• Title/Summary/Keyword: Low-voltage Distribution System

Search Result 201, Processing Time 0.024 seconds

A New Measurement Method of the Ground Resistance Using a Low-pass Filter in Energized Substations (지역필터를 이용한 수변전실 접지저항의 새로운 측정방법)

  • Lee, Bok-Hui;Eom, Ju-Hong;Lee, Seung-Chil;Kim, Seong-Won;An, Chang-Hwan
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.50 no.8
    • /
    • pp.387-393
    • /
    • 2001
  • This paper describes an advanced measuring method and precise evaluation of the ground resistance for the grounding system of energized substations and power equipments. A grounding system of substations consists of all interconnected grounding connections of grounded conductors, neutral ground wires, underground conductors of distribution lines, cable shields, grounding terminals of equipments, and etc. It is very difficult to measure the accurate ground resistance of the grounding terminals of equipments, and etc. It is very difficult to measure the accurate ground resistance of the grounding system of high voltage energized substations because of harmonic components caused by switched power supplies or overloads. The conventional fall-of-potential method may be subject to big error if stray ground currents and potentials are present. In this work, to improve the precision in measurements of the ground resistance by eliminating the effects of harmonic components and stray currents and potentials, the investigations of the ground resistance measurement by using a low pass filter in a model energized grounding system were conducted. The accuracy of ground resistance mesurements was evaluated as a function of the ratio of the test signal to noise (S/N). The errors due to the proposed ground resistance measurement method were decreased with increasing S/N and were less than 5[%] as S/N is 10. The proposed ground resistance measurement method appears to be considerably more accurate than the conventional fall-of -potential method. It is allows cancellation of the parasitic resistance of energized grounding systems, to employ the measurement method that allows cancellation of the parasitic effects due to other circulating ground currents and ground potential rises in practical situations.

  • PDF

Lithium-ion Battery Energy Storage System for Power Quality Improvement in Electrical Propulsion Ships (전기추진선박의 전력품질 개선을 위한 리튬-이온 배터리 에너지저장시스템 적용)

  • Ku, Hyun-Keun;Seo, Hye-Rim;Kim, Jang-Mok
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.20 no.4
    • /
    • pp.351-355
    • /
    • 2015
  • This paper explained the application of a lithium-ion battery energy storage system to electric propulsion ships. The power distribution in electric propulsion ships has low power quality because of the variation in the power consumption of the propulsion motor. For proper operation of the ship, the power quality needs to be improved, and the battery energy storage system is used to solve power-quality problems. The simulation models of electric propulsion ship and battery energy storage systems are constructed on MATLAB/Simulink to verify the improvement in power quality. The proposed system is applied in various scenarios of the propulsion motor state. The power quality achieved by using the battery energy storage system in both voltage and frequency satisfies the standards set by IEC-60092/101.

Development of 460V/225A/50㎄ Contact System in Current Limiting Molded Case Circuit Breakers

  • Park, Young-Kil;Park, Chan-Kyo
    • KIEE International Transaction on Electrical Machinery and Energy Conversion Systems
    • /
    • v.3B no.4
    • /
    • pp.165-172
    • /
    • 2003
  • Low voltage circuit breakers are widely used in power distribution systems to interrupt fault current rapidly and to assure the reliability of the power supply. This paper is focused on understanding the interrupting capability, more specifically of the contacts and the arc runner, based on the shape of the contact system in the current molded case circuit breaker (hereafter MCCB). Moreover, in order to improve the interrupting capability of the circuit breaker, the estimation and analysis of the interrupting capability, based on the 3-D magnetic flux analysis, were developed. Furthermore, this paper also presents results of the estimation and analysis of the interrupting capability when applied to different model breakers. In addition, this paper analyzes the efficiency of the interrupting tests by forming false current paths consisting of a three-division cascade arc runner in the contact system. With regards to the interrupting test, there is a need to assure that the optimum design required to analyze the electromagnetic forces of the contact system generated by the current and flux density be present. Based on the results of this study, this paper presents both computational analysis and test results for the newly developed MCCB 460V/225A/50㎄ contact system.

