• Title/Summary/Keyword: Resistive current

Search Result 449, Processing Time 0.026 seconds

A Study on SFCL with IGBT Based DC Circuit Breaker in Electric Power Grid

  • Bae, SunHo;Kim, Hongrae;Park, Jung-Wook;Lee, Soo Hyoung
    • Journal of Electrical Engineering and Technology
    • /
    • v.12 no.5
    • /
    • pp.1805-1811
    • /
    • 2017
  • Recently, DC systems are considered as efficient electric power systems for renewable energy based clean power generators. This discloses several critical issues that are required to be considered before the installation of the DC systems. First of all, voltage/current switching stress, which is aggravated by large fault current, might damage DC circuit breakers. This problem can be simply solved by applying a superconducting fault current limiter (SFCL) as proposed in this study. It allows a simple use of insulated-gate bipolar transistors (IGBTs) as a DC circuit breaker. To evaluate the proposed resistive type SFCL application to the DC circuit breaker, a DC distribution system is composed of the practical line impedances from the real distribution system in Do-gok area, Korea. Also, to reflect the distributed generation (DG) effects, several DC-to-DC converters are applied. The locations and sizes of the DGs are optimally selected according to the results of previous studies on DG optimization. The performance of the resistive type SFCL applied DC circuit breaker is verified by a time-domain simulation based case study using the power systems computer aided design/electromagnetic transients including DC (PSCAD/ EMTDC(R)).

Development of Remote Supervision System for Guam Lamps by Way of Leakage Current(Igr) Detection Method (보안등 전거설비의 Igr 누설전류 검출 및 원격감시장치 개발)

  • Choi, Myeong-Il;Kim, Young-Seok;Kim, Chong-Min;Bang, Sun-Bae
    • Journal of the Korean Society of Safety
    • /
    • v.25 no.6
    • /
    • pp.75-80
    • /
    • 2010
  • The present study presented the implementation of a remote control/supervision system for guard lamps used in public illumination with little endeavor by far for safe management, which makes possible to supervise the state and to control the functions remotely including electric safety elements. Especially, the developed system adopts the measurement algorithm for detecting resistive leakage current(Igr) flowing based on the phase difference checkable for sensing at a monitor, being allowable for monitoring at MMI and transmitter for data transmittance. To verify reliability about the algorithm to accurately detect Igr leakage current, the laboratory-based functional test was performed.

Operating properties of resistive type superconducting fault current limiters with a single line-to-ground fault (1선지락사고에 대한 초전도한류기의 동작특성)

  • Park, Hyo-Sang;Park, Chang-Joo;Lee, Sang-il;Chung, Soo-Bok;Oh, Geum-Kon;Chung, Hun-Sang
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2003.11a
    • /
    • pp.279-281
    • /
    • 2003
  • We analysed the operating properties of resistive type superconducting fault current limiters (SFCLs) based on YBCO thin films with a single line-to-ground fault. When a single line-to-ground fault occurred, the short circuit current of a fault phase increased up to about 6 times of transport currents immediately after the fault instant and was effectively limited to the designed current level within 2 ms by the resistance development of the SFCL. The fault currents of the sound phases almost did not change because of their direct grounding system. The unsymmetrical rates of a fault phase were distributed from 6.4 to 1.4. It was found that the unsymmetrical rates of currents were noticeably improved within one cycle after the fault instant. We calculated the zero phase currents for a single line-to-ground fault using the symmetrical component analysis. The positive sequence resistance was reduced remarkably right after the fault but eventually approached the balanced positive resistance component prior to the system fault. This means that the system reaches almost the three-phase symmetrical state in about 60 ㎳ after the fault. The ground currents were almost 3 times of the zero phase mts since most of the fault currents flowed through the grounding line.

  • PDF

Development of 6.6kV Resistive Superconducting Fault Current Limiters (6.6kV급 초전도 저항형 한류기 개발에 관한 연구)

  • Lee, B.W.;Park, K.B.;Kang, J.S.;Kim, H.M.;Oh, I.S.;Hyun, O.B.
    • Proceedings of the KIEE Conference
    • /
    • 2004.07c
    • /
    • pp.1745-1747
    • /
    • 2004
  • In order to anticipate gradual increase of fault current in electric power systems, current limiting technology and current limiting device has been investigated for a long time. But the commercial use of current limiting device was delayed due to the lack of effective method to insert impedance to the elective power systems without loss and surplus defects. However, novel current limiting device, which use superconducting materials, was considered as a dream technology to be applied in a distribution and transmission lines. LG Industrial systems and KERPI started to investigate resistive type superconducting fault current limiters in order to develop 154kV fault current limiters and this year, we succeed to test 3 phase 6.6kV/200A fault current limiters. Based on these achievements, 24kV superconducting fault current limiters will be realized withing 3 years which could be tested in a real fields. In this paper, the developments of fault current limiting module which use YBCO thin films, cryogenic systems, the structure and construction of 3 phase fault current limiters and finally the test results of 6.6kV superconducting fault current limiters will be introduced.

