• Title/Summary/Keyword: Pipe Leakage Detection

Search Result 41, Processing Time 0.032 seconds

A Study on the Improvement of Water-Leakage Detection Reliability in Local Heating System (지역난방배관의 누수감지 신뢰성 향상에 관한 연구)

  • 신춘식;안영주;변기식
    • Journal of the Korean Society of Safety
    • /
    • v.14 no.1
    • /
    • pp.66-72
    • /
    • 1999
  • Local heating transportation pipe has sensor and return lines to detect water-leakage. There are impulse and resistance comparison measurement types for a water-leakage detection. The impulse type shows large detection error within a measurement range. Since the resistance comparison type can find a comparative accurate single water-leakage point in the measurement range of heating pipe, it has been used to detect water-leakages these days. However if the multi water-leakages are happened in the measurement range of transportation pipe. the resistance comparison type shows a detection error point by the parallel resistance between a detection sensor line and ground. But the detection error will be minimized by the divided transportation pipe loops. In this research, it suggests the design of remote controlled detection system which can divide a large pipe loop and a possible single water-leakage measurement process in each divided loops.

  • PDF

IMPROVEMENT OF CROSS-CORRELATION TECHNIQUE FOR LEAK DETECTION OF A BURIED PIPE IN A TONAL NOISY ENVIRONMENT

  • Yoon, Doo-Byung;Park, Jin-Ho;Shin, Sung-Hwan
    • Nuclear Engineering and Technology
    • /
    • v.44 no.8
    • /
    • pp.977-984
    • /
    • 2012
  • The cross-correlation technique has been widely used for leakage detection of buried pipes, and this technique can be successfully applied when the leakage signal has a high signal-to-noise ratio. In the case of a power plant, the measured leakage signals obtained from the sensors may contain background noise and mechanical noise generated by adjacent machinery. In such a case, the conventional method using the cross-correlation function may fail to estimate the leakage point. In order to enhance the leakage estimation capability of a buried pipe in a noisy environment, an improved cross-correlation technique is proposed. It uses a noise rejection technique in the frequency domain to effectively eliminate the tonal noise due to rotating machinery. Experiments were carried out to verify the validity of the proposed method. The results show that even in a tonal noisy environment, the proposed method can provide more reliable means for estimating the time delay of the leakage signals.

Determining the Time of Least Water Use for the Major Water Usage Types in District Metered Areas (상수관망 블록의 대표적인 용수사용 유형에 대한 최소 용수사용 시간의 결정)

  • Park, Suwan;Jung, So-Yeon;Sahleh, Vahideh
    • Journal of Korean Society of Water and Wastewater
    • /
    • v.29 no.3
    • /
    • pp.415-425
    • /
    • 2015
  • Aging water pipe networks hinder efficient management of important water service indices such as revenue water and leakage ratio due to pipe breakage and malfunctioning of pipe appurtenance. In order to control leakage in water pipe networks, various methods such as the minimum night flow analysis and sound waves method have been used. However, the accuracy and efficiency of detecting water leak by these methods need to be improved due to the increase of water consumption at night. In this study the Principal Component Analysis (PCA) technique was applied to the night water flow data of 426 days collected from a water distribution system in the interval of one hour. Based on the PCA technique, computational algorithms were developed to narrow the time windows for efficient execution of leak detection job. The algorithms were programmed on computer using the MATLAB. The presented techniques are expected to contribute to the efficient management of water pipe networks by providing more effective time windows for the detection of the anomaly of pipe network such as leak or abnormal demand.

Analysis of Propagation of Negative Pressure Wave Due to Leak Through Damaged Hole in High Pressure Piping System (고압 배관망에서 배관 손상에 의한 누출 및 관내 저압확장파의 전파 특성 해석)

  • Kim, Wang-Yeun;Ha, Jong-Man;Ha, Tae-Woong
    • The KSFM Journal of Fluid Machinery
    • /
    • v.11 no.1
    • /
    • pp.26-32
    • /
    • 2008
  • The safe operation of high pressure pipe line systems is of significant importance. Leaks due to faulty operation from the pipelines can lead to considerable product losses and to exposure of community to dangerous gases. There are several leak detection methods of pipeline network which have recently been suggested. The negative pressure wave detection technology, which has advantages of short time detection availability, accurate leaking location estimate capability and cost effective, is concentrated in this study. Theoretical analysis of the flow characteristics for leaking through a hole on the pipe wall has been performed by using Fluent 6.3, commercial CFD package. The results of 3-dimensional analysis near leaking hole confirm the occurrence of negative pressure wave, and the results of 2-dimensional analysis verify the characteristics of propagation of the wave which travels with speed equal to the speed of sound in the pipeline contents. Characteristics of leakage and pressure in a pipe with a hole have been analyzed for the various pipe and hole sizes.

Back Tracing Calculation Method for the Leakage Detection in Water Distribution System (상수관망에서 누수탐지를 위한 역추적계산법)

  • Kwon, Hyuk Jae
    • Journal of Korean Society of Water and Wastewater
    • /
    • v.27 no.5
    • /
    • pp.611-619
    • /
    • 2013
  • In this study, Back Tracing Calculation Method was developed to determine the leakage location and leakage amount. Previously developed determination method of monitoring location and newly developed Back Tracing Calculation Method were applied to the sample pipe network and real size pilot plant. After leakage was assumed in the pilot plant, leakage location and leakage amount could be traced by Back Tracing Calculation Method. From the results, it was found that Back Tracing Calculation Method can be applied for the leakage detection in water distribution system. Furthermore, this method can be applied for the pressure management or leakage detection as a pressure control method in water distribution system.

