• Title/Summary/Keyword: Power Cable Event

Search Result 19, Processing Time 0.026 seconds

A Study on Heat-Flux Evaluation for Cable Fire Including Diagnostic Methodology for Degradation in Nuclear Power Plants (원전 케이블 화재 열속평가 및 열화 진단방법에 관한 연구)

  • Lim, Hyuk-Soon;Kim, Doo-Hyun
    • Journal of the Korean Society of Safety
    • /
    • v.26 no.2
    • /
    • pp.20-25
    • /
    • 2011
  • The fire event occurred in fire proof zone often causes serious electrical problems such as shorts, ground faults, or open circuits in nuclear power plants. These would be directed to the loss of safe shutdown capabilities performed by safety related systems and equipments. The fire event can treat the basic design principle that safety systems should keep their functions with redundancy and independency. In case of a multi-core cable fire, operators can not perform their mission properly and can misjudge the situation because of spurious operation, wrong indication or instrument. These would deteriorate the plant capabilities of safety shutdown and make disastrous conditions. In this paper, the characteristic of cable fire is investigated and the heat-flux evaluation for cable fire is studied. Moreover, a diagnostic methodology for degraded cable in nuclear power plants is presented.

A Study on Cable Functional Failure Temperature by Exposed Fire in Nuclear Power Plants (원전 노출 화재시 케이블 기능상실 온도에 관한 연구)

  • Kim, Doo-Hyun;Lim, Hyuk-Soon
    • Journal of the Korean Society of Safety
    • /
    • v.26 no.5
    • /
    • pp.41-45
    • /
    • 2011
  • The fire event occurred in fire proof zone often causes serious electrical problems such as shorts, ground faults, or open circuits in nuclear power plants. These would be directed to the loss of safe shutdown capabilities performed by safety related systems and equipments The fire event can treat the basic design principle that safety systems should keep their functions with redundancy and independency. In case of a cable fire, operators can not perform their mission properly and can misjudge the situation because of spurious operation, wrong indication or instrument. These would deteriorate the plant capabilities of safety shutdown and make disastrous conditions. In this paper, the cables of the representative nuclear power plant in korea is selected and the cable functional failure temperature by exposed fire using Cable Response to Live Fire(CAROLFIRE) is studied. It is expected that the results are very useful to know the cable failure temperature by exposed fire. We confirmed the safety and integrity of the cable by exposed fire and those results will use the based data of cable exposed fire characteristics.

Numerical study to reproduce a real cable tray fire event in a nuclear power plant

  • Jaiho Lee ;Byeongjun Kim;Yong Hun Jung;Sangkyu Lee;Weon Gyu Shin
    • Nuclear Engineering and Technology
    • /
    • v.55 no.4
    • /
    • pp.1571-1584
    • /
    • 2023
  • In this study, a numerical analysis was performed as part of an international joint research project to reproduce a real cable tray fire that occurred in the heater bay area of the turbine building of a nuclear power plant. A sensitivity analysis was performed on various input parameters to derive results consistent with the sprinkler activation time obtained from the fire event analysis. For all sensitive parameters, the normalized sprinkler activation time correlated well with the power function of the normalized sprinkler height. A correlation equation was developed to identify the sprinkler activation time at any location when determining the slope or fire growth rate under the conditions assuming a linear or t-squared heat release rate (HRR) time curve. Various cable fire growth assumptions were used to determine which assumption was better to provide the prediction coincident with the information given from the fire event analysis in terms of the sprinkler activation time and total energy generated from cables damaged by fire. In the comprehensive analysis of all the sensitive parameters, the standard deviation of the input parameters increased as the sprinkler height decreased. Within the range of the sensitivity parameter values given in this study, when considering all sprinkler heights, the standard deviation of the cable model change was the largest and that of the overhang position change was the smallest.

