• Title/Summary/Keyword: Liquid Pool Fire

Search Result 29, Processing Time 0.025 seconds

Extinguishing Characteristics of Liquid Pool Eire by Water Mist Containing Sodium Salt (나트륨 염이 첨가된 미분무수의 액체 pool fire소화특성)

  • Park Jae-Man;Shin Chang-Sub
    • Fire Science and Engineering
    • /
    • v.19 no.3 s.59
    • /
    • pp.13-19
    • /
    • 2005
  • An experimental study is presented for extinguishing characteristics of liquid fuel fire by water mist containing sodium acetate trihydrate. To evaluate the extinguishing performance of water mist containing an additive, the evaporation characteristics of a water droplet on a heated surface was examined. The evaporation process was recorded by a charge-coupled-device camera. Also, small-scale extinguishing tests were conducted for n-heptane pool fire in ventilated space to measure flame temperature variation. The average evaporation rate of a water droplet containing an additive was lower than that of a pure water droplet at a given surface temperature due to the precipitation of salt in the liquid-film and change of surface tension. In case of using an additive, the flame temperature was lower than that of pure water at a given discharge pressure and it was because the momentum of a water droplet containing an additive was increased reducing flame size. And also dissociated metal atoms, sodium, were reacted as a scavenger of the major radical species OH^-,\;H^+$ which were generated for combustion process. Moreover, at a high pressure of 4MPa, the fire was extinguished through blowing effect as well as primary extinguishing mechanisms.

Performance of Fire Extinguishing of Water Mist Nozzle for Power Transformer Fire Scenario (주 변압기실 화재시나리오에 적용한 미세물분무 노즐의 소화성능)

  • Lee, Kyoung-Duck
    • Journal of the Korean Society of Safety
    • /
    • v.21 no.6 s.78
    • /
    • pp.46-54
    • /
    • 2006
  • Fire extinguishing experiment was conducted with water mist nozzle in case of the pool fire, cascade fire and spray fire on flammable liquid of class B whether water mist system can be effective system for power transformer fire scenario. In the event of a pool fire, flow rate and time to extinguish was inclined to be increased according to the obstruction rate of ignition space. Furthermore, the performance of fire extinguishing depended upon the spraying angle of the nozzles. In case of cascade fire, the effect of extinguishment was began to show from a combustion pan filled with fuel and fuel flowing plate later on.

Application Study of Design Fire Curves for Liquid Pool Fires in a Compartment (구획실 내 액체 풀화재에 대한 디자인 화재곡선 적용 연구)

  • Baek, Bitna;Oh, Chang Bo;Lee, Eui Ju;Nam, Dong-Gun
    • Fire Science and Engineering
    • /
    • v.31 no.4
    • /
    • pp.43-51
    • /
    • 2017
  • In this study, new design fire curves were suggested for the utilization in fire simulations. Numerical simulations with the Fire Dynamics Simulator (FDS) were performed for the n-octane and n-heptane pool fires in the ISO 9705 compartment to evaluate the prediction performance of the previous quadratic, exponential design fire curves and newly suggested ones. The numerical results were compared with the experimental temperature and concentrations of $O_2$ and $CO_2$. The numerical results with the previous quadratic and exponential curves showed slow increase and decrease trend than experiments. However, the numerical results with the newly suggested 2 design fire curves showed more similar variation trend in temperature, $O_2$ and $CO_2$ concentrations than the quadratic and exponential curves. It was found that the newly suggested design fire curves can be possibly used in the numerical simulation of fires in a practical respect.

Numerical Study on Atmospheric Dispersion and Fire Possibility in Toluene Leakage (톨루엔 누출 시 대기확산 및 화재가능성에 관한 수치해석 연구)

