• 제목/요약/키워드: Overhead Transmission Line

검색결과 215건 처리시간 0.028초

초고압 직류 가공 송전선로에서 발생되는 이온 계측시스템 개발 (The Development of System for Measuring Ion Generated from HVDC Overhead Transmission Line)

  • 주문노;양광호;이동일;신구용;임재섭
    • 전기학회논문지
    • /
    • 제57권11호
    • /
    • pp.2035-2040
    • /
    • 2008
  • The electrical discharge of high voltage direct current(HVDC) overhead transmission line generate audible noise, radio noise, electric field, ion current and induced voltage on the ground. These items are major factors to design environmentally friendly configuration of DC transmission line. Therefore, HVDC transmission lines must be designed to keep all these corona effects within acceptable levels. Several techniques have been used to assess interference caused by ions on HVDC overhead transmission line. In this study, to assess the ion characteristic of DC line, the ion current density and induced voltage caused by ion flow were measured by plate electrodes manufactured from a metal flat board and charged bodies, respectively. The charged body has two types of cylinder and cylindrical plate. From the results of calibration experiments, the sensitivity of flat electrode and charged body can be obtained. At present, the developed system is used to investigate the ion generation characteristics of Kochang DC ${\pm}500kV$ test line.

조류에 의한 가공송전선로의 고장분석 및 예방대책 고찰 (The Study for Analysis and Prevention Measure of Overhead Transmission Line Fault with Birds)

  • 정시환;강철원;김완식
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2006년도 추계학술대회 논문집 전력기술부문
    • /
    • pp.96-98
    • /
    • 2006
  • Recently major power outages are increased, because of transmission line fault by birds. Therefore, after finding out the problem of the current prevention measure for the super high voltage transmission Line in Korea and analyzing the protection measure of other foreign power companies for the transmission facilities fault by birds, this paper describes an effective device for power line fault protection by birds which has no legal problem and also protects birds. The described prevention measure of power outage by birds in this paper, has a special feature that is able to be installed on the current overhead transmission facilities without a replacement or change.

  • PDF

가공송전선의 송전용량을 증가시키기 위한 동적송전용량 시스템의 설계 (A Design for Dynamic Line Rating System to increase Overhead Transmission Line Capacities)

  • 김성덕
    • 조명전기설비학회논문지
    • /
    • 제25권7호
    • /
    • pp.72-77
    • /
    • 2011
  • Dynamic Line Rating (DLR) techniques have been greatly worthy of notice for efficiently increasing transmission capacity as well as controlling load-flow in overhead transmission lines, in comparison with the existing power system operating with Static Line Rating (SLR). This paper describes an utilization method to implement DLR control system for old transmission lines built in the first stage using the ground clearance design standard with lower dips. The suggested DLR system is focused on designing as temperature control system rather than current/load control system. Based on several performance for conductor temperatures, it is shown that DLR system with efficiency can be implemented.

신경회로망을 이용한 송전선 허용용량 예측기법 (Dynamic Line Rating Prediction in Overhead Transmission Lines Using Artificial Neural Network)

  • 노신의;김이관;임성훈;김일동
    • 조명전기설비학회논문지
    • /
    • 제28권1호
    • /
    • pp.79-87
    • /
    • 2014
  • With the increase of demand for electricity power, new construction and expansion of transmission lines for transport have been required. However, it has been difficult to be realized by such opposition from environmental groups and residents. Therefore, the development of techniques for effective use of existing transmission lines is more needed. In this paper, the major variables to affect the allowable transmission capacity in an overhead transmission lines were selected and the dynamic line rating (DLR) method using artificial neural networks reflecting unique environment-heat properties was proposed. To prove the proposed method, the analyzed results using the artificial neural network were compared with the ones obtained from the existing method. The analyzed results using the proposed method showed an error of 0.9% within ${\pm}$, which was to be practicable.

Assesment of the Decrement in Tensile Strength of an Overhead Transmission Line's Conductor in Korean Power System

  • Bae, In-Su;Kim, Dong-Min;Kim, Jin-O
    • 조명전기설비학회논문지
    • /
    • 제20권9호
    • /
    • pp.61-69
    • /
    • 2006
  • The tensile strength of an overhead transmission line's conductor in response to an aging is being assessed in this paper. It is our view that, the decrement in the conductor's tensile strength is a key index that can be used to determine a conductor's end of life and a current limits. This paper describes a probabilistic method of assessing this index for main transmission lines which are responsible for the north bound power flow in the Seoul metropolitan area. Such an assessment can be a useful guide for economic system operation.

