Development of an Inert Gas Water Mist System -A Numerical Study on Ventilation of the Fire Test Room- (불활성가스 미분무소화설비의 개발 -화재시험실의 급기에 관한 수치연구-)

  • Park, Woe-Chul;Jeong, Lee-Gyu
    • Journal of the Korean Institute of Gas
    • /
    • v.12 no.1
    • /
    • pp.25-30
    • /
    • 2008
  • A Numerical study was carried out for a propane gas pool fire in the fire test room of $2.5m{\times}2.0m{\times}2.5m$ for testing a inert gas water mist system, to investigate a possible under-ventilation in the fire test room. For the fire sizes of 60 kW and 120 kW, changes in the temperature and CO concentration with and without a window were investigated. It was confirmed that the influence of the window on the distributions of temperature and CO concentration was small in the two fire sizes, and hence the under-ventilation was not occurred in the room.

  • PDF

Characteristics of Smoke Propagation in Railway Tunnels with Rescue Station (구난역을 갖는 철도 터널 내부의 연기거동 특성)

  • Jang, Won-Cheol;Kim, Dong-Woon;Lee, Seong-Hyuk;Ryou, Hong-Sun
    • Fire Science and Engineering
    • /
    • v.23 no.4
    • /
    • pp.13-18
    • /
    • 2009
  • The main objective of the present study is to investigate smoke propagation in railway tunnels with rescue stations. In particular, based on measurement of HRR (heat release rate) for pool fires formed at different locations, the influence of fire source location on smoke behavior is examined. The fuel is n-heptane and pool fires are generated with a square length 4cm. With the use of MVHS (Modified Volumetric Heat Source) model for fire source, extensive numerical simulations are performed by using the commercial code FLUENT (Ver.6.3) Predicted smoke temperatures and smoke propagation are discussed. From numerical predictions, it is found that ventilation systems may be necessary in the railway tunnels because the smoke moves along the tunnel, and consequently it enters the non-accident tunnel. It is also confirmed that the cross-passage and fire protection wall systems contribute to control the smoke.

An Experimental Study of Smoke Movement in Tunnel Fires with Aspect Ratio of Tunnel Cross Section (터널 화재시 터널 단면의 종횡비에 따른 연기 거동에 관한)

  • Lee, Sung-Ryong;Ryou, Hong-Sun;Kime, Choong-Ik
    • Proceedings of the KSME Conference
    • /
    • 2003.11a
    • /
    • pp.115-120
    • /
    • 2003
  • In this study, smoke movement in tunnel fires was investigated with various aspect ratio(0.5, 0.667, 1.0, 1.5, 2.0) of tunnel cross section. Reduced-scale experiments were carried out under the Froude scaling using 8.27 kW ethanol pool fire. Temperatures were measured under the ceiling and vertical direction along the center of the tunnel. Smoke front velocity and temperature decrease rate were reduced as higher aspect ratio of the tunnel cross-section. Smoke movement was evaluated by analysis of vertical temperature distribution 3 m downstream from the fire source. Elevation of smoke interface according to N percent rule was under about 60% of tunnel height.

  • PDF

Smoke Characteristics of a Small Scale Pool Eire (작은 풀화재에서의 연기 특성)

  • Lee Eui-Ju;Ahn Chan-Sol;Shin Hyun-Joon;Oh Kwang-Chul;Lee Uen-Do
    • Fire Science and Engineering
    • /
    • v.19 no.3 s.59
    • /
    • pp.58-63
    • /
    • 2005
  • Experimental measurements of flames and the product properties were performed for small kerosene pool fires. which is widely used as a fire source of laboratory scale experiments with scaling modeling. The flame length and flickering frequency were investigated for the flame structures, and compared with the theory. Three measurement methods were introduced to clarify the smoke characteristics, i.e. various gas concentrations, smoke density and thermophoretic sampling with transmission electron microscopy (TEM). The yield of carbon dioxide and the consumption of oxygen were proportional to the heat release rate of pool fires, but there is no trend on carbon monoxide emission. Smoke density of turbulent flames was exponentially increased with the heat release rate. The morphology of the soot particle was investigated to address the degree of soot maturing. The results show that the similar smoke morphology between an inverse jet flame and a pool fire exists despite of different combustion controlling mechanisms.

Measurements of Flame Temperature and Radiation Heat Flux from Pool Fire with Petroleum Diesel Fuel (디젤연료의 액면화재로부터 화염온도와 복사열 측정)

  • Lim, Woo-Sub;Choi, Jae-Wook
    • Fire Science and Engineering
    • /
    • v.21 no.3
    • /
    • pp.78-83
    • /
    • 2007
  • Diesel, a kind of petroleum, which is used in vehicles, vessels, boilers etc causes great damage when a fire happens, because it has higher caloric value than gasoline or kerosene has at burning. Therefore, pool fire experiment was carried using diesel which is sold on the gas station and radiation heat flux that occurs from flame and inner temperature of flame at burning was estimated. The maximum instantaneous flame temperature of diesel was more than $900^{\circ}C$, and the average of maximum flame temperature was $800^{\circ}C$ which occurred at 0.5 H/D distance from the surface of inflammable liquid, the distance has more long that has the lower the temperature of flame. In case of radiation heat flux, it grew to vary according to the size and amount of sample. When the size of a container for experiment was 0.5 m and sample layer was 13 mm and 20 mm, the radiant heat was 92.29 kW and 117.43 kW each. When the container was 1.0 m, it was 364.35 kW and 405.88 kW each.