  • PDF

Feasibility study on the inductive fault current limiting cable

  • Lee, Sang Yoon;Choi, Jongho;Kim, Dong Min;Sim, Kideok;Cho, Jeonwook;Kim, Seokho
    • Progress in Superconductivity and Cryogenics
    • /
    • v.15 no.3
    • /
    • pp.24-28
    • /
    • 2013
  • Fault current limiting (FCL) cable is a kind of superconducting cable which has a function of limiting the fault current at the fault of power grid. The superconducting cable detours the fault current through its stabilizer to keep the temperature as low as possible. On the other hands, the FCL cable permits the temperature rise within some acceptable limit and the fault current is limited by the consequent increase of the resistance of superconducting cable. This kind of FCL cable is called 'resistive FCL cable' because it uses resistive impedance to limit the fault current. In this paper, we suggest a novel concept of FCL cable, which is named as 'inductive FCL cable'. The inductive FCL cable is similar as the magnetic shielding fault current limiter in its operating mechanism. The magnetic field of superconducting cable is almost perfectly shielded by the induced current at the shielding layer during its normal operation. However, at the fault condition, quench occurs at the shielding layer by the induced current higher than its critical current and the magnetic field is spread out of the shielding layer. It will induce additional inductive impedance to the superconducting cable and the inductive impedance can be increased more by installing some material with high magnetic susceptibility around the superconducting cable. We examined the feasibility of inductive FCL cable with simple elemental experiments. The current limiting performance of inductive FCL cable was estimated considering an arbitrary power grid and its fault condition.

Performance of Superconducting Fault Current Limiter for Real Substation (초전도 한류기의 실계통 적용 시의 한류 특성 해석)

  • 김홍규;이병윤;박경엽
    • Proceedings of the Korea Institute of Applied Superconductivity and Cryogenics Conference
    • /
    • 2003.10a
    • /
    • pp.201-204
    • /
    • 2003
  • This paper presents the analysis of current limiting performance of superconducting fault current limiter(SCFCL) for real substation. The resistive and inductive type SCFCLs are investigated for 154㎸ substation. The current limiting performance of SCFCL is evaluated with respect to the time constant of SCFCL and impedance of SCFCL.

  • PDF

A Study of Quench Behaviors in YBCO Flims for Superconducting Fault Current Limiter (기포발생에 따른 초전도 한류기용 YBCO 박막 퀜치특성 연구)

  • Kang, J.S.;Park, K.B.;Lee, B.W.;Oh, I.S.;Kim, H.R.
    • Proceedings of the KIEE Conference
    • /
    • 2002.07b
    • /
    • pp.796-798
    • /
    • 2002
  • In these days, the interruption capability of some circuit breakers, which are installed in the transmission systems, is getting lower than the magnitude of the fault current because of continuous increase of power demand and relatively short power line which was installed in forms of mesh network As a result of these situations, fault current limiters (FCLs) are strongly necessary. There are various types which is investigated around the world, and new power apparatuses that have been newly considered and developed by many manufactures. In this paper, we considered resistive superconducting fault current limiters with YBCO thin films. The resistive limiters utilize a transition of YBCO films from superconducting to normal state caused by exceeding the critical current. By means of newly occurred impedance, the fault current will be limited effectively. Generally, a few current path patterns are available for YBCO films to enhance the current limiting performance of YBCO films. In this paper. the meander-type and the bi-spiral-type were used for current paths of YBCO flims. When YBCO films are quenched into the normal state, bubbles could be observed on the surface of YBCO films. Using our high-speed camera, the number of bubbles and the size of bubbles could be visualized and the relation between bubbles and current density was analyzed. By means of moving pictures of bubbles, we observed how the quench extended or how the heat was conducted in films.

