2단 평행판 전기집진기의 서브마이크론입자 집진성능 개선 연구 (Study on improvement of submicron particle collection performance in 2-stage parallel-plate electrostatic precipitators)

  • 유경훈;오명도;이준식
    • 설비공학논문집
    • /
    • 제9권3호
    • /
    • pp.323-332
    • /
    • 1997
  • It was reported by some researchers that two-stage parallel-plate ESPs, commonly called electronic air cleaners, show decreasing behavior of collection efficiency as particle size decreases below about $0.03{\mu}m$. This phenomenon is attributed to partial particle charging characteristics, where some of incoming particles are not charged in the charging cell of 2-stage parallel-plate ESP. One way to improve the decreasing collection efficieny in that particle size range is to enforce particle charging quantity in the charging cell. In the present study, in order to do this a 2-wire series-type charging cell modified from a 1-wire normal-type one was suggested and investigated theoretically and experimentally concerning improvement of the collection efficiency. It was confirmed from the experimental and theoretical works that the collection efficiency was apparently improved.

  • PDF

$CO_2$ 냉동시스템에서 압축기의 흡입온도와 운전주파수가 오일 순환량에 미치는 영향 (Effect of Suction Temperature and Compressor Frequency on Oil Circulation Ratio in a $CO_2$ Refrigeration System)

  • 김경재;이익수;강병하;김석현
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2009년도 하계학술발표대회 논문집
    • /
    • pp.893-898
    • /
    • 2009
  • The quantity of discharged oil from a compressor is one of the most important issues for proper operation of refrigeration system. If the oil is increased in the system not only pressure drop is increased in other components, such as evaporator and gas cooler but also heat transfer coefficient in the heat exchangers is decreased. In addition, the lack of oil in the compressor may cause a critical of the system failure. In this study, one stage single rotary compressor is used for measuring oil circulation ratio(OCR). Carbon dioxide and PAG oil are used as refrigerant and lubricant. Using a U-tube densimeter, mixture density is measured. Characteristics of oil circulation ratio have been investigated for $CO_2$ rotary compressor in the range of operation frequency 45 Hz to 63 Hz and the suction temperature range of $0^{\circ}C$ to $15^{\circ}C$. The results obtained indicate that the oil circulation ratio is increased as the suction temperature or compressor operating frequency is increased.

  • PDF

심냉 증류를 통한 전자급 고순도 이산화탄소의 분리 공정에 대한 전산 모사 연구 (A Computer Simulation Study on the Separation Process for Electronic Grade, Highly Pure Carbon Dioxide through a Cryogenic Distillation)

  • 박일수;문흥만;조정호
    • 한국수소및신에너지학회논문집
    • /
    • 제34권1호
    • /
    • pp.83-89
    • /
    • 2023
  • In this study, a computer simulation work has been performed for the separation of electronic grade highly pure carbon dioxide more than 7 N purity through a cryogenic distillation process. For the cold utility as a cooling medium for a condenser of the cryogenic distillation column, propylene was utilized as a refrigerant in the vapor-recompression refrigeration cycle. Through this work, it was concluded that the cryogenic distillation column with two stage compression and refrigeration cycle were essential to obtain a highly-pure liquefied CO2.

CO2 압축기의 운전조건과 오일토출의 상관분석에 관한 실험적 연구 (An Experimental Study on Correlation between Oil Discharge and Various Operating Conditions of a CO2 Compressor)

  • 이익수;강병하
    • 설비공학논문집
    • /
    • 제23권1호
    • /
    • pp.73-79
    • /
    • 2011
  • A portion of oil for lubrication of compressor flows together with refrigerant in the refrigeration system. If the oil discharge from a compressor is increased in the refrigeration system, not only pressure drop is increased in other components, such as evaporator and gas cooler, but also heat transfer coefficient in the heat exchangers is decreased. Oil discharge rate from a compressor may strongly depend on operating conditions of a compressor. In this study, one stage single rotary compressor is employed for measuring oil circulation ratio(OCR). Carbon dioxide and PAG oil are used as refrigerant and lubricant. Using a U-tube densimeter, mixture density is measured. Oil circulation ratio(OCR) can be estimated by measured mixture density. The results obtained indicate that the oil circulation ratio(OCR) is increased as the suction temperature or compressor operating frequency is increased. Oil circulation ratio(OCR) correlation of the compressor is also suggested.

