• Title/Summary/Keyword: Protection Relay

Search Result 343, Processing Time 0.027 seconds

Considerations Review on Setting of Distance Relay using Technical Standards (기술기준에 의한 거리계전기 정정시 고려사항 검토)

  • Moon, Su-Cheol
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.67 no.9
    • /
    • pp.1141-1145
    • /
    • 2018
  • Generally, in nuclear plants, distance relay (21R) has adapting to protect and to operate main protective of transmission lines and backup protective of main generator. Operation of 21R was required and based on exactly accurate calculation and criteria. But presently method of 21R setting has applied according to protection devices operation guide of KPX, excepting IEEE and ISA standards, which have a difference review directions, consider parameters and devices, also consideration factors were affected to relay operations by uncertain guides. therefore this paper proposed new protection relay setting method and unvague criteria from IEEE 741 and ANSI/ISA 67.04.01, and reviewed a different results through numerical calculation results for methods and criteria including previous and established 21r setting by IEEE, ANSI/ISA Technical standards.

Discrimination Method of Internal and External Fault of Current Differential Relay using Instantaneous Value of Current in Case of Fault with One end CT Saturation (편단 CT 포화 고장 발생시 양단 전류 순시치를 이용한 전류차동계전기의 내·외부 고장위치 판별방안)

  • Lee, Myoung-Hee;Choi, Hae-Sul;Kim, Chul-Hwan
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.61 no.12
    • /
    • pp.1801-1806
    • /
    • 2012
  • This paper presents a simple and practical method which enables to prevent malfunction of protection relay due to differential current caused by one end CT saturation in case of external fault. This method uses difference of magnitude(instantaneous value) between the both end current just before the occurrence of differential current without a separate method to CT staturation detection. One end CT saturation is simulated by current transformer model using type-96 component and the presented method is verified by using EMTP MODELS with respect to internal and external fault with one end CT staturation. The presented method distinguished rightly bewteen external and internal fault with one end CT saturation. This information can be used to prevent malfunction of current differential protection relay in case of external fault. And this method is not affected by sampling rate and has no calculation burden, so it will be applicable to differential current protection relay with ease.

Protection for a Wind Turbine Generator in a Large Wind Farm

  • Zheng, Tai-Ying;Kim, Yeon-Hee;Kang, Yong-Cheol
    • Journal of Electrical Engineering and Technology
    • /
    • v.6 no.4
    • /
    • pp.466-473
    • /
    • 2011
  • This paper proposes a protection algorithm for a wind turbine generator (WTG) in a large wind farm. To minimize the outage section, a protection relay for a WTG should operate instantaneously for an internal fault or a connected feeder fault, whereas the relay should not operate for an internal fault of another WTG connected to the same feeder or an adjacent feeder fault. In addition, the relay should operate with a delay for an inter-tie fault or a grid fault. An internal fault of another WTG connected to the same feeder or an adjacent feeder fault, where the relay should not operate, is determined based on the magnitude of the positive sequence current. To differentiate an internal fault or a connected feeder fault from an inter-tie fault or a grid fault, the phase angle of the negative sequence current is used to distinguish a fault type. The magnitude of the positive sequence current is then used to decide either instantaneous operation or delayed operation. The performance of the proposed algorithm is verified under various fault conditions with EMTP-RV generated data. The results indicate that the algorithm can successfully distinguish instantaneous operation, delayed operation, or non-operation depending on fault positions and types.

Analysis on the Operation Characteristics and Protection Coordination between the Current Ratio Differential Relay for Line Protection and the Trigger-type SFCL in the Power Transmission System (송전급 초전도한류기의 적용에 따른 선로보호용 비율전류차동계전기의 동작특성 및 보호협조 분석)

  • Cho, Yong-Sun;Kim, Jin-Seok;Lim, Sung-Hun;Kim, Jae-Chul
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.62 no.7
    • /
    • pp.925-930
    • /
    • 2013
  • The fault current of the power transmission system is greater than that of the power distribution system. Therefore, the introduction of superconducting fault current limiter (SFCL) is more needed to reduce the increased fault current. The trigger-type SFCL consists of the high-temperature superconducting element (HTSC), the current limiting reactor (CLR) and the circuit breaker (CB). The trigger-type SFCL can be used to supplement the disadvantages of the resistive-type SFCL. The operation characteristics of the current ratio differential relay which is usually applied to the protection device of the power transmission system are expected to be affected under fault conditions and the applicability of the trigger-type SFCL. In this paper, we analyzed the operating characteristics, by the fault conditions, between the current ratio differential relay for line protection and the trigger-type SFCL in the power transmission system through the PSCAD/EMTDC simulation.

A Study on Design of Digital Protective Relay for Transformer Using a DSP (DSP를 이용한 변압기용 디지털 보호계전기 설계에 관한 연구)

  • 서희석;권기백
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.17 no.6
    • /
    • pp.39-46
    • /
    • 2003
  • In this papers, We studied system requirement specification, hardware design and implementation, protective algorithm and software design method to implement digital protective relay which has high trust and high function of protection as well as control and metering for power transformers. Protective relay for transformer is implemented on real time using DSP, which is the specific processor for digital signal processing, as a result, it is completed by the wide improvement of arithmetic capability of protective relay. Reliability is proved testing operating value and operating time, reset value and reset time of an relaying element using protective relay tester made in NF Corporation of Japan.