Human Reliability Assessment for a Installation Task of Temporary Power Cables in Construction Fields (건설현장 임시전력 배선의 가설직무에 대한 인간신뢰성 평가)

  • Kim Doo-Hyun;Lee Jong-Ho;Kim Sang-Chul
    • Journal of the Korean Society of Safety
    • /
    • v.20 no.2 s.70
    • /
    • pp.61-66
    • /
    • 2005
  • This paper presents an human reliability assessment(HRA) for a installation task of the temporary power cable in construction fields. HRA is evolved to ensure that the workers could reliably perform critical tasks such as a process of the temporary power cable. Human errors are extremely commonplace, with almost everyone committing at least some errors every day. The considerable parts of electric shock accidents in the construction field are caused by a series of human errors. Therefore it is required to analyze the human errors contained in the task causing electric shock event, the event tree analysis(ETA) is adopted in this paper, and particularly human reliability was estimated for a installation task of the temporary power cables. It was assumed that the error probabilities of the human actions may be obtained using the technique for human error rate prediction(THERP). The results show that the predominant task on reliability in the cable installation tasks is check-out tasks and the probability causing electric shock by human errors was calculated as $1.0\times10^{-9}$.

Cable Functional Failure Temperature Evaluation of Cable Exposed to the Fire of Nuclear Power Plant (원자력발전소 케이블 노출 화재 시 기능상실온도 분석)

  • Lim, Hyuk-Soon;Bae, Yeon-Kyoung;Chi, Moon-Goo
    • Fire Science and Engineering
    • /
    • v.26 no.1
    • /
    • pp.10-15
    • /
    • 2012
  • The fire event occurred in fire proof zone often causes serious electrical problems such as shorts, ground faults, or open circuits in nuclear power plants. These would be directed to the loss of safe shutdown capabilities performed by safety related systems and equipments. The fire event can treat the basic design principle that safety systems should keep their functions with redundancy and independency. In case of a cable fire, operators can not perform their mission properly and can misjudge the situation because of spurious operation, wrong indication or instrument. These would deteriorate the plant capabilities of safety shutdown and make disastrous conditions. In this paper, investigation and cause analysis of cable fire in Nuclear Power Plant, we described the cable fire temperature and functional failure criteria and the cable functional failure temperature evaluation by exposed fire is studied.

Risk Analysis of Electrical Fire for Electric Power Installations by Event Tree Analysis (사건수목분석을 통한 수배전설비의 전기화재위험성 분석)

  • Park, Young Ho;Kim, Doo-Hyun;Kim, Sung-Chul
    • Journal of the Korean Society of Safety
    • /
    • v.31 no.5
    • /
    • pp.16-21
    • /
    • 2016
  • The purpose of this paper is to conduct ETA on 15 components of power installations: the DS/LBS, LA, MOF, CT, PT, A/V meter, VCB, OCR, COS, PF, Transformer, Condenser(C), Grounding, Cable and Connector. To achieve that, power installations work flow and its components are categorized. Based on performance, human, environmental, management, and safety, this paper drew Initiation events (IE) and End states (ES). ETA is applied to the main functions of each component, and the end states that may occur in one initiation event are suggested. In addition, detailed classification was performed to induce various end states on the basis of the suggested initiation events. If the suggested IEs and ESs are applied on the basis of power installations event cases, it is expected to prevent the same kinds of accident and operate power installations safely.

The Properties of Dielectric Breakdown and Thermal Stresses below 22.9[kV] Class XLPE Power Cable (22.9[kV]이하 XLPE 전력케이블의 열 충격 시험 및 절연파괴 특성)

  • Kim, Young-Seok;Shong, Kil-Mok;Kim, Sun-Gu
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.22 no.4
    • /
    • pp.54-60
    • /
    • 2008
  • It is impossible to database(DB) the patterns of power cable events and cause analysis of faulted cable because the product liability(PL) law have been enforced in Korea, since 2002. In additions, simulation and pattern of power cable events are needed for DB system under accelerated deterioration. In this paper, we tested for resistance to cracking of cable below the 22.9[kV] class due to thermal stresses. This method of exam is following IEC 60811-3-1(Common test methods for insulating and sheathing materials of electric cables). From the results, The 22.9[kV] class A power cable was discolored on the surface and significantly reduced in the longitudinal direction. As the thermal weight properties of A power cable was definitely varied, we are able to guess the problem of manufacture. If the cable was defect by the manufacture, the victims would be able to claim for damage in the PL system.