Model-Based Detection of Pipe Leakage at Joints (모델 기반 파이프 연결부 누수 감지 시스템)

  • Kim, Taejin;Youn, Byeng D.;Woo, Sihyeong
    • Transactions of the Korean Society of Mechanical Engineers A
    • /
    • v.39 no.3
    • /
    • pp.347-352
    • /
    • 2015
  • Time domain reflectometry (TDR) is widely used for wire failure detection. It transmits a pulse that is reflected at the boundaries of different characteristic impedances. By analyzing the reflected signal, TDR makes it possible to locate the failure. In this study, TDR was used to detect the water leakage at a pipe joint. A wire attached to the pipe surface was soaked by water when a leak occurred, which affected the characteristic impedance of the wet part, resulting in a change in the reflected signal. To infer the leakage from the TDR signal, we first developed a finite difference time domain-based forward model that provided the output of the TDR signal given the configuration of the transmission line. Then, by solving the inverse problem, the locations of the leaks were found.

Application of Transient and Frequency Analysis for Detecting Leakage of a Simple Pipeline (누수탐지를 위한 천이류와 주착수분석 적용 연구)

  • Kim, Hyung-Geun;Kim, Hyun-Soo;Lee, Mi-Hyun;Kim, Sang-Hyun
    • Journal of Korean Society of Environmental Engineers
    • /
    • v.27 no.10
    • /
    • pp.1065-1071
    • /
    • 2005
  • Many techniques of leak detection in pipeline systems have developed based on the propagation wave speeds and wave attenuation. In this paper, the transient analysis methodology is used for calculating the wave speed in the plastic pipe and a frequency analysis methodology is developed for leakage detection in water pipe networks. Data acquisition system for pressurized pipeline system were designed md fabricated to obtain high frequency pressure data. The methodology properly handles the unavoidable uncertainties in measurement and modeling error. Based on information from head pressure test data, it provides leak prediction capability from the transient events with leakage.

Artificial Intelligence-based Leak Prediction using Pipeline Data (관망자료를 이용한 인공지능 기반의 누수 예측)

  • Lee, Hohyun;Hong, Sungtaek
    • Journal of the Korea Institute of Information and Communication Engineering
    • /
    • v.26 no.7
    • /
    • pp.963-971
    • /
    • 2022
  • Water pipeline network in local and metropolitan area is buried underground, by which it is hard to know the degree of pipe aging and leakage. In this study, assuming various sensor combinations installed in the water pipeline network, the optimal algorithm was derived by predicting the water flow rate and pressure through artificial intelligence algorithms such as linear regression and neuro fuzzy analysis to examine the possibility of detecting pipe leakage according to the data combination. In the case of leakage detection through water supply pressure prediction, Neuro fuzzy algorithm was superior to linear regression analysis. In case of leakage detection through water supply flow prediction, flow rate prediction using neuro fuzzy algorithm should be considered first. If flow meter for prediction don't exists, linear regression algorithm should be considered instead for pressure estimation.

Study of leak detection in a pipeline system using a portable pressure wave generator (휴대용 압력파 발생장치를 사용한 단일관로에서의 누수탐지 연구)

  • Ko, Dongwon;Lee, Jeongseop;Kim, Jinwon;Kim, Sanghyun
    • Journal of Korean Society of Water and Wastewater
    • /
    • v.34 no.2
    • /
    • pp.139-147
    • /
    • 2020
  • This paper suggests a nonlinear pressure consideration scheme through an unsteady pipe network analyzer for leakage detection with a portable pressure wave generator. In order to evaluate the performance of a proposal scheme, linear input pattern has been simulated and experiments had been carried out under both no leakage and one leakage conditions in a reservoir-pipeline-valve system. This method using portable pressure wave generator showed that a leakage can be detected from a reflection where a leakage is originated through time domain analysis. Meaningful similarity in pressure response between nonlinear input pattern and experimental results were found both no leakage and a leakage conditions.

Preliminary Analysis of a Sampling and Transportation System for Leak Detection during Steam Leak Accident of a Pipe in Nuclear Power Plants (원전 내 배관의 증기 누설 사고 시 누설 탐지 포집/이송 시스템 예비 해석)

  • Choi, Dae Kyung;Choi, Choengryul;Kwon, Tae-Soon;Euh, Dong-Jin
    • Transactions of the Korean Society of Pressure Vessels and Piping
    • /
    • v.16 no.2
    • /
    • pp.25-34
    • /
    • 2020
  • As leakage in nuclear power plants could cause a variety of problems, it is very critical to monitor leakage from the safety point of view. Accordingly, a new type of leak detection system is currently being developed and flow characteristics of the sampling and transportation system are investigated by using numerical analysis as a part of the development process in this study. The results showed that the steam mass fraction varied according to the effect of the gap between the insulation and piping component, transportation velocity, and material properties of porous media during the sampling and transportation process. The results of this study should be useful for understanding flow characteristics of the sampling and transportation system and its design and application.