1단 2실린더 $CO_2$ 압축기의 실린더 형상 최적 설계 (Optimal Design of Cylinder Configuration for a 1-Stage Two Cylinder $CO_2$ Compressor)

  • 안종민;김현진;조성욱
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2008년도 동계학술발표대회 논문집
    • /
    • pp.119-124
    • /
    • 2008
  • Recently, focus has been drawn on natural refrigerants due to increasing concern on global warming. As a consequence, CO2 systems such as a heat pump water heater using CO2 as a refrigerant are rapidly growing on the market. Currently, rolling piston rotary compressors are widely used for CO2 heating and/or refrigeration systems. There are several ways of realizing gas compression structure. They are single stage compression with single cylinder, single stage compression with two cylinders, and two stage compression with two cylinders. In this paper, computer simulation program which was validated for a single stage rotary compressor with one cylinder has been extended for a single stage, two cylinder rotary type. Numerical investigation has been made on optimal design for the cylinder configuration using the extended simulation program. For a single stage two cylinder rotary compressor having a displacement volume of 4 cc for each cylinder, compressor efficiency has been found to be maximum when the cylinder radius and height are 31mm and 10mm, respectively.

  • PDF

설비공학 분야의 최근 연구 동향 : 2016년 학회지 논문에 대한 종합적 고찰 (Recent Progress in Air-Conditioning and Refrigeration Research : A Review of Papers Published in the Korean Journal of Air-Conditioning and Refrigeration Engineering in 2016)

  • 이대영;김사량;김현정;김동선;박준석;임병찬
    • 설비공학논문집
    • /
    • 제29권6호
    • /
    • pp.327-340
    • /
    • 2017
  • This article reviews the papers published in the Korean Journal of Air-Conditioning and Refrigeration Engineering during 2016. It is intended to understand the status of current research in the areas of heating, cooling, ventilation, sanitation, and indoor environments of buildings and plant facilities. Conclusions are as follows. (1) The research works on the thermal and fluid engineering have been reviewed as groups of flow, heat and mass transfer, the reduction of pollutant exhaust gas, cooling and heating, the renewable energy system and the flow around buildings. CFD schemes were used more for all research areas. (2) Research works on heat transfer area have been reviewed in the categories of heat transfer characteristics, pool boiling and condensing heat transfer and industrial heat exchangers. Researches on heat transfer characteristics included the results of the long-term performance variation of the plate-type enthalpy exchange element made of paper, design optimization of an extruded-type cooling structure for reducing the weight of LED street lights, and hot plate welding of thermoplastic elastomer packing. In the area of pool boiling and condensing, the heat transfer characteristics of a finned-tube heat exchanger in a PCM (phase change material) thermal energy storage system, influence of flow boiling heat transfer on fouling phenomenon in nanofluids, and PCM at the simultaneous charging and discharging condition were studied. In the area of industrial heat exchangers, one-dimensional flow network model and porous-media model, and R245fa in a plate-shell heat exchanger were studied. (3) Various studies were published in the categories of refrigeration cycle, alternative refrigeration/energy system, system control. In the refrigeration cycle category, subjects include mobile cold storage heat exchanger, compressor reliability, indirect refrigeration system with $CO_2$ as secondary fluid, heat pump for fuel-cell vehicle, heat recovery from hybrid drier and heat exchangers with two-port and flat tubes. In the alternative refrigeration/energy system category, subjects include membrane module for dehumidification refrigeration, desiccant-assisted low-temperature drying, regenerative evaporative cooler and ejector-assisted multi-stage evaporation. In the system control category, subjects include multi-refrigeration system control, emergency cooling of data center and variable-speed compressor control. (4) In building mechanical system research fields, fifteenth studies were reported for achieving effective design of the mechanical systems, and also for maximizing the energy efficiency of buildings. The topics of the studies included energy performance, HVAC system, ventilation, renewable energies, etc. Proposed designs, performance tests using numerical methods and experiments provide useful information and key data which could be help for improving the energy efficiency of the buildings. (5) The field of architectural environment was mostly focused on indoor environment and building energy. The main researches of indoor environment were related to the analyses of indoor thermal environments controlled by portable cooler, the effects of outdoor wind pressure in airflow at high-rise buildings, window air tightness related to the filling piece shapes, stack effect in core type's office building and the development of a movable drawer-type light shelf with adjustable depth of the reflector. The subjects of building energy were worked on the energy consumption analysis in office building, the prediction of exit air temperature of horizontal geothermal heat exchanger, LS-SVM based modeling of hot water supply load for district heating system, the energy saving effect of ERV system using night purge control method and the effect of strengthened insulation level to the building heating and cooling load.