A Simulator for Calculating Normal Induced Voltage on Communication Line

  • Heo, Jeong-Yong;Seo, Hun-Chul;Lee, Soon-Jeong;Kim, Yoon Sang;Kim, Chul-Hwan
    • Journal of Electrical Engineering and Technology
    • /
    • 제9권4호
    • /
    • pp.1394-1400
    • /
    • 2014
  • The current flowing through the overhead transmission lines causes induced voltage on the communication lines, which can be prevented by calculating the induced voltage at the planning stage for overhead transmission line installment through an agreement between the communication and electric power companies. The procedures to calculate the induced voltages, however, are complicated due to the variety of parameters and tower types of the overhead transmission lines. The difficulty necessitates the development of a simulator to measure the induced voltage on the communication lines. This paper presents two simulators developed for this purpose; one using the Data Base (DB) index method and the other using the Graphic User Interface (GUI) method. The simulators described in this paper have been implemented by the EMTP (Electromagnetic Transient Program).

Analysis on Ampacity of Overhead Transmission Lines Being Operated

  • Yan, Zhijie;Wang, Yanling;Liang, Likai
    • Journal of Information Processing Systems
    • /
    • 제13권5호
    • /
    • pp.1358-1371
    • /
    • 2017
  • Dynamic thermal rating (DTR) system is an effective method to improve the capacity of existing overhead line. According to the methodology based on CIGRE (International Council on Large Electric systems) standard, ampacity values under steady-state heating balance can be calculated from ambient environmental conditions. In this study, simulation analysis of relations between parameters and ampacity is described as functional dependence, which can provide an effective basis for the design and research of overhead transmission lines. The simulation of ampacity variation in different rating scales is described in this paper, which are determined from real-time meteorological data and conductor state parameters. To test the performance of DTR in different rating scales, capacity improvement and risk level are presented. And the experimental results show that the capacity of transmission line by using DTR has significant improvement, with low probability of risk. The information of this study has an important reference value to the operation management of power grid.

가공송전용 철탑설계기준(안) 소개 및 주요내용 해설 (Introduction of the Design Standard of Tower for Overhead Transmission Line in KEPCO)

  • 김경호;우정욱;심응보;신태우;유철환;방항권
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 하계학술대회 논문집 A
    • /
    • pp.351-353
    • /
    • 2002
  • Up to now the design standard of tower for overhead transmission line in KEPCO was revised four times since 1970. During last year. we had reviewed this design standard. This paper shows the design standard of tower for overhead transmission line in KEPCO. In this standard, a kind of tower was defined as standard tower and special tower. Also we had defined usage range of standard tower, tower height, arrangement of power line, design condition of tower arm and etc. On the wind pressure, we had defined basic velocity pressure per region and maximum wind pressure. For special region, design wind pressure will be considered the receded wind velocity of meteorological observatory and regional condition by this standard.

  • PDF

카테너리 각도를 이용한 가공송전도체의 이도 추정 (Dip Estimation for Overhead Transmission Conductor using Catenary Angle)

  • 김성덕;손홍관;장태인
    • 조명전기설비학회논문지
    • /
    • 제21권5호
    • /
    • pp.112-119
    • /
    • 2007
  • 가공송전 도체는 정상 동작조건 하에서 전력회사의 선로 설계지침에 규정된 지상고를 안정범위 내에서 항상 유지할 수 있어야 한다. 따라서 새로운 선로를 건설하거나 노화도체의 장력을 다시 조정하거나 또는 전력용량을 최대화하기 위해 동적송전용량을 모니터링하는 경우에, 도체 이도를 측정/또는 모니터링하는 것은 매우 중요하다. 본 연구에서는 도체의 카테너리 각도로 이도 및 장력을 추정하기 위한 새로운 방법을 제안한다. 가공송전선로의 대부분의 도체들은 전형적인 카테너리 곡선을 나타내므로 철탑 측의 카테너리 각도로부터 도체의 카테너리 곡선을 유일하게 결정할 수 있다. 이 카테너리 곡선을 토대로 도체의 이도나 수평장력을 쉽게 추정할 수 있다. 몇 가지 시뮬레이션과 간단한 실험 결과를 통하여 제안된 방법이 가공송전선의 도체 이도와 장력을 측정/또는 모니터링하는데 효과적으로 사용될 수 있음을 확인하였다.

가공송전선로의 AAR 적용 시 Risk Tolerance 분석을 이용한 계절별 최대 허용전류 산정 및 적용에 관한 연구 (Study on the Estimation of Seasonal Ambient Current for the Application of Ambient Adjusted Line Rating(AAR) in Overhead Transmission Lines Using Risk Tolerance(RT) Method)

  • 이재걸;배영재;송지영;신정훈;김용학;김태균;윤용범
    • 전기학회논문지
    • /
    • 제66권1호
    • /
    • pp.7-15
    • /
    • 2017
  • Ambient Adjusted line Rating(AAR) method for overhead transmission lines considering Risk Tolerance(RT) was proposed in this paper. AAR is suitable for system operators to plan their operation strategy and maintenance schedule because this can be designed as a seasonal line rating. Several candidate transmission lines are chosen to apply the proposed method in the paper. As a result, it is shown that system reliability was significantly enhanced through maximizing transfer capability, solving the system constraints.