• Title/Summary/Keyword: Oil-immersed transformers

Search Result 34, Processing Time 0.032 seconds

The Evaluation of Characteristics for Insulating Oil Using the Distribution Transformer (배전용 변압기 절연유의 특성 비교 평가)

  • Lee, Byung-Sung;Park, Young-Keun;Kim, Dong-Myung;Kim, Pil-Hwan;Han, Sang-Ok
    • Proceedings of the KIEE Conference
    • /
    • 2004.11d
    • /
    • pp.97-99
    • /
    • 2004
  • Liquid-immersed pole transformers have utilized an insulation system consisting of natural cellulose-based materials and mineral oil for many years. If the transformers are installed with the abruptly changing load over limitation, its insulation materials are apt to unexpected aging with high temperature. Therefore we have been conscious of developing a transformer that is more thermally stable then conventional types. To measure temperature distribution in the winding of conventional and newly designed transformers, temperature sensors were installed fordirect reading of oil and conductor temperatures at transformers. And we conducted accelerating aging test for these transformers. The measuring data had made use of the design to hybrid insulation system. Also we could find the possibility of this insulation system to apply in pole mounted transformers.

  • PDF

Analysis of Aging Characteristics in Oil Immerged Pole Transformer (과부하 및 경년 변압기 절연유 열화 특성 분석 연구)

  • Lee, Byung-Sung;Song, Il-Keun;Lee, Jae-Bong;Park, Dong-Bea;Han, Sang-Ok
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2002.05c
    • /
    • pp.203-207
    • /
    • 2002
  • In order to evaluate the aging of mineral oil immersed distribution transformers, it gathered some insulation oil in over loaded and long time(exceed their service life, 13yrs.) aged transformers in the field, we measured moisture content, acid number, dielectric strength of the oil as defined in KS C 2101 standard. And also, it had been measured dielectric constant, specific resistant, $tan{\delta}$ on aged transformer oil at from $10^{\circ}C$ to $130^{\circ}C$. These results are compared with a new mineral oil. From this study, it can be considered that the analysis of mineral oil may be suitable for evaluation of life expectancy in distribution transformers

  • PDF

Development of Management Software for Transformers Based on Artificial Intelligent Analysis Technology of Dissolved Gases in Oil (지능형 유중가스 분석기술 기반 유입식 변압기 전산관리 프로그램 개발)

  • Sun Jong-Ho;Han Sang-Bo;Kang Dong-Sik;Kim Kwang-Hwa
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.54 no.12
    • /
    • pp.578-584
    • /
    • 2005
  • This paper describes development of management software for transformers based on artificial intelligent analysis technology of dissolved gases in oil. Fault interpretation using the artificial intelligent analysis is performed by the artificial neural network and a rule based on the analysis of dissolved gases. The used gases are acetylene($C_{2}H_{2}$), hydrogen($H_2$), ethylene($C_{2}H_{4}$), methane($CH_4$), ethane($C_{2}H_{6}$), carbon monoxide(CO) and carbon dioxide($CO_2$). This software is mainly composed of gases input, fault's causes, expected fault's phenomena in detail, the decision on maintenance as well as report and gas trend windows. It is indicated that this is very powerful software for the efficient management of oil-immersed transformers using data analysis of gas components.

Overload Criterion of Mineral-Oil-Immersed Distribution Transformers Rated 100kVA and Less (100kVA 이하 유입식 배전용변압기의 과부하 판정기준 설정)

  • Yun, Sang-Yun;Kim, Jae-Chul;Lee, Young-Suk;Park, Chang-Ho;Shon, Hwa-Young
    • Proceedings of the KIEE Conference
    • /
    • 2001.11b
    • /
    • pp.6-8
    • /
    • 2001
  • This paper covers general recommendations for top-oil temperature rising of mineral-oil-immersed power distribution transformer rated 100kVA and less, manufactured in Korea. In order to analyze the top-oil temperature rising due to the distribution transformer loading we performed experiments for oil-immersed distribution transformer, manufactured in domestic at KERI(Korea Electrical Research Institute) from December 2000 to May 2001. The magnitude of loading were changed, and the top-oil temperatures for each time were measured. Finally, we present the overload criteria of distribution transformer for summer and winter season in domestic. respectively.

  • PDF

A Study on Deterioration Evaluation Method by Condition Monitoring and Diagnosis for Aging Oil-immersed Power Transformers (유입식 변압기의 상태진단을 통한 노후도 평가 방법)

  • Chang, Jeong-Ho;Lee, Sung-Hun;Lee, Heung-Ho
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.63 no.2
    • /
    • pp.297-305
    • /
    • 2014
  • Nowadays new water supply projects have been on the decline as the water-power constructions have saturated, which means that the existing power equipment have slowly aged and they require more efforts to maintain the system performance. An effective asset management method of power equipment has become a great necessity from both economical and technical aspects. To be balanced, the asset management should look into all three parts: management, engineering, and information. The purpose of this paper is to study a Risk-Based Maintenance (RBM) matrix method through the deterioration evaluation algorithm for an efficient reliability assessment of oil-immersed power transformers by considering both asset management and technical evaluation. Make use of this result, the equipment will be decided to be replace or repair otherwise on service.

