실증시험용 배전급 초전도 한류기의 특성 평가 및 운전 시험 (Introduction of KEPCO's distribution class SFCL fabricated for verification test)

  • 임성우;박충렬;유승덕;김혜림;현옥배;박권배;심정욱;이경호;오일성
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2009년도 제40회 하계학술대회
    • /
    • pp.294_295
    • /
    • 2009
  • Superconducting fault current limiter (SFCL) is an power device of a novel concept. While SFCLs generate no ohmic loss during the operation carrying normal currents, they can limit fault currents very fast making large impedance by their quench characteristics. In 2006, KEPCO has developed a distribution class hybrid type SFCL by a collaborative research project with LS industrial systems. The SFCL has merits in practical and economical points of view. In the SFCL, the superconductor just plays a role of a fault detector and the current limiting is completed by the other current limiting element made of normal metals throu호 the line commutation. As a result, the required amounts of superconductors can be reduced considerably. Consequently, the hybrid SFCL can be fabricated with small size and cost, maintaining perfect current limiting performance. Currently, KEPCO is carrying out a research project at Gochang power test center for the purpose of the verification test of the 22.9 kV/ 630 A class SFCL for the practical application in real grid. Through the project, a long term operational test and fault current test will be done. In this paper, the back ground of development and installation of the SFCL will be explained and the operation plan of the SFCL for the verification test is also introduced.

  • PDF

초전도 한류기 투입 위치에 따른 TRV 영향 분석 (Analysis of a TRV influence according to application position of a SFCL)

  • 방승현;이상봉;김철환;김재철;현옥배
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 제39회 하계학술대회
    • /
    • pp.91-92
    • /
    • 2008
  • The rating of a circuit breaker depends not only on the interrupting current but also on a transient recovery voltage (TRV). To achieve a successful interruption, the circuit breaker must withstand the TRV. A superconducting fault current limiter (SFCL) is a device that limits the fault current fast and effectively without having high impedance during normal operation of the power system. Therefore, we studied the influence of the TRV according to the application of a resistive type SFCL in distribution system. This paper analyses the influence of the TRV for various application position of the resistive SFCL. The distribution system and the resistive SFCL were modeled by using EMTP-RV (Electromagnetic Transient Program - Restructured Version)

  • PDF

스마트 그리드 배전계통을 위한 직렬 공진형 한류기 적용 방법 및 EMTP-RV 시뮬레이션 연구 (Application Method and EMTP-RV Simulation of Series Resonance Type Fault Current Limiter for Smart Grid based Electrical Power Distribution System)

  • 고윤석;이우철
    • 한국전자통신학회논문지
    • /
    • 제19권2호
    • /
    • pp.361-370
    • /
    • 2024
  • 본 논문에서는 저비용 제작이 가능한 직렬 공진형 한류기를 스마트 그리드 배전 계통에 적용하기 위한 방법을 연구하였다. 먼저, 한류기의 직렬 공진 회로에 주입되는 단락 전류의 고조파 성분들이 과도 응답의 피크 값에 미치는 영향에 대해서 분석하였으며, 퍼센트 임피던스 기반 고장 전류 계산법을 적용하여 정상 상태 응답을 결정하는 방법을 연구하였다. 다음, 시험 배전 선로에 적용하여 채택된 방법의 유효성을 검증하였다. 설계된 한류기를 적용한 시험 배전계통을 EMTP_RV를 이용하여 모델링하였으며 3상 단락 고장 시나리오를 모의하였다. 고장 모의 결과에서 한류기 적용 후 고장 전류의 정상 상태 응답이 설계 목표 값을 정확하게 추종하는 것을 확인하였다. 또한 한류기 적용 전과 후의 고장전류 파형 비교에서 고장 전류가 크게 억제되는 것을 확인함으로써 배전 계통에 대한 직렬 공진형 한류기 적용 효과를 확인할 수 있었다.

스마트 그리드 배전계통에서 인공신경회로망을 이용한 DSP 기반 실시간 고장 판단 방법론 기초 연구 (DSP based Real-Time Fault Determination Methodology using Artificial Neural Network in Smart Grid Distribution System)

  • 김진언;이유림;최정우;노병훈;고윤석
    • 한국전자통신학회논문지
    • /
    • 제18권5호
    • /
    • pp.817-826
    • /
    • 2023
  • 본 논문에서는 스마트 그리드 배전 계통에서 선로상의 고장으로부터 계통을 보호하기 위한 인공 신경 회로망을 기반으로 하는 고장 판단 방법론을 제안하였다. 제안된 방법론에서는 먼저 전류 실효값 크기를 기반으로 일반 고장 여부를 판단하고 다음, 정상 전류로 판단되는 경우 인공 신경 회로망을 기반으로 하는 normal/HIF classifier를 이용하여 고 임피던스 지락 고장 여부를 판단하도록 설계하였다. 반복적인 DSP 모듈 기반 알고리즘 검증 시험들 중에서, 실효 값 크기가 최소 동작전류보다 작은 정상 전류 파형 시험인 경우에 normal/HIF classifier가 전류 파형을 정상상태로 인식하여 부 동작하였으며, 반면에, 저 임피던스 고장의 경우는 고장 상태로 인식하여 정해진 절차에 따라 재폐로 동작을 보임으로써 제안된 방법론의 유효성을 확인할 수 있었다.

