• 제목/요약/키워드: Partial discharge sensors

검색결과 86건 처리시간 0.019초

신경회로망을 이용한 부분방전 신호의 패턴분석 (The Analysis of PD Signal using Neural Network)

  • 김종서;박용필;천민우
    • 한국전기전자재료학회논문지
    • /
    • 제17권5호
    • /
    • pp.567-571
    • /
    • 2004
  • Recently, GIS(Gas Insulated Switchgear) has been recognizing of importance on development of diagnosis technique which is happened problem on confidence for a long time use. Therefore, the measurement and analysis of PD with prior phenomenon of insulation breakdown is used many method of diagnosis for GIS. In this paper, we simulate trouble condition in DS and analysis trouble signal to use electrical and mechanical methods, interpretation of detected signal has analysed with to use ø-q-n pattern and neural network. For this analysis, we have used the induction and AE(acoustic emission) sensors. For the simulation experiment, we make DS for 170 KV GIS and analyze the classification and characteristics of detected signals with the application of neural network algorithm.

수중에서 2개의 광섬유센서를 이용한 초음파 음원의 위치 검출에 관한 연구 (A Study on Ultrasonic Location in Underwater Using the Two Optical Fiber Sensors)

  • 권태호;신대용;이준호;이종길
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2002년도 추계학술대회 논문집 Vol.15
    • /
    • pp.62-66
    • /
    • 2002
  • The preliminary results on the application of optical fiber sensor(OFS) for locations of ultrasonic signals in underwater are presented and analyzed. The OFS utilizing the principle of Sagnac interferometry was designed and the hollowed cylindrical mandrel wound by single mode optical fiber was used as sensing component. The ultrasonic signal source was simulated by the PZT actuator operated with function generator. It has been shown that the OFS could detect the signals less affected by ultrasonic path comparing to conventional acousto-electric sensor and accurate location of ultrasonic signal could be carried out using two OFSs.

  • PDF

GIS 부분방전 검출용 내장형 UHF 센서의 특성조사 (Studies of Internal UHF Partial Discharge Sensors for the Gas Insulated Switchgear)

  • 구선근;박기준;은진열
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 하계학술대회 논문집 C
    • /
    • pp.1840-1842
    • /
    • 2000
  • GIS(Gas Insulated Switchgear) 내부에서 부분방전 신호를 검출 할 수 있는 UHF(Ultra High Frequency) 센서를 제작하고 그 특성을 조사하였다. UHF 센서는 GIS 내부에서 전기적, 기계적으로 안정된 형태로 제작되었으며, 영국의 NGC(National Grid Company)에서 제시한 규격을 충분히 만족함을 확인하였다. 부분방전 신호가 발생되는 모형 GIS 내에 UHF 센서를 장착하여 실제 부분방전 산호가 잘 측정됨을 확인하였다.

  • PDF

부분방전 측정을 위한 음향방출센서의 교정방법에 관하여 (Calibration Method of Acoustic Emission Sensors for Measurement of Partial Discharge)

  • 김광화;이상화;선종호;한상보;김민규
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2007년도 춘계학술대회 논문집 전기설비전문위원
    • /
    • pp.131-133
    • /
    • 2007
  • This paper was described about the calibration method and setup of calibration system. This method and system were based on ISO 12713 and 12714. This system consisted of a conical type reference sensor, test block, glass capillary source and measuring oscilloscope. The waves of reference sensor and tested sensor was shown and these wave was analyzed with ISO method.

  • PDF

SF6 가스중의 공진주파수에 따른 신호특성 (Characteristic as a Resonance Frequency of $SF_6$ Gas)

  • 이용희;이현동;박정남;신양섭;박장수;서정민
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 하계학술대회 논문집 C
    • /
    • pp.1867-1869
    • /
    • 2003
  • In this paper, chamber(Circuit breaker compartment of C-GIS) made of stainless steel with 4 mm width is used. Artificial defect was made on enclosure or HV conductor of chamber and $SF_6$ gas was injected into it according to pressure. In this experiment, Acoustic emission sensors of different types was used to compare sensitivity to detect acoustic signal occurred by Partial discharge(PD) of according to types and resonance frequency in $SF_6$ gas atmosphere. Sensors used in tests was R6I, R15I and 2/4/6 Pre-Amplifier connected with R6IU without pre. amp. In case of R6IU, gain was adjusted with 40 dB like other sensors and operated by differential mode. Post amplifier(post. amp) and band pass filter(BPF) were developed Gain of post. amp. is 60 dB and BPF has band width of $50{\sim}300$ kHz. Also, envelope circuit developed reduces frequency of AE sensor. As a result, in $SF_6$ atmosphere, R6IU and R6I had resonance frequency of 60 Hz was better than R15I. Also, R6IU was better than R6I because of type property of pre.amp. had differential mode.

  • PDF

탄소나노튜브 가스센서의 SF6 분해생성물 검출 및 확산현상에 관한 연구 (Detection with a SWNT Gas Sensor and Diffusion of SF6 Decomposition Products by Corona Discharges)

  • 이종철;정세훈;백승현
    • 한국진공학회지
    • /
    • 제18권1호
    • /
    • pp.66-72
    • /
    • 2009
  • 가스절연개폐장치 (Gas-insulated switchgear, GIS)의 내부에는 절연에 관한 이상 여부를 감시하고 판단할 수 있는 시스템이 요구된다. 부분방전에 의해 발생되는 $SF_6$ 분해생성물에 관한 단일벽 탄소나노튜브 (Single-walled carbon nanotube, SWNT)가 지닌 우수한 검출기능 때문에 SWNT를 이용한 가스센서 개발이 활발히 진행되고 있다. 하지만 아직까지 부분방전에 의해 발생된 분해생성물의 확산현상에 관한 해석적 연구는 미흡한 실정이다. 본 논문에서는 실험 데이터 및 상용 CFD (Computational Fluid Dynamics) 프로그램을 이용하여 SWNT 가스센서에 포획되는 분해생성물의 코로나 방전에 의한 발생 과정과 챔버 내부에서의 확산과정을 모델링하여 부분방전 발생 시 챔버 내부의 온도, 압력, 그리고 분해생성물의 농도 등을 수치계산하였다. 분해생성물의 시간당 질량생성율과 발생온도는 각각 $5.04{\times}10^{-10}$ [g/s]와 773 K이라 가정하였다. 농도방정식을 계산함에 있어 미지의 확산계수를 임의의 값으로 가정하여 직접 부여하는 방법을 사용하지 않고, 확산계수를 정의하는데 사용되는 Schmidt수의 값을 지정하여 확산계수가 $SF_6$ 가스의 물성치인 점성계수와 밀도의 함수로 계산되도록 하였다. 수치결과로부터 분해생성물의 농도구배가 확산을 일으키는데 주요 구동포텐셜 (Drive potential)이 됨을 확인하였다. 센서 설치위치가 부분방전 발생영역에서 멀리 떨어질수록 분해생성물 농도가 낮음을 알 수 있었고, 부분방전이 지속될수록 분해생성물의 농도가 증가함을 확인하였다. 다수의 센서를 챔버 내부에 설치하면 각 센서의 응답시간을 확인하여 PD 발생위치를 판단할 수 있을 것이고, 이를 통해 GIS 진단 및 유지보수에 관한 유용한 정보로 사용될 수 있을 것이다.