZnO blocks (온도에 따른 ZnO 피뢰기 소자의 누설전류의 온도의존성)

  • Lee, Bok-Hee;Lee, Su-Bong;Li, Feng;Kim, Dong-Sung
    • Proceedings of the KIEE Conference
    • /
    • 2006.07c
    • /
    • pp.1572-1573
    • /
    • 2006
  • This paper presents electrical properties of Zinc Oxide(ZnO) surge arrester blocks under the power frequency AC voltages and various temperatures. The leakage current, $I_{R}-V$ curios and power dissipation for the fine and aged ZnO surge arrester blocks were measured as a function of the temperatures and applied voltages. When the temperature is increased from $50\;[^{\circ}C]$ to $150\;[^{\circ}C]$, the total leakage current significantly increased at the sane applied voltage level. Also, the resistive leakage currents and power dissipation were increased with increasing temperature. The leakage current and power dissipation of the aged ZnO arrester blocks were higher than the fine ZnO arrester blocks.

  • PDF

Electrical properties of 18kV ZnO surge arrester according to the variation of surrounding conditions (외부환경 변화에 따른 배전용 피뢰기의 전기적 특성)

  • Lee, Bok-Hee;Lee, Seung-Ju;Lee, Su-Bong;Jung, Dong-Sung;Shin, Hee-Kyung
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2008.05a
    • /
    • pp.289-292
    • /
    • 2008
  • This paper describes the electrical characteristics of the ZnO surge arrester according to the variation of surrounding conditions. To investigate the characteristics of degraded ZnO surge arrester, 8/20 [${\mu$s], 2.5 [kA] impulse currents were applied to the ZnO surge arrester to be test. To present the effect of the surrounding con야tions, the leakage currents of ZnO surge arrester were measured to the surrounding temperature and wet conditions. As a result, the increase of ambient temperature causes the increase of resistive leakage current of ZnO surge arrester. Also, in the wet test, the outside leakage current through the ZnO surge arrester housing is much larger than the intrinsic leakage current.

  • PDF

Aging Characteristics of ZnO Surge Arresters (ZnO 피뢰기의 경년변화 특성분석)

  • 김주용;김찬영;송일근;이병성;한용희
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 1999.05a
    • /
    • pp.383-386
    • /
    • 1999
  • Surge arrestor is used for protection of facilities and lines. Recently lots of arresters fatted prematurely In the distribution lines. It is important to know that what the cause of the failures is. This paper presents characteristics of the aged and new 18kV surge arrester. In order to analyse characteristics, we measured leakage current using specialty made leakage current measurement system and also investigated Tan $\delta$ of the arrester and microstructure of the elements. Through the investigation we found that the characteristics among the ZnO elements in an arrester were a little different, It means that the surge arreste can have non-uniform electric field due to the characteristic difference of The each element. Owing to this concentration of the electric field, the localized aging might be proceeded.

  • PDF

Increased impedance by quench at a shield layer of HTS power cable for fault current limiting function

  • Choi, Youngjun;Kim, Dongmin;Cho, Jeonwook;Sim, Kideok;Kim, Sungkyu;Kim, Seokho
    • Progress in Superconductivity and Cryogenics
    • /
    • v.21 no.4
    • /
    • pp.59-63
    • /
    • 2019
  • To reduce the fault current below the current capacity of a circuit breaker, researches on HTS (High Temperature Superconductor) power cables with fault current limiting (FCL) function are increasing. An FCL HTS power cable transports current with low a impedance during normal operation. Yet, it limits the fault current by an increased inductive or resistive impedance of conducting layer when quench occurs at the FCL HTS power cable by the large fault current. An inductive type FCL HTS power cable uses increased inductive impendence caused by leakage magnetic flux outside the cable core when the quench occurs at a shield layer losing the magnetic shielding effect. Therefore, it has an advantage of less resistive heating than resistive type FCL HTS power cable and temperature increase is suppressed. This paper describes an ideal circuit model for the FCL HTS power cable to investigate the effectiveness of increased inductive impedance when quench occurs at the shield layer. Then, FEM analysis is presented with a simplified model cable composed of various iron yokes to investigate the effect of the shape of yoke on the generation of the inductive impedance.

A New Approach to On-Line Monitoring Device for ZnO Surge Arresters

  • Lee Bok-Hee;Gil Hyoung-Jun;Kang Sung-Man
    • KIEE International Transactions on Electrophysics and Applications
    • /
    • v.5C no.3
    • /
    • pp.131-137
    • /
    • 2005
  • This paper describes a new approach to the algorithm and fundamental characteristics of the device for monitoring the leakage currents flowing through zinc oxide (ZnO) surge arresters. In order to obtain a technique for a new on-line monitoring device that can be used in the deterioration diagnosis of ZnO surge arresters, the new algorithm and on-line leakage current detection device for extracting the resistive and capacitive currents using the phase shift addition method were proposed. The computer-based on-line monitoring device can sense accurately the power frequency leakage currents flowing through ZnO surge arresters. The on-line leakage current monitoring device of ZnO surge arresters proposed in this work has the high sensitivity compared to the third harmonic leakage current detection devices. As a consequence, it was found that the proposed leakage current monitoring device would be useful for forecasting the defects and degradation of ZnO surge arresters.

Implementation of an Export System for GIS Arrester Facilities (GIS 피뢰설비 전문가 시스템 구현)

  • Kim, Il-Kwon;Song, Jae-Yong;Moon, Seung-Bo;Cha, Myung-Soo;Rhyu, Keel-Soo;Kil, Gyung-Suk
    • Proceedings of the KIEE Conference
    • /
    • 2006.07c
    • /
    • pp.1465-1466
    • /
    • 2006
  • The monitoring and diagnosing technique for lightning arresters is important to assure the reliability of power supply in GIS-substation. In this paper, we described the implementation of an expert system for GIS arrester facilities. The proposed system consists of a data acquisition module (DAM), a wireless communication module, and a personal computer. The DAM detects system voltages, total leakage currents and its harmonic components, and includes an algorithm to calculate the resistive leakage current by the principle that the magnitudes of resistive leakage current are equal at the same level of the system voltage applied to the arrestor. Also, we designed a surge event detection circuit which can acquire the date, the polarity, and the amplitude of surge events. All the acquired data are transmitted after correction by many algorithms to the remote station through the ZigBee protocol. The expert system is based on the Jave Expert System Shell (JESS) and make more reliable decision by using an exclusive inference process.

  • PDF