Flow and Heat Transfer along Burner Positions in Aluminium Pool Furnace (버너의 위치에 따른 알루미늄 용해로내의 유동 및 열전달)

  • Kim, Jin-Ho;Kang, Deok-Hong;Kim, Ki-Hong
    • Proceedings of the KSME Conference
    • /
    • 2004.04a
    • /
    • pp.1207-1212
    • /
    • 2004
  • For the design of Aluminium pool furnace, position of burner and pool depth effects on flow and temperature field in Aluminium pool furnace are examined by the commercial computational code, CFD-ACE+. From the results, position of burner which is on the same face in side wall is better to distribute the flow field in Al furnace. That yields temperature to distribute more uniformly. And the burner position is on upper wall, fire frame reach pool surface. Customer must consider that, because it make Aluminium to oxidize.

  • PDF

Application Study of Design Fire Curves for Liquid Pool Fires in a Compartment (구획실 내 액체 풀화재에 대한 디자인 화재곡선 적용 연구)

  • Baek, Bitna;Oh, Chang Bo;Lee, Eui Ju;Nam, Dong-Gun
    • Fire Science and Engineering
    • /
    • v.31 no.4
    • /
    • pp.43-51
    • /
    • 2017
  • In this study, new design fire curves were suggested for the utilization in fire simulations. Numerical simulations with the Fire Dynamics Simulator (FDS) were performed for the n-octane and n-heptane pool fires in the ISO 9705 compartment to evaluate the prediction performance of the previous quadratic, exponential design fire curves and newly suggested ones. The numerical results were compared with the experimental temperature and concentrations of $O_2$ and $CO_2$. The numerical results with the previous quadratic and exponential curves showed slow increase and decrease trend than experiments. However, the numerical results with the newly suggested 2 design fire curves showed more similar variation trend in temperature, $O_2$ and $CO_2$ concentrations than the quadratic and exponential curves. It was found that the newly suggested design fire curves can be possibly used in the numerical simulation of fires in a practical respect.

Extinguishing Charactristics of Water Mist by Discharge Properties (방사특성 변화에 따른 미세물분무의 소화특성)

  • 이경덕;신창섭
    • Fire Science and Engineering
    • /
    • v.15 no.4
    • /
    • pp.41-48
    • /
    • 2001
  • Halogen-based fire suppressing agents have been the most effective fire suppressants and widely used for flammable liquid and electric fire. However they have environmental problems causing stratospheric ozone depletion and globe warming. As a substitution of halon, fire suppression system using fine water mist is one of an effective fire suppressant. Suffocating and cooling effects of water mist are increased by the evaporation characteristics because it has droplet size less than 1,000 $\mu{m}$ and very large surface area. In this study, the extinguishing characteristics of fire was measured with changing of water mist droplet size, flow density; discharge pressure, and fire size. As a result, the extinguishing time of pool fire was shortened with the increase of flow density and in case of low flow density less than 0.5$\pm$0.05 ml/$\textrm{cm}^2$ . min, the extinguishing time was shortened with the increase of droplet size. The cycling discharge was effective for $\eta$-heptane pool fire, and total amount of water mist required to extinguish fire was reduced to a quarter compare with continuous discharge.

  • PDF

Effects of the Geometry and Location of an Vertical Opening on the Fire Characteristics in the Under-Ventilated Compartment Fire (환기부족 구획화재에서 수직 개구부의 형상 및 위치가 화재특성에 미치는 영향)

  • Mun, Sun-Yeo;Park, Chung-Hwa;Hwang, Cheol-Hong;Park, Seul-Hyun
    • Fire Science and Engineering
    • /
    • v.27 no.3
    • /
    • pp.20-29
    • /
    • 2013
  • To investigate numerically the effects of geometry and location of vertical opening on the thermal and chemical fire characteristics in full-scale under-ventilated compartment fires, the ventilation factor ($A\sqrt{h}$) to estimate a theoretical maximum inflow of ambient air and the mass loss rate in a heptane pool fire were fixed for all cases. It was shown that variations in door geometry affected significantly the change in thermal and chemical characteristics inside the compartment. Variations in window location resulted in the complex change in additional fire characteristics including the fire duration time and recirculating flow structure. These results were analyzed in details by the multi-dimensional flow and fire characteristics including the vent flow and fuel/air mixing phenomena.