설비공학 분야의 최근 연구 동향 : 2013년 학회지 논문에 대한 종합적 고찰 (Recent Progress in Air-Conditioning and Refrigeration Research : A Review of Papers Published in the Korean Journal of Air-Conditioning and Refrigeration Engineering in 2013)

  • 이대영;김사량;김현정;김동선;박준석;임병찬
    • 설비공학논문집
    • /
    • 제26권12호
    • /
    • pp.605-619
    • /
    • 2014
  • This article reviews the papers published in the Korean Journal of Air-Conditioning and Refrigeration Engineering during 2013. It is intended to understand the status of current research in the areas of heating, cooling, ventilation, sanitation, and indoor environments of buildings and plant facilities. Conclusions are as follows. (1) The research works on the thermal and fluid engineering have been reviewed as groups of fluid machinery, pipes and relative parts including orifices, dampers and ducts, fuel cells and power plants, cooling and air-conditioning, heat and mass transfer, two phase flow, and the flow around buildings and structures. Research issues dealing with home appliances, flows around buildings, nuclear power plant, and manufacturing processes are newly added in thermal and fluid engineering research area. (2) Research works on heat transfer area have been reviewed in the categories of heat transfer characteristics, pool boiling and condensing heat transfer and industrial heat exchangers. Researches on heat transfer characteristics included the results for general analytical model for desiccant wheels, the effects of water absorption on the thermal conductivity of insulation materials, thermal properties of Octadecane/xGnP shape-stabilized phase change materials and $CO_2$ and $CO_2$-Hydrate mixture, effect of ground source heat pump system, the heat flux meter location for the performance test of a refrigerator vacuum insulation panel, a parallel flow evaporator for a heat pump dryer, the condensation risk assessment of vacuum multi-layer glass and triple glass, optimization of a forced convection type PCM refrigeration module, surface temperature sensor using fluorescent nanoporous thin film. In the area of pool boiling and condensing heat transfer, researches on ammonia inside horizontal smooth small tube, R1234yf on various enhanced surfaces, HFC32/HFC152a on a plain surface, spray cooling up to critical heat flux on a low-fin enhanced surface were actively carried out. In the area of industrial heat exchangers, researches on a fin tube type adsorber, the mass-transfer kinetics of a fin-tube-type adsorption bed, fin-and-tube heat exchangers having sine wave fins and oval tubes, louvered fin heat exchanger were performed. (3) In the field of refrigeration, studies are categorized into three groups namely refrigeration cycle, refrigerant and modeling and control. In the category of refrigeration cycle, studies were focused on the enhancement or optimization of experimental or commercial systems including a R410a VRF(Various Refrigerant Flow) heat pump, a R134a 2-stage screw heat pump and a R134a double-heat source automotive air-conditioner system. In the category of refrigerant, studies were carried out for the application of alternative refrigerants or refrigeration technologies including $CO_2$ water heaters, a R1234yf automotive air-conditioner, a R436b water cooler and a thermoelectric refrigerator. In the category of modeling and control, theoretical and experimental studies were carried out to predict the performance of various thermal and control systems including the long-term energy analysis of a geo-thermal heat pump system coupled to cast-in-place energy piles, the dynamic simulation of a water heater-coupled hybrid heat pump and the numerical simulation of an integral optimum regulating controller for a system heat pump. (4) In building mechanical system research fields, twenty one studies were conducted to achieve effective design of the mechanical systems, and also to maximize the energy efficiency of buildings. The topics of the studies included heating and cooling, HVAC system, ventilation, and renewable energies in the buildings. Proposed designs, performance tests using numerical methods and experiments provide useful information and key data which can improve the energy efficiency of the buildings. (5) The field of architectural environment is mostly focused on indoor environment and building energy. The main researches of indoor environment are related to infiltration, ventilation, leak flow and airtightness performance in residential building. The subjects of building energy are worked on energy saving, operation method and optimum operation of building energy systems. The remained studies are related to the special facility such as cleanroom, internet data center and biosafety laboratory. water supply and drain system, defining standard input variables of BIM (Building Information Modeling) for facility management system, estimating capability and providing operation guidelines of subway station as shelter for refuge and evaluation of pollutant emissions from furniture-like products.