  • Ko, Jae Sun;Kim, Joo-Seok
    • Fire Science and Engineering
    • /
    • v.31 no.3
    • /
    • pp.1-10
    • /
    • 2017
  • This study examined the risk of accidents when handling hazardous materials in hazardous materials storage facilities without safety facilities. In the case of illegal dangerous cargo containers, the burning rate is very fast in the case of fire, which leads to explosions, that are damaging and difficult to control. In addition, accidents that occur in flammable liquid hazardous materials are caused mostly by accidents that occur in the space due to leakage. Therefore, the variables that affect these accidents were derived and the influence of these variables was investigated. Numerical and computational fluid dynamics programs were used to obtain the following final results. First, when a flammable liquid leaks into a specific space, it is influenced by temperature and relative humidity until a certain concentration (lower limit of combustion) is reached. In the case of temperature, it was found that the reaching time was shorter than the flash point In addition, the effect of variables on pool fire accidents of leakage tanks is somewhat different, but the variables that have the largest influence are the wind speed. Therefore, it is expected that the results of this study will be used as basic data for similar numerical analysis and it will provide useful numerical information about the accidental leakage of hazardous materials under various research conditions.

Extinguishment of Liquid Fuel Fire by Water Mist Containing Additives

  • Park, Jae-Man;Won, Jung-Il;Shin, Chang-Sub
    • International Journal of Safety
    • /
    • v.4 no.2
    • /
    • pp.24-29
    • /
    • 2005
  • An experimental study was presented for extinguishing characteristics of liquid fuel fire by water mist($Dv_{0.99}{\leq}200{\mu}m$) containing potassium acetate and sodium acetate trihydrate. To evaluate the extinguishing performance of water mist containing additives, the evaporation characteristics of a water droplet on a heated surface was examined. The evaporation process was recorded by a charge-coupled-device camera. Also, small-scale extinguishing tests were conducted for n-heptane pool fire in ventilated space. During the experiments, flame temperatures were measured, and concentrations of oxygen and carbon monoxide were analyzed by a combustion gas analyzer. The average evaporation rate of water droplet containing additives was lower than that of pure water at a given surface temperature and decreased with the concentration increase due to the precipitation of salt in the liquid-film and change of surface tension. In case of using additives, the fire extinguishing times was shorter than that of pure water at a given discharge pressure and it was because the momentum of a water droplet containing additives was increased. And also dissociated metal atoms, potassium or sodium, were reacted as a scavenger of the major radical species OH, H which were generated for combustion process. Moreover, at a high pressure of 4 MPa, the fire was extinguished through blowing effect as well as primary extinguishing mechanisms.

A Study on the Probability of BLEVE of Above-ground LP Gas Storage Tanks Exposed to External Fire (지상식 LPG 저장탱크의 외부화재에 의한 BLEVE 가능성 해석)

  • Lee Seung-Lim;Lee Young-Soon
    • Journal of the Korean Institute of Gas
    • /
    • v.7 no.1 s.18
    • /
    • pp.19-23
    • /
    • 2003
  • The purpose of this thesis is to investigate the BLEVE probability of LP gas storage tanks which are relatively more dangerous, by the deductive calculating method using the results of Birk's pilot tank test and the required heat capacity of BLEVE. The result that BLEVEs can occur in only above 43.68 percent of liquid filling level under $600^{\circ}C$ of tank pate temperature and $53^{\circ}C$ of inner liquid temperature, was obtained and will be useful for preventing the BLEVE of LP gas storage tanks in fire sites. In addition, this research showed conditions of external leak and fire causing BLEVE, based on 15ton capacity of LP gas tank which has the same specifications as those in Puchon LP gas filling station accident. The result of the calculation is that the minimum pool fire conditions of BLEVE are above 7.2mm equivalent diameter under a liquid release condition and above 17.6mm equivalent diameter under a two-phase release condition. In the end, the result of calculating the pool size corresponding the above conditions using EFFECTS version 2.1, concludes that a minimum of 3.3 meters of diameter and 10.4 meters of height should be needed for BLEVE outbreak.

  • PDF

Measurements of Flame Temperature and Radiation Heat Flux from Pool Fire with Petroleum Diesel Fuel (디젤연료의 액면화재로부터 화염온도와 복사열 측정)

  • Lim, Woo-Sub;Choi, Jae-Wook
    • Fire Science and Engineering
    • /
    • v.21 no.3
    • /
    • pp.78-83
    • /
    • 2007
  • Diesel, a kind of petroleum, which is used in vehicles, vessels, boilers etc causes great damage when a fire happens, because it has higher caloric value than gasoline or kerosene has at burning. Therefore, pool fire experiment was carried using diesel which is sold on the gas station and radiation heat flux that occurs from flame and inner temperature of flame at burning was estimated. The maximum instantaneous flame temperature of diesel was more than $900^{\circ}C$, and the average of maximum flame temperature was $800^{\circ}C$ which occurred at 0.5 H/D distance from the surface of inflammable liquid, the distance has more long that has the lower the temperature of flame. In case of radiation heat flux, it grew to vary according to the size and amount of sample. When the size of a container for experiment was 0.5 m and sample layer was 13 mm and 20 mm, the radiant heat was 92.29 kW and 117.43 kW each. When the container was 1.0 m, it was 364.35 kW and 405.88 kW each.

