• 제목/요약/키워드: Mineral Oil

검색결과 524건 처리시간 0.029초

친환경 식물성 절연유의 유중가스 분석 (Dissolved Gas Analysis of Environment-Friendly Vegetable Insulating Oils)

  • 최순호;김관식;허창수
    • 한국전기전자재료학회논문지
    • /
    • 제28권4호
    • /
    • pp.238-243
    • /
    • 2015
  • The vegetable insulating oils are substitute for the mineral oil in power transformer. Vegetable insulating oils has higher flash/fire point and biodegradability than conventional mineral oils. In this paper, we investigated the dissolved gas analysis of vegetable oils. In the experiment, I had to accelerated aging under the same conditions mineral oil and vegetable oils. Accelerated aging proceeded to about 100% of the life of oil-filled transformer. In addition, we performed gas analysis of insulating oil of accelerated aging progress. The experiment results of the five gases was measured with the exception of Hydrogen and Acetylene. The mineral oil and vegetable oils gas is generated in a similar tendency depending on the accelerated aging. As a result, vegetable oils, can be dissolved gas analysis by method such as mineral oil.

최상부 유온 상승 특성을 이용한 100kVA 이하 유입식 배전용 변압기의 과부하 판정 기준 (Overload Criterion of Mineral-Oil-immersed Distribution Transformers Rated 100kVA and Less Using the Characteristics of Top-Oil Temperature Rising)

  • 윤상윤;김재철;박창호
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제51권11호
    • /
    • pp.559-567
    • /
    • 2002
  • This paper presents the general recommendations for the overload criterions of mineral-oil-immersed distribution transformers rated 100kVA and less. For this purpose, we analyze the characteristics of top-oil temperature rising for mineral-oil-immersed power distribution transformer rated 100kVA and less, manufactured in Korea, In order to analyze the characteristics of top-oil temperature rising due to the distribution transformer loading, we performed experiments at KERI (Korea Electrical Research Institute) from December 2000 to May 2001. The restraint of ambient temperatures for the experiment results is solved using the results of foreign standards. Finally, we present the overload criterions of distribution transformer for summer and winter season, respectively.

과부하 및 경년 변압기 절연유 열화 특성 분석 연구 (Analysis of Aging Characteristics in Oil Immerged Pole Transformer)

  • 이병성;송일근;이재봉;박동배;한상옥
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2002년도 춘계학술대회 논문집 유기절연재료 전자세라믹 방전플라즈마 일렉트렛트 및 응용기술
    • /
    • pp.203-207
    • /
    • 2002
  • In order to evaluate the aging of mineral oil immersed distribution transformers, it gathered some insulation oil in over loaded and long time(exceed their service life, 13yrs.) aged transformers in the field, we measured moisture content, acid number, dielectric strength of the oil as defined in KS C 2101 standard. And also, it had been measured dielectric constant, specific resistant, $tan{\delta}$ on aged transformer oil at from $10^{\circ}C$ to $130^{\circ}C$. These results are compared with a new mineral oil. From this study, it can be considered that the analysis of mineral oil may be suitable for evaluation of life expectancy in distribution transformers

  • PDF

열화된 광유와 식물성절연유에서 온도, 벤조트리아졸의 유동대전 영향 (Influence of Temperature and Benzotriazole on the Flow Electrification by aging Mineral, Vegetable Oil)

  • 최순호;정중일;허창수
    • 전기학회논문지
    • /
    • 제60권2호
    • /
    • pp.338-343
    • /
    • 2011
  • In this paper, the FT-IR, conductivity and flow electrification phenomena of Vegetable oils were discussed. Vegetable oil has high flash point and eco-friendly properties compared to conventional mineral oil. Accelerated aging transformer oil samples produced in the oven at 140[$^{\circ}C$] for 500 hours, 1000 hours, 1500 hours, 2000 hours. Serial device to measure the flow electrification phenomena was designed and fabricated. Pico ammeter and the Labview data measurements were utilized. The effects of Temperature and antistatic agent on fluid flow electrification were investigated. Both Mineral and vegetable oil showed similar trends for temperature change. The polarity reversal occurred in mineral oil with antistatic agent above 10 ~ 30[ppm] and in vegetable oil with antistatic agent above 5[ppm].