Investigation into Transformer Protective Relay Setting Rule Considering Error Ratio (오차를 고려한 765kV 변압기 보호 계전 정정룰 고찰)

  • Bae, Y.J.;Lee, S.J.;Choi, M.S.;Kang, S.H.;Kim, S.T.;Choi, J.L.;Jeong, C.H.;Yoo, Y.S.;Cho, B.S.
    • Proceedings of the KIEE Conference
    • /
    • 2002.07a
    • /
    • pp.229-231
    • /
    • 2002
  • The digital current differential relaying scheme is widely used for primary protection of 765(kV) power transformer. The current differential relay pickup the internal fault at the threshold which is set at 30% of rating current. Margin of 30% include current transformer error 5%, relay error 5%, on load tap changer error 7% and margin factor 140% obtained from the field experience. In this paper transformer protection relay and relay setting rule of high voltage power system are discussed. And we verify the correctness of relay setting rule with current differential relay using Matlab simulation.

  • PDF

A Study on Design of IED for Generator Protection Panel (발전기보호반을 위한 IED의 설계에 관한 연구)

  • Park, Chul-Won;Park, Sung-Wan
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.62 no.3
    • /
    • pp.133-138
    • /
    • 2013
  • A large generator is an important role in transferring an electric power to power system. The IEDs of large generator often use microprocessor technology to obtain a digital relay system with a wide range of measuring, protection, control, monitoring, and communication functions. However, all generator protection and control systems in Korea imported from abroad and are being operated. In order to reduce the large expense and improve the reliable operation, development of generator protection and control system by domestic technology is required. This paper deals with the design of the IED of generator protection panel for development of generator protection and control system. The major emphasis of the paper will be on the description of hardware and signal processing test results and measurement accuracy of the prototype IED. By developing of generator IED based on DSP and microprocessor, replacement of the generator protection panel imports are expected to be effective.

Transformer Differential Relay by Using Neural-Fuzzy System

  • Kim, Byung Whan;Masatoshi, Nakamura
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 2001.10a
    • /
    • pp.157.2-157
    • /
    • 2001
  • This paper describes the synergism of Artificial Neural Network and Fuzzy Logic based approach to improve the reliability of transformer differential protection, the conventional transformer differential protection commonly used a harmonic restraint principle to prevent a tripping from inrush current during initial transformer´s energization but such a principle can not performs the best optimization on tripping time. Furthermore, in some cases there may be false operation such as during CT saturation, high DC offset or harmonic containing in the line. Therefore an artificial neural network and fuzzy logic has been proposed to improve reliability of the transformer protection relay. By using EMTP-ATP the power transformer is modeled, all currents flowing ...

  • PDF

A Study on Implementation of Multi-Function Prototype IED H/W for Generator Protection (발전기 보호용 다기능 IED 시제품 H/W 구현에 관한 연구)

  • Kim, Yoon-Sang;An, Tae-Pung;Park, Chul-Won
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.27 no.12
    • /
    • pp.74-80
    • /
    • 2013
  • Generator faults does not happen more often than the transmission and substation facility faults. However, impacts on the power system by generator faults are very large. In order to minimize the impact of generator faults, generator protection and control system with high reliability is required. Most of the generator relay in generator protection and control system of large power plant of Korea is operated by imports from abroad. Accordingly, in order to accumulate source technology and increase the import substitution effect, localization of multi-function generator protection IED is being developed. This paper deals with the implementation of a multi-function prototype IED H/W, which can be command and data exchange through communication for measuring, monitoring, protection and control. And the IED specification, various relay elements, measurement elements, communication functions, module function, and test system for the prototype IED H/W are described.

Derivation of Protection Ratio and its Calculation for Microwave Relay System Based upon Composite Fade Margin and Availability (합성 페이드 마진 및 가용율에 근거한 M/W 중계 시스템의 보호비 유도 및 계산)

  • Suh, Kyoung-Whoan;Lee, Joo-Hwan
    • The Journal of Korean Institute of Electromagnetic Engineering and Science
    • /
    • v.18 no.3 s.118
    • /
    • pp.341-350
    • /
    • 2007
  • In this paper, the derivation of protection ratio is newly proposed for the detailed planning of frequency coordination in microwave relay networks, and computed results for protection ratio of co-channel and adjacent channel are illustrated over the actual system and its frequency. It is shown that the suggested method based upon availability prediction can be expressed in terms of composite fade margin, interference-to-noise ratio(I/N), net filter discrimination, and system parameters. According to results, for 6.7 GHz, 60 km, 64-QAM, and I/N= -6 dB at BER $10^{-6}$, composite fade margin and co-channel protection ratio provide 25.5 and 50.7 dB, respectively. Also, net filter discrimination and adjacent channel protection ratio are obtained as 26.3 and 24.4 dB, respectively, at the first adjacent channel of 40 MHz. The proposed method provides some merits in computing protection ratio for microwave relay networks in view of an easy extension and practical applications considering more detailed and various system parameters.