  • PDF

Analysis on Current Limiting Characteristics of the SFCL with Magnetically Coupled Two Coils and YBCO Coated Conductor Due to the Winding Direction and the Turn Number' Ratio Between Two Coils (직렬 연결된 두 코일과 YBCO Coated Conductor로 구성된 초전도 전류제한기의 권선방향과 권선 비에 따른 전류제한 특성 분석)

  • Lee, Dong-Hyeok;Du, Ho-Ik;Kim, Yong-Jin;Han, Byoung-Sung;Han, Sang-Chul;Lee, Jeong-Phil
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.24 no.1
    • /
    • pp.52-56
    • /
    • 2011
  • The ongoing Superconducting Fault Current Limiter(SFCL) development mainly has focused on the application of commercializaton and power system through combining with normal-conducting device, moving away from current-limiting method, which is solely dependant on the existing superconductor. Compared to the structural development above, on the other hand, the research on applying superconducting current-limiting element to SFCL, the heart of SFCL, still has a lot left to do, apart form traditional resistive type SFCL. In this study, we looked into the current limiting characteristic of SFCL using core and coil. YBCO coated conductor with stainless steel stabilizer layer was verified by the excellent of current-limiting element of the resistive type SFCL that has a high Jc and index as well as being superior in mechanical property. Also, we study temperature characteristics and resistance characteristics, max voltage, response time and current-limiting ability that can be an indicator as current-limiting element while applying to superconducting current-limiting element caused by variation of winding direction, winding ratio of SFCL using core and coil.

A Study on The Ignition Limit of Flammable Gases by Discharge Spark of Resistive Circuit (저항회로의 개폐불꽃에 의한 폭발성 가스의 점화한계에 관한 연구)

  • Lee Chun-Ha
    • Journal of the Korean Institute of Gas
    • /
    • v.1 no.1
    • /
    • pp.106-112
    • /
    • 1997
  • This study measured the ignition limits of methane-air, propane-air, ethylene-air, and hydrogen-air mixture gases by discharge spark of D.C. power resistive circuit. The used experimental device is the IEC type spark ignition test apparatus, it consists of explosion chamber and supply -exhaust system of mixture gas. Mixture gases (methane-air, propane-air, ethylene-air, and hydrogen-air) were put into explosion chamber of IEC type spark ignition test apparatus, then it was confirmed whether ignition was made by 3,200 times of discharge spark between tungsten electrode and cadmium electrode. The ignition limits were found by increasing or decreasing the value of current. For the exact experiment, the ignition sensitivity was calibrated before and after the experiment in each condition. The ignition limits were found by changing the value of concentration of each gas-air mixture in D.C. 24 [V] resistive circuit. As the result of experiment, it was found that the minimum ignition limit currents exist at the value of methane-air 8.3 [$Vol\%$], propane-air 5.25[$Vol\%$], ethylene-air 7.8 [$Vol\%$], and hydrogen-air 21[$Vol\%$] mixture gases. For each the minimum ignition concentration of gases, the relationships between voltage and minimum ignition current were found. The results are as follows. - The minimum ignition limits are decreasing in the order of methane, propane, ethylene, and hydrogen. - The value of ignition current is inversely proportional to the value of source voltage. - The minimum ignition limit currents increase sharply at more than 2 [A]. The reason is caused by overheating the electrode.

  • PDF

On the Current Limiting Characteristics and Parameters of Superconducting Fault Current Limiter Introduced to 345kV Electric Power System due to Resistive-Type, Reactive-Type and Their Performance Comparison (유도형과 저항형 초전도한류기의 파라메타를 고려한 전력계통도입효과의 분석 및 성능평가에 관한 연구)

  • 홍원표;김용학
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.16 no.3
    • /
    • pp.74-83
    • /
    • 2002
  • The maximun short circuit current of modern power system is becoming so large that circuit breaker is not expected to be able to shut down the current in the future In order cut over-currents, a system composed of a superconducting fault current limiter(SFCL) and traditional breaker seems to provide a promising solution for furture power operation. In present paper, three line-to-ground fault is assumed to happen at the center of 345kV transmission lines in a large capacity electric power system. The superconducting fault current limiter was represented using a commutation type, which consists of a non-inductive superconducting coil and current limiting element (resistor or reactor). from the viewpoint of current limiting performance, the prevention of the voltage drop at the load bus and comparision characteristics for two type SFCL. Desired design specification and operation parameters of SECL were also given qualitatively by the performance.