A Study on Mitigating Accidents for Liquid Hydrogen (액체수소 사고피해 완화기술에 대한 연구)

  • Jo, Young-Do;Kim, Jin-Jun
    • Journal of the Korean Institute of Gas
    • /
    • v.16 no.6
    • /
    • pp.29-33
    • /
    • 2012
  • This paper is an attempt to give a concise overview of the state-of-the-art in the recent liquid hydrogen safety researches with unwanted event progress. The vessel of liquified hydrogen may fail and liquid hydrogen spilled. The hydrogen will immediately start to evaporate above a pool and make a hydrogen cloud. The cloud will disperse and can produce a vapor cloud explosion. The vessel containing the liquid hydrogen may not be able to cope with the boil-off due to heat influx, especially in case of a fire, and a BLEVE may occur. In equipment where it exists as compressed gas, a leak generates a jet of gas that can self-ignite immediately or after a short delay and produce a jet flame, or in case it ignites at a source a certain distance from the leak (delayed ignition), a flash fire occurs in the open and with confinement a deflagration or even detonation may develop. The up-to-date knowledge in these events, recent progress and future research are discussed in brief.

Extinguishing Charactristics of Water Mist by Discharge Properties (방사특성 변화에 따른 미세물분무의 소화특성)

  • 이경덕;신창섭
    • Fire Science and Engineering
    • /
    • v.15 no.4
    • /
    • pp.41-48
    • /
    • 2001
  • Halogen-based fire suppressing agents have been the most effective fire suppressants and widely used for flammable liquid and electric fire. However they have environmental problems causing stratospheric ozone depletion and globe warming. As a substitution of halon, fire suppression system using fine water mist is one of an effective fire suppressant. Suffocating and cooling effects of water mist are increased by the evaporation characteristics because it has droplet size less than 1,000 $\mu{m}$ and very large surface area. In this study, the extinguishing characteristics of fire was measured with changing of water mist droplet size, flow density; discharge pressure, and fire size. As a result, the extinguishing time of pool fire was shortened with the increase of flow density and in case of low flow density less than 0.5$\pm$0.05 ml/$\textrm{cm}^2$ . min, the extinguishing time was shortened with the increase of droplet size. The cycling discharge was effective for $\eta$-heptane pool fire, and total amount of water mist required to extinguish fire was reduced to a quarter compare with continuous discharge.

  • PDF

Evaluation of Modified Design Fire Curves for Liquid Pool Fires Using the FDS and CFAST (FDS와 CFAST를 이용한 액체 풀화재의 수정된 디자인 화재곡선 평가 연구)

  • Baek, Bitna;Oh, Chang Bo;Lee, Chi Young
    • Fire Science and Engineering
    • /
    • v.32 no.2
    • /
    • pp.7-16
    • /
    • 2018
  • In this study, the previous design fire curve for fire simulation was modified and re-suggested. Numerical simulations with the FDS and CFAST were performed for the n-heptane and n-octane pool fires in the ISO 9705 compartment to evaluate the prediction performances of the previous 1-stage and modified 2-stage design fire curves. The numerical results were compared with the experimental temperature and concentrations of $O_2$ and $CO_2$. The FDS and CFAST simulations with the 2-stage design fire curve showed better prediction performance for the variation of temperature and major species concentration than the simulations with 1-stage design fire curve. Especially, the simulations with the 2-stage design fire curve agreed with the experimental temperature more reasonably than the results with the 1-stage design fire curve. The FDS and CFAST simulations showed good prediction performance for the temperature in the upper layer of compartment and the results with the FDS and CFAST were similar to each other. However, the FDS and CFAST showed poor and different prediction performance for the temperature in the lower layer of compartment.