• Title/Summary/Keyword: Reactive power capability

Search Result 109, Processing Time 0.021 seconds

Calculation of Active Power Transfer Capability using Repeated Power Flow Program

  • Ham, Jung-Pil;Kim, Jung-Hoon;Lee, Byung-Ha;Won, Jong-Ryul
    • KIEE International Transactions on Power Engineering
    • /
    • v.12A no.1
    • /
    • pp.15-19
    • /
    • 2002
  • The power transfer capability is determined by the thermal, dynamic stability and voltage limits of the generation and transmission systems. The voltage stability depends on the reactive power limit and it affects the power transfer capability to a great extent. Then, in most load flow analysis, the reactive power limit is assumed as fixed, relatively different from the actual case. This paper proposes a method for determining the power transfer capability from a static voltage stability point of view using the IPLAN which is a high level language used with PSS/E program. The f-V curve for determining the power transfer capability is determined using Repeated Power Flow method. It Is assumed that the loads are constant and the generation powers change according to the merit order. The maximum reactive power limits are considered as varying similarly with the actual case and the effects of the varied maximum reactive power limits to the maximum power transfer capability are analyzed using a 5-bus power system and a 19-bus practical power system.

Development of Generator Reactive Capability Test Method in Generation Stations (발전기 무효전력 성능시험 절차 개발)

  • Shin, Man-Su;Jeong, Tae-Won
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.60 no.5
    • /
    • pp.936-941
    • /
    • 2011
  • Generation cooperations have focused on active power directly related to economic value. So, utility cooperation have taken expense to stabilize power system, although generator has responded quickly with variation of power system voltage and is controlled at real time. As a reactive power source, it is necessary for generator's capabilities to be verified. But domestic generators scarcely have been tested and operated to reactive power capability. In case of power system fault, operators would not quickly take a follow-up actions about reactive power disturbance. Therefore generator reactive power capability verification strategy must be developed, several generators is tested as examples since 2004. This paper is extracted from the test results.

Reactive Power Capability Verification Strategy (발전기 무효전력 성능시험 절차서 정립)

  • Shin, Man-Su;Lee, Ju-Hyun;Lim, Ick-Heon;Ryu, Ho-Seon;Shin, Jung-Seon;Byun, Seong-Hyun
    • Proceedings of the KIEE Conference
    • /
    • 2006.07a
    • /
    • pp.87-88
    • /
    • 2006
  • Generator has responded quickly with variation of power system voltage and is controlled at real time. As a reactive power source, generator is revalued better than power condenser and as a reactive power sink, is revalued. But Domestic generators scarcely have been tested and operated to reactive power capability. In case of power system fault, operators wouldn't quickly take a follow-up measures about reactive power disturbance. Therefore generator reactive power capability verification strategy must be developed, several generators is tested as a exhibition since 2004. This paper is extract from the test contents.

  • PDF

Transfer Capability Enhancement to Population Center Using VSC HVDC System (부하집중지로의 송전용량 증대를 위한 전압형 HVDC의 활용 방안)

  • Oh, Sea-Seung;Han, Byung-Moon;Cha, Jun-Min;Jang, Gil-Soo
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.55 no.6
    • /
    • pp.236-241
    • /
    • 2006
  • This paper presents a transfer capability enhancement process using VSC HVDC system which can control active power as well as reactive power. The transfer capability is constrained by stability like voltage stability as well as thermal rating of power system components. Transfer capability of the power system limited by these constraints may be enhanced by reactive power control ability and active power flow control ability of the VSC HVDC system. To enhance the transfer capability of the system using VSC HVDC, selection of the HVDC installation site is performed. In this work, power zones which consist of major power plants and their sinks are identified using power tracing and distribution factor. Alternative route of major AC transmission line in the power zone is identified as VSC HVDC system.

Hierarchical Voltage Control of a Wind Power Plant Using the Adaptive IQ-V Characteristic of a Doubly-Fed Induction Generator

  • Kim, Jinho;Park, Geon;Seok, Jul-Ki;Lee, Byongjun;Kang, Yong Cheol
    • Journal of Electrical Engineering and Technology
    • /
    • v.10 no.2
    • /
    • pp.504-510
    • /
    • 2015
  • Because wind generators (WGs) in a wind power plant (WPP) produce different active powers due to wake effects, the reactive power capability of each WG is different. This paper proposes a hierarchical voltage control scheme for a WPP that uses a WPP controller and WG controller. In the proposed scheme, the WPP controller determines a voltage error signal by using a PI controller and sends it to a doubly-fed induction generator (DFIG). Based on the reactive current-voltage ($I_Q-V$) characteristic of a DFIG, the DFIG injects an appropriate reactive power corresponding to the voltage error signal. To enhance the voltage recovery capability, the gains of the $I_Q-V$ characteristic of a DFIG are modified depending on its reactive current capability so that a DFIG with greater reactive current capability may inject more reactive power. The proposed scheme enables the WPP to recover the voltage at the point of common coupling (PCC) to the nominal value within a short time after a disturbance by using the adaptive $I_Q-V$ characteristics of a DFIG. The performance of the proposed scheme was investigated for a 100 MW WPP consisting of 20 units of 5 MW DFIGs for small and larger disturbances. The results show the proposed scheme successfully recovers the PCC voltage within a short time after a disturbance.