Experimental Study on the Dynamic Characteristics of Porcelain Surge Arrestor Considering the Variation of Cable's Tension and Arrestor's Stiffness (케이블 장력 및 피뢰기의 강성 변화를 고려한 애자형 피뢰기의 동특성 시험 연구)

  • Jang, Jung Bum;Hwang, Kyeong Min;Yun, Kwan Hee
    • Journal of the Earthquake Engineering Society of Korea
    • /
    • v.18 no.5
    • /
    • pp.253-259
    • /
    • 2014
  • Porcelain surge arrestor is very vulnerable to earthquake but there is very few information on its dynamic characteristics which are necessary to the seismic design. Therefore, the dynamic characteristics of the porcelain surge arrestor are evaluated considering the variation of its cable tension and stiffness by shaking table test. The test results show that the first natural frequencies are 5.3 Hz and 5.2 Hz in the horizontal x- and y-axis directions, respectively, and higher than 30 Hz in the vertical z-axis direction, respectively. The installation of cable on the surge arrestor reduces the horizontal natural frequencies due to the constraint effect of the cable but cable tension has no effect on the natural frequency. Also, the natural frequency is proportional to the stiffness of the surge arrestor. This test result will be used for the seismic design and seismic capacity assessment of domestic substations and contribute to the stability of the electric power supply under earthquake event.

Cable Functional Failure Time Evaluation for a Main Control Room Fire using Fire Dynamic Simulator (FDS 이용한 주제어실 화재시 케이블 기능상실시간 평가)

  • Lim, Heok-Soon;Kim, In-Hwan;Kim, Myung-Su
    • Fire Science and Engineering
    • /
    • v.30 no.3
    • /
    • pp.79-85
    • /
    • 2016
  • Serious electrical problems, such as shorts, ground faults, or circuits, often cause fire events in the fire proof zone of nuclear power plants. These would be directed to the loss of safe shutdown capabilities performed by safety-related systems and equipment. The fire event can be treated with the basic design principle that safety systems should maintain their functions with redundancy and independency. In the case of a cable fire in the main control room, operators cannot perform their mission properly and can misjudge the situation because of spurious operation, incorrect indication or instrument. These would deteriorate the plant capabilities of safety shutdown and result in disastrous conditions. Therefore, during a main control room fire, 5 minutes of operator action time is very important to operate the safety shutdown components. This paper describes the cable functional failure temperature criteria and conducted a cable functional failure time evaluation using Fire Dynamic Simulator to obtain the operator action time for a main control room fire.

Analysis of PD Distribution Characteristics and Comparison of Classification Methods according to Electrical Tree Source in Power Cable (전력용 케이블 시편에서 전기트리 발생원에 따른 부분방전 분포 특성 및 발생원 분류기법 비교)

  • Park, Seong-Hee;Jeong, Hae-Eun;Lim, Kee-Joe;Kang, Seong-Hwa
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.20 no.1
    • /
    • pp.57-64
    • /
    • 2007
  • One of the cause of insulation failure in power cable is well known by electrical treeing discharge. This is occurred for imposed continuous stress at cable. And this event is related to safety, reliability and maintenance. In this paper, throughout analysis of partial discharge(PD) distribution when occurring the electrical tree, is studied for the purpose of knowing of electrical treeing discharge characteristics according to defects. Own characteristic of tree will be differently processed in each defect and this reason is the first purpose of this paper. To acquire PD data, three defective tree models were made. And their own data is shown by the phase-resolved partial discharge method (PRPD). As a result of PRPD, tree discharge sources have their own characteristics. And if other defects (void, metal particle) exist internal power cable then their characteristics are shown very different. This result Is related to the time of breakdown and this is importance of cable diagnosis. And classification method of PD sources was studied in this paper. It needs select the most useful method to apply PD data classification one of the proposed method. To meet the requirement, we select methods of different type. That is, neural network(NN-BP), adaptive neuro-fuzzy inference system and PCA-LDA were applied to result. As a result of, ANFIS shows the highest rate which value is 98 %. Generally, PCA-LDA and ANFIS are better than BP. Finally, we performed classification of tree progress using ANFIS and that result is 92 %.