Design of a 1 MVA HTS Transformer with Double Pancake Windings

  • Kim, Woo-Seok;Park, Kyeong-Dal;Joo, Hyeong-Gil;Han, Jin-Ho;Hong, Gye-Won;Park, Jungho;Heesuck Song;Kim, Sung-Hoon;Hahn, Song-yop
    • Progress in Superconductivity and Cryogenics
    • /
    • v.5 no.1
    • /
    • pp.48-51
    • /
    • 2003
  • A 1 MVA transformer with BSCCO-2223 high Tc superconducting (HTS) tapes was designed. The rated voltages of each sides of the transformer are 22.0 kV and 6.6 kV respectively. Double pancake HTS windings, which have advantages of insulations and distribution of high voltage, were adopted. Four HTS tapes were wound in parallel fer the windings of low voltage side. Each winding was composed of several double pancake windings made of four parallel conductors were transposed in order to distribute the currents equally in each conductor. A core of the transformer was designed as a shell type core made of laminated silicon steel plate and the core is separated with the windings by a cryostat with a room temperature bore. The operating temperature of HTS windings will be 65K with liquid nitrogen, and a cooling system using a cryocooler was proposed and designed conceptually. This HTS transformer is going to be manufactured in near future based on the design parameters presented in this paper.

Effects of distribution fault current limiting apparatus and emerging applications (배전급 전류제한 장치 효과 분석 및 도입 방안)

  • Lee, B.W.;Park, K.B.;Kim, H.M.;Oh, I.S.
    • Proceedings of the KIEE Conference
    • /
    • 2006.07c
    • /
    • pp.1540-1541
    • /
    • 2006
  • For limitation and interruption of short circuit currents from low voltage to extra high voltage applications, the electrical equipment including fuses and circuit breakers, are widely used today. But in order to anticipate increasing needs for effective and competitive device for limiting the growing fault current in electrical power systems, fault current limitation technologies and fault current limitation devices are widely introduced and investigated in these days. Fault current limiters are emerging electric equipment which is under development using various methods including superconducting fault current limiter, solid state fault current limiter, arc driving fault current limiters. And these various methods have some advantages and disadvantages to take into considerations In order to commercialize fault current limiters in the electrical networks, a lot of discussions should be given on the point that fault current limiting methods, need for fault current limiters, coordination with existing protective system, and field experience before commercialization. In this paper, recent trends of fault current limiting technologies will be reviewed and the key issues of superconducting fault current limiters will be dealt with. And finally, future applications of superconducting fault current limiters would be discussed.

  • PDF

Model Predictive Control of Bidirectional AC-DC Converter for Energy Storage System

  • Akter, Md. Parvez;Mekhilef, Saad;Tan, Nadia Mei Lin;Akagi, Hirofumi
    • Journal of Electrical Engineering and Technology
    • /
    • v.10 no.1
    • /
    • pp.165-175
    • /
    • 2015
  • Energy storage system has been widely applied in power distribution sectors as well as in renewable energy sources to ensure uninterruptible power supply. This paper presents a model predictive algorithm to control a bidirectional AC-DC converter, which is used in an energy storage system for power transferring between the three-phase AC voltage supply and energy storage devices. This model predictive control (MPC) algorithm utilizes the discrete behavior of the converter and predicts the future variables of the system by defining cost functions for all possible switching states. Subsequently, the switching state that corresponds to the minimum cost function is selected for the next sampling period for firing the switches of the AC-DC converter. The proposed model predictive control scheme of the AC-DC converter allows bidirectional power flow with instantaneous mode change capability and fast dynamic response. The performance of the MPC controlled bidirectional AC-DC converter is simulated with MATLAB/Simulink(R) and further verified with 3.0kW experimental prototypes. Both the simulation and experimental results show that, the AC-DC converter is operated with unity power factor, acceptable THD (3.3% during rectifier mode and 3.5% during inverter mode) level of AC current and very low DC voltage ripple. Moreover, an efficiency comparison is performed between the proposed MPC and conventional VOC-based PWM controller of the bidirectional AC-DC converter which ensures the effectiveness of MPC controller.