사무공간의 통합유니트 구축을 위한 공조유니트 도출에 관한 연구 (Development of the Air-Conditioning Unit for Workspace Integrated Units)

  • 김지현;김선숙;양인호;김광우
    • 설비공학논문집
    • /
    • 제17권7호
    • /
    • pp.669-680
    • /
    • 2005
  • The purpose of this study is to develop the air-conditioning unit combined with the lighting unit for workspace and to supply its performance data at architectural design stage. The air-conditioning unit is one of the components of a workspace integrated unit, which can be defined as the planning unit satisfying the environmental comfort criteria of workspace. Air-conditioning diffusers are classified according to throws and features by literature review and case study. Then diffusers are combined with the lighting unit. Through the CFD simulation, the thermal performance of each unit was evaluated and finally various air-conditioning units combined with the lighting units were developed.

2단 압축 방식을 적용한 초저온 액화 사이클 특성 (Characteristics of cryogenic liquefaction cycle using two stage compression type)

  • 오승택;이호생;이경범;윤정인;이상규
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2009년도 하계학술발표대회 논문집
    • /
    • pp.556-560
    • /
    • 2009
  • In this paper, two different types of natural gas liquefaction process are simulated and designed for secure a competitiveness in the industry of natural gas liquefaction plant. These processes are based on basic cascade process, and one of these is improved with two staged intercooler and the other is modified two staged intercooler. These processes are compared characteristics of performance with basic process. COP of cascade process with two staged intercooler and modified two staged intercooler showed about 13.74% and 21.64% higher than basic process, and yield efficiency of modified process improved comparing with the basic process by 25.93% lower specific power, respectively.

  • PDF

해수열원 히트펌프 시스템의 냉난방 운전 특성에 관한 실증 연구 (Experimental Study on the Cooling and Heating Operation Characteristics of a Sea Water Source Heat Pump)

  • 김지영;백영진;나호상;장기창
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2009년도 하계학술발표대회 논문집
    • /
    • pp.544-549
    • /
    • 2009
  • The purpose of this study is to investigate the field Operation Characteristics of a sea water heat source cascade heat pump system and system applicable to Building. Cascade heat pump system is composed R410A compressor, R134a compressor, EEV, cascade heat exchanger, Plate heat exchanger etc. Building area is $890m^2$ and has five floors above ground. R410A is used for a low-stage working fluid while R134a is for a high-stage. The system could runs at dual mode. One is mode of general R410A refrigeration cycle in summer and the other is cascade cycle. In order to gain a high temperature supply water in winter season, the system is designed to perform a cascade cycle. The filed test results show that the sea water heat source heat pump system exhibits a COP of about 5.5 in cooling mode along with a heating COP of about 4.0 in 1-stage heating mode. Cascade 2-stage heat pump system is enough to supply $60^{\circ}C$ water and heating COP is about 3.0