• Title/Summary/Keyword: Puffer-type circuit breaker

Search Result 20, Processing Time 0.023 seconds

Analysis of the Cold Gas Flow in Puffer Type Circuit Breaker (Puffer식 차단기 내의 냉가스 유동 해석)

  • Kim, Hong-Gyu;Sin, Seung-Rok;Jeong, Hyeon-Gyo;Kim, Du-Seong;Gwon, Gi-Yeong
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.49 no.4
    • /
    • pp.233-239
    • /
    • 2000
  • There are many difficult problems in analyzing the gas flow in puffer type circuit breaker such as complex geometry, moving boundary, shock wave and so on. To predict the interruption performance accurately, these should be considered in the simulation. In this paper, the analysis procedure of the cold gas flow in the circuit breaker is presented. Euler equation is solved by FVFLIC method which is an explicit time difference scheme for an unsteady flow computation. Moving boundaries are treated with a cell elimination-addition technique. The pressure and density in front of piston are calculated from the rate of the cell volume change. The presented method is applied to the real circuit breaker model and the pressure in front of the piston is good agreement with the experimental one.

  • PDF

Thermal Flow Characteristics Driven by Arc Plasmas in a Thermal Puffer Type GCB (열파퍼식 가스차단기에서 발생하는 아크 플라즈마에 의한 열유동 특성)

  • Lee, Jong-Chul;Kim, Youn J.
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.54 no.11
    • /
    • pp.527-532
    • /
    • 2005
  • During the last ten years the new interruption techniques, which use the arc energy itself to increase the pressure inside a chamber by the PTFE nozzle ablation, have displaced the puffer circuit breakers due to reduced driving forces and better maintainability. In this paper, we have investigated the thermal flow characteristics inside a thermal puffer type gas circuit breaker by solving the Wavier-Stokes equations coupled with Maxwell's equations for considering all instabilities effects such as turbulence and Lorentz forces by transient arc plasmas. These relative inexpensive computer simulations might help the engineer research and design the new interrupter in order to downscale and uprating the GIS integral.

Estimation of Interruption Capability of a Serial-Hybrid Type Model Gas Circuit Breaker (직렬-복합소호형 모델 가스차단기의 차단성능평가)

  • 송기동;정진교;박경엽
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.53 no.9
    • /
    • pp.538-544
    • /
    • 2004
  • This paper presents the interruption capability of serial-hybrid type GCB (gas circuit breaker) compared with that of puffer type. First a puffer type model interrupter which has the stroke length of 80 mm has been designed and manufactured. And also, a serial-hybrid type interrupter which has the same design parameters as the puffer type interrupter except the serially arranged thermal-expansion chamber and puffer cylinder has been fabricated. Using a simplified synthetic test facility, the critical interruption capabilities of the two GCBs have been estimated. The critical di/dt, the critical dV/dt of ITRV (initial transient recovery voltage) and the minimum arcing time of the puffer type model GCB were 10.7 A/${\mu}\textrm{s}$, 5.5 kV/${\mu}\textrm{s}$, and 15.0 ms respectively. In the case of serial-hybrid type model GCB, each of the values was 16.6A/${\mu}\textrm{s}$, 11.5 kV/${\mu}\textrm{s}$ and 13.0 ms. As a conclusion of this work, it has been quantitatively confirmed that the hybrid type interrupter can obtain the sufficient interruption capability at the operating force which is so low that puffer type interrupter has not the interruption capability.

Cold Flow Simulation of $SF_{6}$ Puffer Circuit Breaker

  • Bae, Chae-Yoon;Jung, Hyun-Kyo;Shin, Sang-In;Park, Oh-Hyun
    • KIEE International Transaction on Electrical Machinery and Energy Conversion Systems
    • /
    • v.11B no.4
    • /
    • pp.121-128
    • /
    • 2001
  • Numerical schemes for the simulation of the cold gas flow in the SF6 puffer type circuit breaker is presented. The governing equation is axisymmetric compressible Euler Equation and FVM is used to analyze the behavior of flow. The upwind scheme is used to avoid numerical instability and MUSCL is used to obtain high order accuracy. For the efficient calculation, AF-ADI scheme is used. The simulation result shows good agreement with the experimental data.

  • PDF

Analysis of Hot Gas Flew Considering Arc-Flow Interaction (아크플라즈마와 유동간의 상호작용을 고려한 열가스 유동 해석)

  • Kim, Hong-Gyu;Park, Gyeong-Yeop;Bae, Chae-Yun;Jo, Gyeong-Yeon;Jeong, Hyeon-Gyo
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.51 no.3
    • /
    • pp.107-115
    • /
    • 2002
  • This parer presents the analysis of hot gas flow in puffer-type circuit breakers using FVFLIC method. For the analysis of arc-flow interaction, the flow field is analyzed from the equations of conservation for mass, momentum and energy with the assumption of local thermodynamic equilibrium state. The arc is represented as the energy source term composed of ohmic heating and radiation term in the energy conservation equation. Ohmic heating is computed by the electric field analysis only within the conducting plasma region. An approximate radiation transport model is employed for the evaluation of emission and absorption of the radiation. The analysis method was applied to the real circuit breaker model and simulation results such as pressure rise and arc voltage were compared with the experimental ones.

