• Title/Summary/Keyword: Liquid breakdown

Search Result 175, Processing Time 0.029 seconds

A Study on Life Characteristics of Insulator for Stability of a HTS equipment (고온초전도 기기의 신뢰성 확보를 위한 고려한 절연재료의 수명 특성 연구)

  • Baek, Seung-Myeong;Kim, Hyun-Hee;Kim, Sang-Hyun
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.965-966
    • /
    • 2007
  • For practical electrical insulation design of high temperature superconducting (HTS) power apparatuses, knowledge of the dielectric behavior of insulators in cryogenic liquid such as liquid nitrogen ($LN_2$) is essential. So in this paper, we discussed experimental investigations of breakdown and V-t characteristics of several insulators such as Kapton and glass fiber reinforced plastic (GFRP) that are candidates of insulator for HTS apparatus in cryogenic liquid. And we investigated the degradation of these insulation samples after breakdown with the microscope and SEM photograph. Moreover, survival and hazard analysis was performed.

  • PDF

Insulation Characteristics of the Model Cable for 22.9 kV Class HTS Power Cable

  • Kim, Hae-Jong;Seong, Ki-Chul;Cho, Jeon-Wook;Kwag, Dong-Soon;Cheon, Hyeon-Gweon;Kim, Sang-Hyun
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2005.07a
    • /
    • pp.542-543
    • /
    • 2005
  • In this paper, describes the fabrication and dielectric insulation characteristics experimental results of the model cable for the 22.9kV class HTS power cable. The model cable were tested with partial discharge(PD), AC and impulse withstand voltage in liquid nitrogen($LN_2$) and liquid nitrogen pressure. In these test results, PD inception stress and AC, impulse breakdown strength increase as the pressure of the liquid nitrogen increases.

  • PDF

Adhesion properties and Breakdown behaviors of LSR Interface (LSR 계면의 접착특성 및 절연파괴거동)

  • Yoon, Seung-Hoon;Nam, Jin-Ho;Lee, Gun-Ju;Choi, Soo-Geol;Shin, Doo-Sung;Ji, Eung-Seo
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2002.11a
    • /
    • pp.232-235
    • /
    • 2002
  • Recently developed liquid silicone rubber (LSR) can be cured by platinum catalyzed additional hydrosilylation mechanism and has the advantage of no byproduct compared to traditional millable peroxide curing silicone rubber. We investigated the characteristics of dielectric breakdown of silicone rubber and adhesion properties between semi-conductive LSR and insulating LSR for high voltage application of pre-molded joint (PMJ). In order to understand the dielectric breakdown characteristics, we used the sheet samples and the paired type rogowski insert electrode system. The breakdown strength and adhesion strength of LSR (E-3) were superior to those of several silicone rubbers. Adhesion strength could be improved by curing at high temperature without post-curing process or enhanced by post-curing process. When LSR (E-3) was cured at $(150^{\circ}C{\times}10min$ semi-conductive )${\times}$ ($175^{\circ}C{\times}10min$ insulation), it showed the high breakdown strength with low standard deviation, and good adhesion strength. In this results, we could apply this process to the fabrication of PMJ without post-curing.

  • PDF

The Effects of Gap Length and Tip Radius Influenced in Breakdown of Mineral Based Insulating Oil (광유의 절연파괴에 미치는 전극간격 및 침전극 곡률반경의 영향)

  • 이종섭;신태수;이운용;박영국;강성화;임기조
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 1997.11a
    • /
    • pp.254-257
    • /
    • 1997
  • In this paper, we investigated the effects of gap length and tip radius influenced in breakdown of mineral based insulation oil Electrode system was needle-plane geometry It is to model conductive extrusions in oil filled electrical power apparatus. The tip radius of needle electrode was 5, 10, 20 and 25${\mu}{\textrm}{m}$, respectively. We measured breakdown voltage for each of tip radius with increasing electrode gap, 2mm to 12mm. It was calculated electrical breakdown strength at tip using Mason\`s equation from breakdown voltage As gap lenght increased. breakdown strength increased linearly. But, as tip radius of needle increased, breakdown strength decreased exponentially. It can be explained by tole phenomenon that electron is easily injected, as tip radius increases, and effective work function decreases. When appling DC voltage. breakdown 7tr7ilgtll was higher wheal polarity of needle was negative than positive. It is because of the space charge effect ill accordance with the influence of liquid motion.

  • PDF

The Influence of Gap Length and Tip Radius on Breakdown of Electrical Insulating Oil (전기절연유의 절연파괴에 미치는 전극간격 및 곡률반경의 영향)

  • Kang, Seong-Hwa;Chae, Hong-In;Lee, Jong-Pil;Lim, Kee-Joe
    • Journal of the Korean Society of Safety
    • /
    • v.19 no.1
    • /
    • pp.56-59
    • /
    • 2004
  • In this paper, we investigated the influence of gap length and tip radius on breakdown of mineral based insulation oil. Applied voltages were DC and AC voltage. Electrode system was needle-plane structure. The tip radius of needle electrode was 5, 10, 20 and 25${\mu}m$, respectively. We measured breakdown voltage for each of tip radius with increasing electrode gap, 2mm to 12mm. Electric breakdown strength at tip was calculated using Mason's equation contained geometric figure. As gap length increased, breakdown strength increased linearly. But, as tip radius of needle increased, breakdown strength decreased exponentially. It can be explained by the phenomenon that electron is easily injected, as tip radius increases, and effective work function decreases. When appling DC voltage, breakdown strength was higher when polarity of needle was negative than positive. It is because of the space charge effect in accordance with the influence of liquid motion.

