• Title/Summary/Keyword: Plenum

Search Result 189, Processing Time 0.026 seconds

Study of the RBTRAN Code for Upper Plenum Analysis in Very Small LOCA (매우 작은 규모의 LOCA에 있어서 Upper Plenum분석을 위한 RETRAN코드의 연구)

  • Hee Cheon No
    • Nuclear Engineering and Technology
    • /
    • v.16 no.3
    • /
    • pp.125-130
    • /
    • 1984
  • In the application of the RETRAN code to the analysis of very small LOCA one of main concerns is placed on use of the bubble rise model in the upper plenum, because the bubble rise model nay cause a numerical divergence problem and coefficients used to describe it are based on experimental results of large LOCA. In order to solve this problem, a method, which enables us to predict the mixture level in the upper plenum without use of the bubble rise model, was proposed. For this method the local void distribution in the core and upper plenum was derived by using a simplified slip model. It was shown that results predicted from the derived equation are in excellent agreement with experimental data. Additionally it was found that local void in the upper plenum has a uniform distribution unlike a linear distribution in large LOCA. Communication between the upper plenum and upper head was investigated. By introducing the concept of Taylor instability, it was proved that counter-current Hon between them is possible.

  • PDF

Control Methods of the VAV Air Handling Unit for the Required Outdoor Air Demand (변풍량 공조시스템의 요구외기량 확보를 위한 제어방식)

  • Han, Do-Young;Joo, Young-Duk;Kim, Jin;Lee, Jun-Ho
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.15 no.3
    • /
    • pp.203-209
    • /
    • 2003
  • Control algorithms of an air handling unit by using the mixing box plenum pressures were developed and verified by experiments. Control algorithms developed for this study were the setpoint algorithms for the outdoor damper position, the outdoor/fixed plenum pressure, and the return/exhaust plenum pressure. The outdoor/fixed plenum pressure setpoint was used to control the bypass damper position, and the return/exhaust plenum pressure setpoint was used to control the return fan speed. Experimental results showed the good control of the required outdoor air demand. Therefore, setpoint algorithms developed for this study may effectively be applied for the control of the VAV air handling unit.

An Experimental Study on the Flow characteristics in the Plenum Chamber (플레넘 챔버 내의 유동 특성에 관한 실험적 연구)

  • 정재우;이기형;이창식
    • Transactions of the Korean Society of Automotive Engineers
    • /
    • v.7 no.7
    • /
    • pp.24-31
    • /
    • 1999
  • The MPI engine becomes increasingly popular because it meets two requirements of stringent pollutant emission and the lower fuel consumption. Even though supplies the same amount of fuel to each cylinder , it is hard to precisely control the air-duel ration due to the different amount of air flowing into each cylinder. The uniformity of air-fuel ration in each cylinder is considerably affected by the plenum chamber configuration . This study is focused on experimentally analyzing the flow characteristics within the plenum chamber In the present experiment , steady and valve dynamic state flow tests are performed and the flow field inside the plenum chamber is visualized and measured by utilizing a laser sheet visualization technique and a PTV method. These measured results indicate that the flow structure in the plenum chamber is highly influenced by the plenum chamber configurations, suction flow rates, crank speeds and so on.

  • PDF

Airflow Characteristic Experiments for the Upper Plenum Design of Clean Room (클린룸의 상부 플레넘 설계를 위한 유동특성 실험)

  • Oh, M.D.;Bae, G.N.;Kim, S.C.;Lee, C.S.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.1 no.4
    • /
    • pp.276-289
    • /
    • 1989
  • The airflow characteristics in both the upper plenum and the clean space of clean room are investigated by measuring the pressure distribution of the upper plenum and the velocity profile in the clean space, at the various conditions of the supplied airflow rate, the volume of upper plenum and the air supply type. The performance of vertical air supply type and horizontal air supply type is analyzed in terms of the airflow uniformity which is frequently used in indicating the clean room performance, and the relations among the volume of upper plenum, the supplied airflow rate and the airflow uniformity are confirmed. The results of this experimental study can be applied to the designing of the upper plenum of clean room.

  • PDF

NUMERICAL INVESTIGATIONS OF SUPERSONIC JET IMPINGEMENT ON A FLAT WALL IN A CONFINED PLENUM (화염배출 출구면적 변화에 대한 수직발사관 내부 초음속 충돌유동의 수치적 해석)

  • Lee K. S.;Hong S. K.;Ahan C. S.
    • 한국전산유체공학회:학술대회논문집
    • /
    • 2005.10a
    • /
    • pp.281-285
    • /
    • 2005
  • Viscous solutions of supersonic jet impinging on a flat wall in a confined plenum are simulated using three-dimensional Navier-Stokes solver. A confined plenum was designed for simulating the missile launch and analyzing the behavior of the exhaust plume, which were accompanied by complex flow interactions with shock and boundary layer. Concerns of this paper are to show accurate simulation of internal flow in confined plenum and to demonstrate the jet flow structure when the jet interacts with a small opening on the side. Objectives of this numerical simulation are to understand the effect of changing the plume exit area of the plenum. Pressure and temperature rise at certain position in the plenum are traced and compared with test data.

