• Title/Summary/Keyword: Low voltage wiring

Search Result 32, Processing Time 0.028 seconds

A Study on Dynamic Characteristics of EFPCD for Conductor Breaks in Low Voltage Wiring (저압배선 선로의 단선사고 발생시 전기화재예방 제어장치(EFPCD)의 동작 특성에 관한 연구)

  • 이상호;신미영;이경호
    • Fire Science and Engineering
    • /
    • v.18 no.3
    • /
    • pp.103-107
    • /
    • 2004
  • Recently. the spark and the overheat due to in the conductor breaks have been the major causes of electrical fire in low voltage wiring. Also, because in these cases the current is a surge one, the losses and faults of a communication, a home appliances, a computer and a measuring instrument may occur. Especially, in such cases, we are very difficult to detect the condition of the conductor breaks. In this paper, we have developed an auxiliary control device, the electrical fire prevention control device (EFPCD), of an earth leakage breaker (ELB). And we can prevent the electrical fire caused by the spark and the overheat occurring in the conductor breaks with the EFPCD.

A Study on the High Speed Interruption of Parallel Arcing (병렬아크의 고속차단에 관한 연구)

  • Kil, Gyung-Suk;Ji, Hong-Keun;Park, Dae-Won;Kim, Il-Kwon;Kim, Young-Il;Cho, Young-Jin
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.22 no.12
    • /
    • pp.95-100
    • /
    • 2008
  • Conventional Earth Leakage Circuit Breakers (ELCBs) have defects of a breaking failure or a long breaking-time against parallel arc current. In this paper, breaking characteristics of conventional ELCBs were analyzed by simulation of parallel arc in a low-voltage indoor wiring system, and an air-core current sensor and a signal converter being most available for parallel arc detection were developed and applied to a conventional ELCB. The proposed tripped the ELCB regardless of the location of parallel arc. The breaking-time was in ranges of $1.74{\sim}8.3[ms]$ depending on the phase of arc generation, which is about 5 times as fast as conventional ELCBs with the breaking-time of 50[ms].

Electric Safety Protection Device of High Speed for Incapable Operation of ELB and MCCB Using the Low Voltage Distribution Line (저압 배전선로의 누전 및 배선용 차단기의 오동작 방지를 위한 고속형 전기안전 보호장치)

  • Kwak, Dong-Kurl;Jung, Do-Young
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.56 no.11
    • /
    • pp.1925-1929
    • /
    • 2007
  • This paper is studied on a novel Electric Safety Protection Device (ESPD) of high speed for incapable operation of Earth Leakage Circuit Breaker (ELB) and Molded_case Circuit Breaker (MCCB) using the low voltage distribution line. The major causes of electrical fire are classified to short circuit fault, overload fault, electric leakage and electric contact failure. The occurrence factor of the fire is electric arc or spark accompanied with electrical faults. Residual Current Protective Device (RCD), that is ELB and MCCB, of high sensitivity type used at low voltage wiring cuts off earth leakage and overload, but the RCD can't cut off electric arc or spark to be a major factor of electrical fire. As the RCDs which are applied low voltage distribution panel are prescribed to rated breaking time about 30[ms] (KS C 4613), the RCDs can't perceive to the periodic electric arc or spark of more short wavelength level. To be improved on such problem, this research development is proposed to a novel ESPD of high speed to trip of distribution line on electric arc or spark due to electrical fire. Some experimental results of the proposed ESPD are confirmed to the validity of the analytical results.

A Study on Series Arc Detection Using Band-pass Filters (대역통과필터를 이용한 직렬아크 검출에 관한 연구)

  • Kim, Il-Kwon;Kim, Jin-Su;Park, Keon-Woo;Kim, Kwang-Soon;Kim, Young-Il
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.1345-1347
    • /
    • 2008
  • This paper described a method of determining whether arcing is present in a low-voltage wiring system. We simulated the series arcing that generated in electrical loads and fabricated a arc detection module which can discriminate between normal and arcing state. The module consists of a high-pass filter with a low cut-off frequency of 3 kHz to attenuate power frequency voltage and an active band-pass filter with a frequency of 4 kHz ${\sim}$ 8 kHz to detect series arc signals only. We tested an Incandescent lamp that was controlled by a dimmer and analysed. The module consists of a high-pass filter with a low cut-off frequency of 3 kHz to attenuate power frequency voltage by 80 dB and an active band-pass filter with a frequency of 4 kHz to detect series arc signals only. From the experimental results, we could detect series arc signals without an influence of non-linear loads.

  • PDF

Comparison of Traction Motor design and characteristics for battery driven hybrid tram (무가선 트램용 추진 전동기 설계 및 특성 비교)

  • Ham, Sang-Hwan;Kim, Kwang-Soo;Kim, Mi-Jung;Lee, Hyung-Woo;Lee, Ju
    • Proceedings of the KSR Conference
    • /
    • 2010.06a
    • /
    • pp.1383-1388
    • /
    • 2010
  • The latest generation of tram is low-floor design, various nations in europe and japan have developed battery driven hybrid trams that combine battery and wiring. Battery driven tram system is achieved by contactless power supply system, thus system is needed high efficiency, high power and low weight traction motor for maximization of energy efficiency. Research from abroad is still in induction motor(IM) application, and it is not meet the efficiency and the power per unit volume in IPMSM. In this paper, we design compare IM and IPMSM to apply battery driven tram, and then compare these motors. To design the motor, we estimate the loading condition at first. Loading condition includes rolling resistance, air-drag resistance, and slope resistance. Based on the loading condition by estimation, we determine the power and compute rated voltage and rated current. In this paper, voltage is limited by battery voltage level. As a result, volume about IM is 1.98 times bigger than IPMSM under same condition. Even though IPMSM is bigger than IM in power density per volume, we consider more factors for actual application because there are demagnetization of permanent magnet in IPMSM and so on by external environment conditions.