이천 변전소 초전도 케이블 보호를 위한 보호협조 방안에 관한 연구 (Protection Coordination to Protect the Superconducting Cable in Icheon Substation)

  • 이한상;서재완;정창호;양병모;장길수
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2011년도 제42회 하계학술대회
    • /
    • pp.501-502
    • /
    • 2011
  • Based on the several advantages of high-temperature superconducting cable, there are many researches about HTS cable. In the aspect of power system engineering, since it has very low impedance, approximately zero, it is profitable for large capacity distribution line into the large scale load. In the step of its verifications, the HTS cable had been installed in Icheon substation and operated. In this paper, the protection coordination for Icheon substation had been designed and verified using PSCAD/EMTDC.

  • PDF

전기품질 모니터링 시스템에서의 사고거리계산 알고리즘 (A Modified Fault Distance Calculation in the Power Quality Monitoring System)

  • 강현구;정일엽;원동준;문승일
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2006년도 제37회 하계학술대회 논문집 A
    • /
    • pp.167-168
    • /
    • 2006
  • This paper proposes a new fault distance calculation method in the power quality (PQ) monitoring system. The proposed method calculates the fault impedance and the fault distance based on the measurement data of the PQ monitors and the information of the topology of the distribution systems. By using the iterative calculation method, the proposed method can find more exact location of the PQ events than the existing methods. The proposed method is applied to the IEEE 34 bus test feeders by using the PSCAD/EMTDC$^{TM}$.

  • PDF

배전용 변압기 %임피던스 운영에 관한 고찰 (The Study on Improvement of %Impedance Management in Distribution Transformers)

  • 나동채;김동명
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 제39회 하계학술대회
    • /
    • pp.410-411
    • /
    • 2008
  • 변압기의 %임피던스는 무부하손, 부하손, 효율, 전압변동율 등과 밀접한 관계가 있으며, %임피던스의 크기에 따라 변압기 2차에서 단락고장이 발생할 경우에 고장전류의 크기가 결정되어 변압기 보호장치 선정의 기준이 된다. 특히 전압변동율과 직접 관계가 있어 저압 배전선로의 규정전압을 유지하기 위해서 1992년부터 주상변압기의 용량별로 일정범위를 규정하여 운영하고 있다. 규정 전압의 관리측면에서는 %임피던스가 가급적 낮게 운영하여야 하나, 고장전류의 증가에 따른 변압기 단락강도의 개선이 수반되어 변압기 제조기술에 제약요인이 있다. 이에 따라 주상변압기의 %임피던스와 전압변동률을 중심으로 현재 운영하고 있는 각종 배전용 변압기의 특성값을 분석하고 이에 대한 개선방안을 모색하였다.

  • PDF

Droop Method를 이용한 50[W]급 태양전지 가상구현장치의 다중병렬연결 출력특성에 관한 연구 (A study of Multiple parallel Characteristics of 50[W] Virtual Implement of 50[W] Solar Cell modules Using Droop-Method)

  • 이병인;이상용;정병환;최규하
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2003년도 추계학술대회 논문집
    • /
    • pp.81-84
    • /
    • 2003
  • For increasing power of photovoltaic systems, serial and parallel connection needed. In parallel connection, a desirable characteristic of parallel-connected supply system is that individual converters share the load current equally and stably. The current sharing(CS) can be implemented using two approaches. The first one, known as a Droop method, and the other is Active current-sharing. In Droop method, current distribution characteristics relies on the high output impedance of each converter. This scheme is more simple and no need interconnections. but also has a disadvantages of degrading current sharing characteristics. In this paper, using droop method at multiful-parallel connection with it's convenience and simplicity.

  • PDF

3차 권선을 고려한 단상 33MVA 고온초전도 변압기의 개념설계 (Conceptual Design of a Single Phase 33 MVA HTS Transformer with a Tertiary Winding)

  • 이승욱;김우석;한송엽;황영인;최경달
    • Progress in Superconductivity
    • /
    • 제7권2호
    • /
    • pp.162-166
    • /
    • 2006
  • We have proposed a 3 phase, 100 MVA, 154 kV class HTS transformer substituting for a 60 MVA conventional transformer. The power transformer of 154 kV class has a tertiary winding besides primary and secondary windings. So the HTS transformer should have the 3rd superconducting winding. In this paper, we designed conceptually the structure of the superconducting windings of a single phase 33 MVA transformer. The electrical characteristics of the HTS transformer such as % impedance and AC loss vary with the arrangement of the windings and gaps between windings. We analyzed the effects of the winding parameters, evaluated the cost of each design, and proposed a suitable HTS transformer model for future power distribution system.

  • PDF

Operational Mode Analysis of Cooler Driver Electronics in Satellite and System Safety Margin

  • Kim, Kyudong
    • 항공우주시스템공학회지
    • /
    • 제14권6호
    • /
    • pp.79-84
    • /
    • 2020
  • Cooler driver electronics (CDE) for maintaining low temperature of the satellite payload IR sensor consists of a compressor that has a pulsation current load condition when it is operated. This pulsation current produces large voltage fluctuation, which affects both load and regulated bus stability. Thus, CDE power conditioning system consists of a primary bus, infrared power distribution unit for battery charging and protection, reverse current protection diode, and battery, which is used as a buffer. In this study, the operational mode analysis is performed by each part with equivalent impedance modeling verified through system level simulation. From this mode analysis, the safety margin for state of charge and open circuit voltage of the battery is determined for satisfying the minimum operational voltage of the CDE load.