Comparative Study of DC Breakdown and Space Charge Characteristics of Insulation Paper Impregnated with Natural Ester and Mineral Oil

  • Hao, Jian;Zou, Run-Hao;Liao, Rui-Jin;Yang, Li-Jun;Liao, Qiang;Zhu, Meng-Zhao
    • Journal of Electrical Engineering and Technology
    • /
    • 제13권4호
    • /
    • pp.1682-1691
    • /
    • 2018
  • Natural ester is a suitable substitute for mineral oil and has been widely used in AC transformer in many countries. In order to further application of natural ester in direct current (DC) equipment, it is needed to investigate its long term insulation property under DC condition. In this paper, a thermal ageing experiment was conducted for both mineral oil-paper and natural ester-paper insulation. The DC breakdown and space charge characteristics of insulation paper impregnated with natural ester and mineral oil was compared. Results show that the resistivity of the paper immersed in natural ester and mineral oil both increase as the ageing goes on. While insulation paper impregnated with natural ester has higher resistivity and DC breakdown voltage than the paper impregnated with mineral oil. The DC breakdown voltage for the oil impregnated insulation paper being DC pre-stressing is higher than that without pre-stressing. The average DC breakdown field strength difference between the test with pre-stressing and without pre-stressing clearly shows that there is an apparent enhancement effect for the homo-charge injection on the DC breakdown.

식물성 절연유의 전력용 변압기 적용에 따른 문제점 고찰 및 전망 (Problem considerations and expectations in applying vegetable oil to power transformer)

  • 박현수;김지호;이향범
    • 한국정보통신설비학회:학술대회논문집
    • /
    • 한국정보통신설비학회 2009년도 정보통신설비 학술대회
    • /
    • pp.184-186
    • /
    • 2009
  • In past, transformer connection study was concentrated on efficiency improvement and life time broadening. But environmental side began to become important recently. In existing, quick transaction of mineral oil used to insulation oil of transformer is possibility to be difficult and causes environmental pollution in case of was outpoured and there is worry of fire occurrence. Accordingly, nonflammable performance becomes many interest in excellent vegetable oil because ignition point is high than mineral oil and environment friendly material. But, vegetable oil is cooling of transformer and insulation problem of insulating paper for cause of insulation oil special quality. Therefore, in this paper, special quality of vegetable oil that there are being a lot of mineral oil and the latest interest examined about problem and consideration item to be solved to analyzed comparison and applies vegetable oil to transformer for electric power.

  • PDF

Investigations on Eco Friendly Insulating Fluids from Rapeseed and Pongamia Pinnata Oils for Power Transformer Applications

  • Thanigaiselvan, R.;Raja, T. Sree Renga;Karthik, R.
    • Journal of Electrical Engineering and Technology
    • /
    • 제10권6호
    • /
    • pp.2348-2355
    • /
    • 2015
  • Transformer mineral oil which is normally hydrocarbon based is non- biodegradable and pollutes the environment in all aspects. Though vegetable oils are eco-friendly in nature and potentially could be used in transformers as a replacement for the mineral oil, there usage is restricted because of their oxidative instability. The present work focuses on using rapeseed oil and pongamia (pongamia pinnata) oil as effective alternatives for the traditional mineral oil in power transformer. The oxidative stability of the rapeseed oil and pongamia oil is increased by using combinations of the natural and synthetic anti-oxidants as additives. The parameters like breakdown voltage, viscosity, flash point, fire point are measured for the rapeseed oil and pongamia oil with and without the additives as per IEC and ASTM standards. The results shown encouraging changes in the parameter values and ensures the use of the oils as a potential alternative insulation in power transformers.

향 요법이 혈액투석 환자의 피부건조와 소양증에 미치는 효과 (Effect of Aromatherapy on Skin Xerosis and Pruritus in Patients Undergoing Maintenance Hemodialysis)