  • PDF

A Study on the Detection Algorithm of Series Arc Signals in Air Conditioners (에어컨에서 직렬아크검출 알고리즘에 관한 연구)

  • Ji, Hong-Keun;Choi, Sung-Kuk;Jung, Kwang-Seok;Park, Dae-Won;Kil, Gyung-Suk
    • Proceedings of the KSR Conference
    • /
    • 2009.05a
    • /
    • pp.1970-1976
    • /
    • 2009
  • This paper describes a series arc detection algorithm in a low-voltage wiring system. We designed and fabricated an arc detection circuit which consists of a high-pass filter with the low cut-off frequency of 170 kHz to attenuate power frequency. The series arcing phenomena was simulated by an arc generator specified in UL1699. In the experiment, various loads such as resistive loads, resistive loads controlled by a dimmer, and vacuum cleaners were used. Whether the signal is arc or noise is discriminated by pulse counts and periodicity of the detected signal.

  • PDF

Detection of Series Arc Signal (직렬아크신호의 검출)

  • Ji, Hong-Keun;Park, Dae-Won;Kim, Il-Kwon;Kil, Gyung-Suk
    • Proceedings of the KSR Conference
    • /
    • 2008.11b
    • /
    • pp.225-229
    • /
    • 2008
  • This paper describes a series arc detection algorithm in a low-voltage wiring system. We designed and fabricated an arc detection circuit which consists of a high-pass filter with the low cut-off frequency of 3 kHz to attenuate power frequency. The series arcing phenomena was simulated by an arc generator specified in UL1699. In the experiment, various loads such as resistive loads, resistive loads controlled by a dimmer, and vacuum cleaners were used. Whether the signal is arc or noise is discriminated by pulse counts and periodicity of the detected signal.

  • PDF

REffects of Surge Protective Devices with Respect to Types of System Grounding and Wiring Methods (전원계통의 접지방식 및 배선방식에 따른 서지보호기의 효과)

  • 이수봉;이복희;길형준
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.18 no.2
    • /
    • pp.90-99
    • /
    • 2004
  • High speed info-communications equipment are required with development of highly information-oriented society, the intelligent industrial facilities and social systems such as administrative, financial and traffic systems, are gradually becoming to automation, which are composed of the integrated circuits and micro-semiconductors, remote control and operation. Thus modern micro-electronic circuits can frequently be damaged by lightning surge. The protection of electronic circuits from lightning overvoltages is concentrated very interesting. In this paper, for the purpose of providing the effective protection method of electronic devices such micro-computers from lightning surges in a residential building, the protection effect of surge protective devices according to types of system groundings were experimentally analyzed. Also the effective installation method of surge protective devices was examined and proposed. The installation of SPDs in retrofits was a high remnant voltage across the protected device owing to the inductance in the long wires to the SPDs. Finally the method of installing the SPD by twisted pain wires is remarkably effective for fast rising transient overvoltages.

A Study on Electrical Fire Disaster Prevention Device used in Double Circuit Break (고정밀 전류센서를 이용한 이중 차단용 전기화재 방재장치에 관한 연구)

  • Park, Dong-Pil;Kwak, Dong-Kurl;Jung, Do-Young;Kim, Choon-Sam;Shin, Ho-Joon
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.2102-2103
    • /
    • 2008
  • The major causes of electrical fire are classified to short circuit fault, overload fault, electric leakage and electric contact failure. The occurrence factor of the fire is electric arc or spark accompanied with electrical faults. Residual Current Protective Device(RCD) of high sensitivity type used at low voltage wiring cuts off earth leakage and overload, but the RCD can't cut off electric arc or spark to be a major factor of electrical fire. As the RCDs which are applied low voltage distribution panel are prescribed to rated breaking time about 30[ms](KS C 4613), the RCDs can't perceive to the periodic electric arc or spark of more short wavelength level. To be improved on such problem, this paper is proposed to a electrical fire disaster prevention device(EFDPD) for a RCD trip or a self circuit-breaking function on electric arc or spark due to electrical fire. Some experimental results of the proposed apparatus is confirmed to the validity of the analytical results.

  • PDF

Analysis of Electrical Equipment and Work Environment for Domestic Small-Scale Construction Site (국내 소규모 건설현장의 전기설비 및 작업환경 분석)

  • Kim, Doo-Hyun;Hwang, Dong-Kyu;Kim, Sung-Chul;Kang, Shin-Uk;Choi, Sang-Won
    • Journal of the Korean Society of Safety
    • /
    • v.29 no.4
    • /
    • pp.42-47
    • /
    • 2014
  • This paper is aimed to investigate and analyze of characteristic for electrical equipment and work environment for the small-scale site. In order to investigate and analyze electrical equipment and work environment for preventing electric shock disaster in construction sites, 50 small-scale construction sites and 12 large-scale construction sites are selected. This paper completed site investigations of low-voltage equipment and the portable electric machine and equipment in 12 large-scale construction sites and 50 small-scale construction sites. The findings were about the electric shock environment relevant to the ground-relevant equipment, the panel board, the protection tools, the sockets, the temporary wiring system, the portable and movable electric machines and equipments in small-scale construction sites. Finally, this study analyzed the domestic and foreign relevant standards and regulations and these findings can be utilized as educational data warning electric shock risk caused by electric equipment in small-scale construction site.