Primary Restoration Path Selection Considering Ferranti Effect and Reactive Power Capability of Black-start Generators

  • Park, Ji-Man;Lee, Heung-Jae;Yu, Won-Kun;Jang, Byung-Tae;Lee, Kyeong-Seob
    • Journal of Electrical Engineering and Technology
    • /
    • v.10 no.3
    • /
    • pp.1377-1382
    • /
    • 2015
  • Power system restoration following a massive blackout starts with re-energizing Primary Restorative Transmission (PRT) systems at first. As power systems have been gradually enlarged and become more complex, periodical evaluation and reassignment of PRTs are needed. So far it has been decided by try and error approach by corresponding human experts to analyze and evaluate them. This paper presents an intelligent system that finds optimal primary restoration paths using analytic and heuristic knowledge from PSS/E data, and suggests an optimal PRTs depending on the condition of Ferranti effect or a reactive power capability margin of black-start generator. This system was tested in Korea Electric Power system, and showed a promising result.

Transfer Capability Enhancement Using Voltage Source Converter HVDC (전압원 HVDC를 이용한 부하집중지로의 송전용량 증대방안)

  • Oh, Sea-Seung;Jang, Gil-Soo;Cha, Jun-Min
    • Proceedings of the KIEE Conference
    • /
    • 2005.11b
    • /
    • pp.328-330
    • /
    • 2005
  • This paper presents a transfer capability enhancement of using VSC HVDC system which can control reactive power as well as active power. The transfer capability is constrained by stability like voltage stability. These constraints may relieved by reactive power control ability of the VSC HVDC system. Site selection algorithm is also proposed.

  • PDF

An Analytical Solution for Voltage Stability Studies Incorporating Wind Power

  • Lin, Yu-Zhang;Shi, Li-Bao;Yao, Liang-Zhong;Ni, Yi-Xin;Qin, Shi-Yao;Wang, Rui-Ming;Zhang, Jin-Ping
    • Journal of Electrical Engineering and Technology
    • /
    • v.10 no.3
    • /
    • pp.865-876
    • /
    • 2015
  • Voltage stability is one of the most critical security issues which has not yet been well resolved to date. In this paper, an analytical method called PQ plane analysis with consideration of the reactive power capability of wind turbine generator and the wake effect of wind farm is proposed for voltage stability study. Two voltage stability indices based on the proposed PQ plane analysis method incorporating the uncertainties of load-increasing direction and wind generation are designed and implemented. Cases studies are conducted to investigate the impacts of wind power incorporation with different control modes. Simulation results demonstrate that the constant voltage control based on reactive power capability significantly enhances voltage stability in comparison of the conventional constant power factor control. Some meaningful conclusions are obtained.

Coordinated Control of Reactive Power between STATCOMs and Wind Farms for PCC Voltage Regulation

  • Nguyen, Thanh Hai;Lee, Dong-Choon;Van, Tan Luong;Kang, Jong-Ho
    • Journal of Power Electronics
    • /
    • v.13 no.5
    • /
    • pp.909-918
    • /
    • 2013
  • This paper proposes a coordinated control of the reactive power between the STATCOMs (static synchronous compensators) and the grid-side converters (GSC) of wind farms equipped with PMSGs (permanent-magnet synchronous generators), by which the voltage fluctuations at the PCC (point of common coupling) are mitigated in the steady state. In addition, the level of voltage sags is reduced during grid faults. To do this, the GSC and the STATCOM supply reactive power to the grid coordinately, where the GSCs are fully utilized to provide the reactive power for the grid prior to the STATCOM operation. For this, the GSC capability of delivering active and reactive power under variable wind speed conditions is analyzed in detail. In addition, the PCC voltage regulation of the power systems integrated with large wind farms are analyzed for short-term and long-term operations. With this coordinated control scheme, the low power capacity of STATCOMs can be used to achieve the low-voltage ride-through (LVRT) capability of the wind farms during grid faults. The effectiveness of the proposed strategy has been verified by PSCAD/EMTDC simulation results.

Reactive Power and Soft-Switching Capability Analysis of Dual-Active-Bridge DC-DC Converters with Dual-Phase-Shift Control

  • Wen, Huiqing;Su, Bin
    • Journal of Power Electronics
    • /
    • v.15 no.1
    • /
    • pp.18-30
    • /
    • 2015
  • This paper focuses on a systematical and in-depth analysis of the reactive power and soft-switching regions of Dual Active Bridge (DAB) converters with dual-phase-shift (DPS) control to achieve high efficiency in a wide operating range. The key features of the DPS operating modes are characterized and verified by analytical calculation and experimental tests. The mathematical expressions of the reactive power are derived and the reductions of the reactive power are illustrated with respect to a wide range of output power and voltage conversion ratios. The ZVS soft-switching boundary of the DPS is presented and one more leg with ZVS capability is achieved compared with the CPS control. With the selection of the optimal operating mode, the optimal phase-shift pair is determined by performance indices, which include the minimum peak or rms inductor current. All of the theoretical analysis and optimizations are verified by experimental tests. The experimental results with the DPS demonstrate the efficiency improvement for different load conditions and voltage conversion ratios.