Development of an Inert Gas Water Mist System -A Numerical Study on Ventilation of the Fire Test Room-

불활성가스 미분무소화설비의 개발 -화재시험실의 급기에 관한 수치연구-

  • Park, Woe-Chul (Division of Safety Engineering, Pukyong National University) ;
  • Jeong, Lee-Gyu (Korea Institute of Maritime and Fisheries Technology)
  • Published : 2008.03.30

Abstract

A Numerical study was carried out for a propane gas pool fire in the fire test room of $2.5m{\times}2.0m{\times}2.5m$ for testing a inert gas water mist system, to investigate a possible under-ventilation in the fire test room. For the fire sizes of 60 kW and 120 kW, changes in the temperature and CO concentration with and without a window were investigated. It was confirmed that the influence of the window on the distributions of temperature and CO concentration was small in the two fire sizes, and hence the under-ventilation was not occurred in the room.

불활성가스 미분무소화설비의 실험용으로 제작된 $2.5m{\times}2.0m{\times}2.5m$ 크기의 화재시험실에 급기부족 여부를 확인하기 위해, 화재시험실 내 프로판가스 풀(pool) 화재에 대한 수치연구를 수행하였다. 결과의 일관성을 확인하기 위해 설계 화재규모인 60 kW와 그 2배인 120 kW에 대하여 창문의 개폐에 따른 온도 및 일산화탄소 농도의 변화를 조사하였다. 두 화재규모에서 모두 창문의 개폐가 온도 및 CO농도의 변화에 미치는 영향이 작음을 확인하였고, 따라서 급기부족의 발생이 없음을 알 수 있었다.