  • 하혜정
    • 대한간호학회지
    • /
    • 제29권6호
    • /
    • pp.1284-1293
    • /
    • 1999
  • This study was designed to investigate the effect of aromatherapy on skin xerosis and pruritus in patients undergoing maintenance hemodialysis. Twenty one subjects of this study were selected from St. Paul's Hosipital in Seoul. All the subjects were received the mineral oil massage at the arm without fistular three timesper week for 4 weeks. After 2 weeks period of wash-out, the subjects were received the aromatherapy of lavender and tea tree essence oil in the same way. This study was carried out from March 20 to June 13, 1998. Pruritus score, skin pH and stratum corneum hydration were measured before and after each treatment. But, biochemical parameters were measured before the treatment of the mineral oil massage, after the treatment of the mineral oil massage and the aromatherapy. Data of this study were analyzed by paired t-test, repeated measures ANOVA, Bonferroni multiple comparisons and Pearson correlation coefficient. The results were as follows ; 1. Pruritus score was significantly decreased after the aromatherapy, while no significant change after the treatment of the mineral oil massage. Therefore, there was a significant difference in the priritus score between the two treatments. 2. Stratum corneum hydration was significantly increased after the aromatherapy, while no significant change after the treatment of the mineral oil massage. Therefore, there was a significant difference in the stratum corneum hydration between the two treatments. 3. Skin pH was significantly increased after the treatment of the mineral oil massage, while no significant change after the aromatherapy. Therefore, there was no significant difference in the skin pH between the two treatments.4. After the aromatherapy, the serum calcium was significantly increased. Whereas the serum parathyroid hormone intact was significantly decreased compared with the treatment of the mineral oil massage. But the level of the serum Ca and PTH-intact were within the normal range. 5. Stratum corneum hydration was decreased corresponding to the duration of hemodialysis, while pruritus score and skin pH showed no change corresponding to the duration of hemodialysis and the age of the subjects. The correlation of pruritus score on skin pH, stratum corneum hydration and biochemical parameters was not significant. In conclusion, this findings indicate that aromatherapy may be effective in decreasing skin xerosis and pruritus score in uremic pruritus patients undergoing maintenance hemodialysis.

  • PDF

Renewable Low-viscosity Dielectrics Based on Vegetable Oil Methyl Esters

  • Yu, Hui;Yu, Ping;Luo, Yunbai
    • Journal of Electrical Engineering and Technology
    • /
    • 제12권2호
    • /
    • pp.820-829
    • /
    • 2017
  • Vegetable oil dielectrics have been used in transformers as green alternatives to mineral insulating oils for about twenty years, because of their advantages of non-toxic, biodegradability, and renewability. However, the viscosity of vegetable oils is more than 3 times of mineral oils, which means a poor heat dissipation capacity. To get low-viscosity dielectrics, transesterification and purification were performed to prepare vegetable oil methyl esters in this study. Electrical and physical properties were determined to investigate their potential as dielectrics. The results showed that the methyl ester products had good dielectric strengths, high water saturation and enough fire resistance. The viscosities (at $40^{\circ}C$) were 0.2 times less than FR3 fluid, and 0.7 times less than mineral oil, which indicated superior cooling capacity as we expected. With the assistance of 0.5 wt% pour point depressants, canola oil methyl ester exhibited the lowest pour point ($-26^{\circ}C$) among the products which was lower than FR3 fluid ($-21^{\circ}C$) and 25# mineral oil ($-23^{\circ}C$). Thus, canola oil methyl ester was the best candidate as a low-viscosity vegetable oil-based dielectric. The low-viscosity fluid could extend the service life of transformers by its better cooling capacity compared with nature ester dielectrics.

EFFECT OF ENGINE OIL ON EXHAUST EMISSIONS

  • Maxa, D.
    • 한국윤활학회:학술대회논문집
    • /
    • 한국윤활학회 2002년도 proceedings of the second asia international conference on tribology
    • /
    • pp.423-424
    • /
    • 2002
  • Amount of regulated emissions (CO, $NO_x$, HC), and emissions of some groups of organic substances (volatile hydrocarbons, polyaromatics, and aldehydes) were measured in the standard ECE 83 test on spark ignition engine of a passenger car. The influence of the engine oil composition (mineral or fully synthetic) was examined. For both engine oils, exhaust emissions were measured with fresh oil as well as used oil at the end of the oil drain interval. Unleaded petrol and CNG were used as fuels in all experiments performed. The main conclusion made from the tests is that polyaromatics is the only part of th ε exhaust emissions that was influenced with the nature of the engine oil. Effect on the other components of emissions (aldehydes and VOC) was negligible. Emissions of polyaromatics were almost twice higher for fresh mineral as for fresh fully synthetic oil. The amount of polyaromatics in the exhaust emissions increased slightly with mileage for fully synthetic and substantially more for mineral engine oil.

  • PDF