Improvement of Short Circuit Performance in 460[V]/400{A]/85(kA] Molded Case Circuit Breakers (460[V]/400[A]/85[kA] 배선용 차단기의 아크런너 변형을 통한 차단성능 향상)

  • Lee, Seung-Su;Her, June;Yoon, Jae-Hun;Kang, Seong-Hwa;Lim, Kee-Joe
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2009.06a
    • /
    • pp.394-394
    • /
    • 2009
  • Owing to the increasing number of intelligent homes(or called Smart home), the corresponding cost is much higher. Low voltage circuit breakers are widely used in the intelligent homes to interrupt fault current rapidly and to assure the reliability of the power supply. The distribution of magnetic field induced by arc current in the contact system of molded case circuit breaker(hereafter MCCB) depends on the shape, arrangement, and kinds of material of arc runner. This paper is focused on understanding the interrupting capability, more specifically of the arc runner, based on the shape of the contact system in the current MCCB. The magnetic driving force was calculated by using the flux densities induced by the arc current, which are obtained by three-dimensional finite element method. There is a need to assure that the optimum design required to analyze the electromagnetic forces of the contact system generated by current and the flux density be present. This is paper present our computational analysis on contact system in MCCB.

  • PDF

Development of 460[V]/225[A]/50[kA] Contact System in Current Limiting MCCB using an estimation and analysis method for the interrupting capability (차단성능 평가해석기법을 적용한 강자계 구동방식의 460[V]/225[A]/50[kA]급 한류형 MCCB 소호부 개발)

  • 최영길;박찬교
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.18 no.1
    • /
    • pp.78-84
    • /
    • 2004
  • Low voltage circuit breakers which interrupt rapidly and raise the reliability of power supply are widely used in power distribution systems. In the paper, it has been investigated how much interrupting capability is improved by correcting the shape of the contact system in molded case circuit breaker(below MCCB), especially contacts and arc runner. Prior to the interrupting testing, it is necessary for the optimum design tc analyze electromagnetic forces on the contact system generated by current and flux density. This paper presents both our computational analysis and test results on contact system in MCCB

Development of Contact System in 460[V]/225[A]/50[kA] Molded Case Circuit Breaker (460[V]/225[A]/50[kA] 한류형 배선용 차단기 소호부 개발)

  • 최영길;구태근;이광식
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.16 no.6
    • /
    • pp.137-144
    • /
    • 2002
  • Low voltage circuit breakers which interrupt rapidly and raise the reliability of power supply are widely used in power distribution systems. In the paper, it has been investigated how much interrupting capability is improved by correcting the shape of the contact system in molded case circuit breaker(below MCCB), especially arc runner. Prior to the interrupting testing, it is necessary for the optimum design to analyze electromagnetic forces on the contact system generated by current and flux density. This paper presents both our computational analysis and test results on contact system in MCCB.

Study on Measurement Method of Dielectric Recovery Voltage to analysis Dielectric Recovery Characteristic of Molded Case Circuit Breaker (저압 배선용차단기 절연회복특성 파악을 위한 절연회복전압 측정기법 연구)

  • Song, Tae-Hun;Cho, Young-Maan;Ko, Kwang-Cheol
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.29 no.8
    • /
    • pp.49-54
    • /
    • 2015
  • Molded Circucit Breaker(MCCB) is a most widely used device to protect loads from the over-current in low power level distribution system. When the MCCB interrupts the over-current, the arc discharge occurred between fixed contact and moving contact to create hot gas. By the Lorentz force due to arc current, the occurred arc is bent to the grids. The grids extend and cool and divide it for arc extinguish. In the majority cases, the MCCB protects loads by interrupting the over-current successfully but in some cases the re-ignition is occurred by hot-gas created during process of interruption. The re-ignition arises when the recovery voltage(RV) is more higher than the recovery strength between contacts and it leads to interruption fault. Therefore to find out the dielectric recovery characteristics of protecting device has a great importance for preventing interruption fault. In this paper, we studies measurement method of the dielectric recovery characteristics considering inherent attribute of the MCCB. To measure the dielectric recovery characteristic of MCCB, we makes an experiment circuit for applying the over-current and the randomly recovery voltage. The measurement methode to find out the dielectric recovery voltage of the MCCB was established and the result was based on experiment results.