  • PDF

Prediction of transmission loss of parallelepiped plenum chambers with liner (흡음재가 부착된 직방형 소음기의 전달 손실 예측)

  • 김회전;이정권;박철민
    • Proceedings of the Korean Society for Noise and Vibration Engineering Conference
    • /
    • 2003.05a
    • /
    • pp.383-386
    • /
    • 2003
  • This paper deals with transmission loss of 3-dimensional rectangular plenum lined chamber. There are three kinds of rectangular plenum lined chamber: throughflow type, flow-reversal type, and end-in/side-out type. The combination of above three types of rectangular plenum lined chamber is used for the commercial HVAC system and automobile exhaust system. However, the ambiguity and complexity of sound absorbing material property and 3-dimensional property have impeded research. In this paper, the transmission loss of three kinds of rectangular plenum lined chamber is derived and calculated. The effect of increase of sound absorbing material is also considered. Analytical solution is calculated by using the locally-reacting property of sound absorbing material.

  • PDF

Improving Vertical Airflow Uniformity Considering the Structures of the Lower Plenum in a Cleanroom (하부 플레넘 구조물 조건을 고려한 클린룸의 편류 개선 방법)

  • Kim, Young-Sub;Ha, Man-Yeong
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.20 no.1
    • /
    • pp.17-25
    • /
    • 2008
  • To achieve the unidirectional airflow in a cleanroom, we need to predict accurately the static pressure losses at the lower plenum and to control properly the opening pressure ratio of access floor panels based on these pressure losses. At first, the present study proposed a correlation to predict the velocity distribution at the lower plenum, because the accuracy to predict pressure losses at the lower plenum depends on how to calculate the velocity correctly against the inner structures at the lower plenum. In the second place, this study proposed correlations which considered the effect of inner structures such as columns, ducts and equipments at the lower plenum on pressure losses. In order to test the accuracy of these correlations, we compared air flow patterns before regulating the opening ratio of access floor with those after regulating. Results after regulating the opening ratio of access floor show good unidirectional uniform airflow pattern. So the present method can be used as an important tool to control the air flow in a cleanroom.

Employing rotating vaneless diffuser to enhance the performance of plenum fan

  • Dou, Hua-Shu;Wu, Lin;Wei, Yikun;Chen, Yongning;Cao, Wenbin;Ying, Cunlie
    • International Journal of Fluid Machinery and Systems
    • /
    • v.10 no.1
    • /
    • pp.9-18
    • /
    • 2017
  • Numerical simulation is carried out for flow characteristics in a plenum fan and the influence of the diameter ratio of the rotating vaneless diffuser on the performance of plenum fan is analyzed. The diameter ratio of the rotating vaneless diffuser employed is from 1.03 to 1.3. The research results show that the rotating vaneless diffuser is able to enhance the performance of plenum fan. It is found that there is significant improvement in static pressure and efficiency at the diameter ratio of 1.05 at high flow coefficients, while the optimal diameter ratio is 1.2 at rated and low flow coefficient.

Acoustic Analysis of Plenum Fan using Kirchhoff-BEM (Kirchhoff-BEM 을 이용한 Plenum Fan 소음해석)

  • Song, W.-S.;Jang, G. J.;Lee, S.
    • 유체기계공업학회:학술대회논문집
    • /
    • 2004.12a
    • /
    • pp.89-93
    • /
    • 2004
  • To numerically construct the sound fields by a plenum fan mostly found in Air-Handling Unit (AHU), the Kirchhoff-BEM approach was applied to the near-field data of a turbo fan. The scattering effects were found to be significant by the plenum box structure for high-frequency components of source. The directivity petterns and sound pressure levels were also dependent upon the helmholts number which must be considered of the design stage for sound reduction program.

  • PDF

Pressure and Flow Distribution in the Inlet Plenum of a Pebble Bed Modular Reactor (PBMR)

  • Ahmad, Imteyaz;Kim, Kwang-Yong
    • 유체기계공업학회:학술대회논문집
    • /
    • 2005.12a
    • /
    • pp.244-249
    • /
    • 2005
  • Flow distribution and pressure drop analysis for an inlet plenum of a Pebble Bed Modular Reactor (PBMR) have been performed using Computational Fluid Dynamics. Three-dimensional Navier-Stokes equations have been solved in conjunction with $k-{\epsilon}$ model as a turbulence closure. Non-uniformity in flow distribution is assessed for the reference case and parametric studies have been performed for rising channels diameter, Reynolds number and angle between the inlet ports. Also, two different shapes of the inlet plenum namely, rectangular shape and oval shape, have been analysed. The relative flow mal-distribution parameter shows that the flow distribution in the rising channels for the reference case is strongly non-uniform. As the rising channels diameter decreases, the uniformity in the flow distribution as well as the pressure drop inside the inlet plenum increases. Reynolds number is found to have no effect on the flow distribution in the rising channels for both the shapes of the inlet plenum. The increase in angle between the inlet ports makes the flow distribution in the rising channels more uniform.

  • PDF