Interruption Capability of Hybrid Type GCB with High Opening Speed (고속도 개극 시의 복합소호 가스차단기의 차단특성)

  • Song Ki-Dong;Chong Jin-Kyo;Park Kyong-Yop
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.54 no.9
    • /
    • pp.408-413
    • /
    • 2005
  • This paper presents the basic design technology on the hybrid type GCB(gas circuit breakers) through the test results. The three type hybrid interrupters according to the arrangement of the thermal expansion chamber and the puffer cylinder(they are called 'serial type', ' parallel/exchanged type ,' and ' parallel/separated type ' respectively in this work) were designed and manufactured and then the tests of operating characteristics and interrupting were performed using a simplified synthetic test facility. The interruption capability with the type and the opening speed and the pressure rise which is required to interrupt were examined. The change of pressure rise with the number of interruption was given quantitatively and therefore the pressure rise can be predicted. Finally, it was shown that the interruption capability tends to increase with the increasing of opening speed in the puffer type; however, the hybrid type interrupter has a different interruption characteristic.

Analysis on Dynamic Characteristics of Air-Pressure Type Chamber in Puffer Circuit Breaker (공압식 조작기의 동작특성에 관한 해석)

  • Park, Sang-Hun;Bae, Chae-Yoon;Jung, Hyun-Kyo
    • Proceedings of the KIEE Conference
    • /
    • 2002.04a
    • /
    • pp.18-20
    • /
    • 2002
  • In this paper, various forces generated in the Gas Circuit Breaker(GCB) such as operating force, repulsive force, spring force, and dashpot force are analyzed with the fluid properties and the mechanical structure. The operation of GCB can be understood. A stroke curve from the result of simulation is compared with experimental one.

  • PDF

A Study on Optimization of the Weil-Dobkes Synthetic Short-Circuit Tests (Weil-Dobke 합성단락시험로의 최적화 연구)

  • 김맹현;고희석
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.50 no.6
    • /
    • pp.287-292
    • /
    • 2001
  • This paper deals with the configuration, operating principles, systematic calculation method of parameter and optimization method of test circuit for parallel current injection method, series voltage injection method and hybrid synthetic test method as the method for performance test of circuit breaker with extra high interrupting capacity. The test method depicted above is applied to short-circuit making and breaking test (operating sequence :Os CdOs, Od-CdOs) and out-of-phase tests(operating sequence :Os, CdOs) for performance test of the newly-developed 420kV, 50kA and 800kV 50kV puffer-type gas circuit-breaker according to IEC 60056 and IEC 60427. The testing results, evaluation of equivalence for test and analyzed results are also presented in this paper.

  • PDF

A Research on Dielectric Characteristics of Small Current Interruption Considering Pre-Condition Test for Puffer Type Circuit Breaker (Pre-Condition 시험을 고려한 Puffer식 차단기의 진상소전류 차단성능에 관한 연구)

  • Ahn, Heui-Sub;Yoon, Jeong-Hoon;Lee, Jong-Chul;Choi, Jong-Ung;Oh, Il-Sung;Lee, Sung-Ho
    • Proceedings of the KIEE Conference
    • /
    • 2003.10b
    • /
    • pp.12-14
    • /
    • 2003
  • This paper presents the small current interruption capability of $SF_6$ puffer circuit breaker considering pre-condition. Firstly, the change of dielectric strength of the 3 breakers was compared with testing breakers as clean contacts and eroded contacts after 3 shots of 760 according to new IEC 62271-100 standard. Also the dielectric strength curve of each model was calculated through flow and electric field simulations. From these results, we could modify the empirical equation, being used to predict the dielectric strength of small current interruption capability, considering the effects of pre-condition.

  • PDF

Investigation of Small Current Interruption Performance for New Type of Interrupting Chamber in SF$_{6}$ Gas Circuit Breaker (신차단방식 SF$_{6}$ 가스 차단기의 소전류 차단성능 연구)

  • Song, Won-Pyo;Kweon, Ki-Yeoung;Lee, Jae-Sung;Song, Ki-Dong;Kim, Maeng-Hyun;Ko, Hee-Seok
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.54 no.11
    • /
    • pp.519-526
    • /
    • 2005
  • This paper presents computer simulation results for developing new type of SF$_{6}$ Circuit Breaker in terms of cold gas flow after small current interruption. This cold gas flows down a nozzle into the chamber of a circuit breaker. There are many difficult problems in analyzing the gas flow due to complex geometry, moving boundary, shock wave and so on. When predicting the dielectric capability of a gas circuit breaker after interruption, the gas pressure and density distributions due to the cold gas must be considered in addition to the electrical field imposed across the gas. A self-coded computational fluid dynamics (CFD) program is used for the simulation of cold gas flow in order to evaluate the electrical field characteristic across open contacts and transient characteristics of insulations after small current interruption.