A Study on the Acoustic Detection of Partial Discharges in Insulation Oil (유중 부분방전의 음향검출에 관한 연구)

  • Kil, Gyung-Suk;Kim, Sung-Wook;Park, Dae-Won;Kim, Sun-Jae;Song, Jae-Man
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.23 no.1
    • /
    • pp.53-60
    • /
    • 2010
  • This paper dealt with the acoustic detection of partial discharge (PD) in insulation oil for insulation diagnostics of oil immersed transformers. Electrode systems such as needle to plane, plane to plane, and floating were fabricated to simulate some defects in transformers. A wide band acoustic emission(AE) sensor with the frequency ranges of 100 kHz~1 MHz and a narrow band AE sensor with the resonant frequency of 140 kHz were used in the experiment. Also, a decoupler and an amplifier were designed to detect and amplify the acoustic signal only. The decoupler separates acoustic signal from DC source without any distortion, and the amplifier has the gain of 40 dB in frequency ranges of 11 kHz~4 MHz. In the experiment, frequency components and propagation characteristics of acoustic signal were analyzed, and an algorithm of positioning of PD occurrence by the time difference of arrival was proposed. From the results, the frequency components of the acoustic signal exist from 50 kHz to 200 kHz and the positioning error of PD calculated by three AE sensors was within 1%.

Characteristic Analysis and Origin Positioning of Acoustic Signals Produced by Partial Discharges in Insulation Oil

  • Park, Dae-Won;Jo, Hyang-Eun;Kim, Sun-Jae;Kil, Gyung-Suk
    • Journal of Electrical Engineering and Technology
    • /
    • v.8 no.6
    • /
    • pp.1468-1473
    • /
    • 2013
  • This paper dealt with the propagation characteristics of acoustic signals produced by partial discharges and the positioning of PD origin in insulation oil to develop insulation diagnostic techniques of oil-immerged transformers. Electrode systems such as needle to plane, plane to plane, and particle electrodes were fabricated to simulate some defects of power transformers. In addition, the frequency spectrum and propagation characteristics of acoustic signals with partial discharge (PD) in insulation oil were analyzed. Although there were differences based on the type of defect, the frequency spectra of the acoustic signals measured by wide and narrow band acoustic emission (AE) sensors were distributed in the range of 50 kHz-400 kHz. Therefore, a narrowband AE sensor is suitable for the diagnosis of oil-immersed power transformers. We could find the position of the PD source with an error margin of 10% in the experiments by calculating the position of the PD occurrence using the time difference of arrival measured by five AE sensors.

The Study on Application of Hybrid Insulation System for Thermally Upgraded Distribution pole Transformers (주상변압기 열적 특성 향상을 위한 복합절연 시스템 적용)

  • Lee, B.S.;Song, I.K.;Lee, J.B.;Kim, D.M.;Han, S.O.
    • Proceedings of the KIEE Conference
    • /
    • 2002.07c
    • /
    • pp.1896-1898
    • /
    • 2002
  • In this paper, to developing thermally and mechanically upgraded ones, we dismounted pole transformers used in the fields for over 13 years and conducted aged oil analysis. Also, when the cellulose and aramid papers in test cell were aging with oil at $130^{\circ}C$ for 3000 hours, with the testing period cellulose paper deteriorated more rapidly than the others. For example dielectric strength and dissipation factor of papers deteriorated with aging time. For evaluation of thermal aging characteristics, a mineral oil-immersed transformer was constructed with hybrid insulation system comprised of aramid paper and cellulose insulation. A Hybrid system has economic advantages. Cellulose materials are confined to cooler regions of the transformer winding. And aramid papers are served to insulate contact parts of hot conductors.

  • PDF

A Hybrid Type Based Expert System for Fault Diagnosis in Transformers (변압기 고장 진단을 위한 하이브리드형 전문가 시스템)

  • Jeon, Young-Jae;Yoon, Yong-Han;Kim, Jae-Chul;Choi, Do-Hyuk
    • Proceedings of the KIEE Conference
    • /
    • 1996.11a
    • /
    • pp.143-145
    • /
    • 1996
  • This paper presents the hybrid type based expert system for fault diagnosis in transformers. The proposed system uses the novel fault diagnostic technique based on dissolved gas analysis(DGA) in oil-immersed transformers. The uncertainty of key gas analysis, norm threshold, and gas ratio boundaries are managed by using a fuzzy set. Also, the uncertainty of the fault diagnostic rules are handled by using fuzzy measures. Finally, kohnen's feature map performs fault classification in transformers. To verify the effectiveness of the proposed diagnosis technique, the hybrid type based expert system for fault diagnosis has been tested by using KEPCO's transformer gas records.

  • PDF

Application of On-line Diagnostic System for Oil-filled Power Transformers (대용량 변압기 예방진단 시스템 적용 사례)

  • Kim Y.H.;Lee C.R.;Hwangbo S.W.;;Shin Y.T.;Park K.S.;Lee J.B.
    • Proceedings of the KIEE Conference
    • /
    • summer
    • /
    • pp.590-593
    • /
    • 2004
  • This paper presents recent trends on the on-line monitoring and diagnostic systems for oil-immersed transformers. Specially, our system on YeoSu thermal power plant is introduced for high sensitivity and accuracy of ours. It is combined with communication networks to provide an on-line remote monitoring system. Several alarm criteria are formulated to enable a superimposed monitoring system to perform decisive action. The reasons for monitoring the condition and maintaining the health of electrical apparatus were discussed. The experience at the fields and the criteria for the judgment are also discussed in detail.

  • PDF