Breakdown Characteristics of Insulators for a Resistor Type HTS Fault Current Limiter (저항형 고온초전도 한류기용 절연체의 절연 특성)

  • 백승명;류엔반둥;김상현
    • Progress in Superconductivity and Cryogenics
    • /
    • v.6 no.1
    • /
    • pp.48-52
    • /
    • 2004
  • Breakdown characteristics of insulator-liquid nitrogen ($LN_2$) composite insulation for resistor type High $T_c$/ superconducting fault current limiter (HTSFCL) under ac and impulse voltage in $LN_2$ has been studied using model electrode systems. Electrodes for model electrode systems were made of SUS 304 contacted fiberglass reinforced plastic (FRP) and Au coated sapphire. The breakdown characteristics of model electrode systems were investigated experimentally for FRP thickness ranging from 1 mm to 5 mm. surface distance ranging from 2.5 mm to 7 mm and electrode gap ranging from 1 to 5 mm. The experimental data suggested that the breakdown voltage of model electrode systems in $LN_2$ is highly dependent on the surface distance, electrode gap as well as on the FRP thickness. Also, we had observed discharge traces and puncture due to high-voltage 60-Hz AC stress.

Breakdown, V-t and Degradation Characteristics of Insulation in Liquid Nitrogen for HTS Transformer (고온초전도 변압기를 위한 액체질소 중 절연 파괴, V-t. 열화 특성)

  • Nguyen, Van-Dung;Joung, Jong-Man;Baek, Seung-Myeong;Lee, Chang-Hwa;Suck, Song-Hee;Kim, Sang-Hyun
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.53 no.6
    • /
    • pp.316-323
    • /
    • 2004
  • HTS transformer is one of the most promising devices to supply enough electric energy for quick increase consumption. However, for practical design of the HTS transformer, it is necessary to establish the research on breakdown, V-t characteristics, degradation, and so on. In this paper, we discussed breakdown characteristics and V-t characteristics of polyimide/L$N_2$ and glass fiber reinforced plastic/$LN_2$ composite insulations. These composite insulations have been used as turn-to-turn and layer-to-layer insulations for HTS transformer respectively, Moreover, we investigated the degradation of these insulation samples after breakdown using microscope and SEM photograph.

Breakdown Characteristics of Insulation Materials for a Termination of Power Transmission Class HTS Cable

  • Kwag Dong-Soon;Cheon Hyeon-Gweon;Choi Jae-Hyeong;Kim Sang-Hyun
    • Progress in Superconductivity and Cryogenics
    • /
    • v.8 no.2
    • /
    • pp.37-42
    • /
    • 2006
  • A research on several characteristics such as volume breakdown and surface discharge of insulators for a termination of power transmission class HTS cable was performed. We investigated the surface discharge of glass fiber reinforced plastic (GFRP) under air, cryogenic nitrogen gas and nitrogen gas media. The breakdown characteristics of these media were studied. Experimental results revealed that flashover voltage greatly depends on pressure, temperature, the kinds of insulating media and voltages, but it is slightly affected by shape and material of electrode. The breakdown voltage of liquid nitrogen, cryogenic nitrogen gas and nitrogen gas deeply depends on the shape and dimension of electrode, kinds of voltages and pressure. Moreover, the breakdown voltage of cryogenic nitrogen gas and flashover voltage of GFRP in the cryogenic nitrogen gas is also influenced by temperature and vapour-mist density of the gas.

Experimental Study of Breakdown Pressure, Acoustic Emission, and Crack Morphology in Liquid CO2 Fracturing (액체 이산화탄소 파쇄법의 파쇄 압력, 음향 방출, 균열 형상에 관한 실험적 연구)

  • Ha, Seong Jun;Yun, Tae Sup
    • Tunnel and Underground Space
    • /
    • v.29 no.3
    • /
    • pp.157-171
    • /
    • 2019
  • The fracturing by liquid carbon dioxide ($LCO_2$) as a fracking fluid has been an alternative to mitigate the environmental issues often caused by the conventional hydraulic fracking since it facilitates the fluid permeation owing to its low viscosity. This study presents how $LCO_2$ injection influences the breakdown pressure, acoustic emission, and fracture morphology. Three fracturing fluids such as $LCO_2$, water, and oil are injected with different pressurization rate to the synthetic and porous mortar specimens. Also, the shale which has been a major target formation in conventional fracking practices is also tested to examine the failure characteristics. The results show that $LCO_2$ injection induces more tortuous and undulated fractures, and particularly the larger fractures are developed in cases of shale specimen. On the other hand, the relationship between the fracturing fluids and the breakdown pressure shows opposite tendency in the tests of mortar and shale specimens.

Electrical Insulation Characteristics of Insulators in Cryogenic Liquid for a HTS Apparatus (고온초전도 기기를 위한 극저온 액체 중 절연물의 전기적 특성)

  • Baek, Seung-Myeong;Kwag, Dong-Soon;Cheon, Hyeon-Gweon;Choi, Jae-Hyeong;Kim, Sang-Hyun;Kim, Hyun-Hee
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2006.06a
    • /
    • pp.263-264
    • /
    • 2006
  • For practical electrical insulation design of high temperature superconducting (HTS) power apparatuses, knowledge of the dielectric behavior of insulators in cryogenic liquid such as liquid nitrogen ($LN_2$) is essential. So in this paper, we discussed experimental investigations of breakdown and V-t characteristics of several insulators such as Kapton and glass fiber reinforced plastic (GFRP) that are candidates of insulator for HTS apparatus in cryogenic liquid. And we investigated the degradation of these insulation samples after breakdown with the microscope and SEM photograph. Moreover, survival and hazard analysis were performed.

  • PDF