• 제목/요약/키워드: KEPCO's loss

검색결과 58건 처리시간 0.025초

Investigation on Effective Operational Temperature of HTS Cable System considering Critical Current and AC loss

  • Kim, Tae-Min;Yim, Seong-Woo;Sohn, Song-Ho;Lim, Ji-Hyun;Han, Sang-Chul;Ryu, Kyung-Woo;Yang, Hyung-Suk
    • KEPCO Journal on Electric Power and Energy
    • /
    • 제2권2호
    • /
    • pp.307-310
    • /
    • 2016
  • The operational cost for maintaining the superconductivity of high-temperature superconducting (HTS) cables needs to be reduced for feasible operation. It depends on factors such as AC loss and heat transfer from the outside. Effective operation requires design optimization and suitable operational conditions. Generally, it is known that critical currents increase and AC losses decrease as the operational temperature of liquid nitrogen ($LN_2$) is lowered. However, the cryo-cooler consumes more power to lower the temperature. To determine the effective operational temperature of the HTS cable while considering the critical current and AC loss, critical currents of the HTS cable conductor were measured under various temperature conditions using sub-cooled $LN_2$ by Stirling cryo-cooler. Next, AC losses were measured under the same conditions and their variations were analyzed. We used the results to select suitable operating conditions while considering the cryo-cooler's power consumption. We then recommended the effective operating temperature for the HTS cable system installed in an actual power grid in KEPCO's 154/22.9 kV transformer substation.

2000년 하계 첨두시의 지역별 송전손실 특성분석 (Analysis on Characteristics of Regional Transmission Loss based on the KEPCO's Peak Load Data of Year 2000)

  • 남궁재용;최흥관;문영환;임성황;한용희
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 추계학술대회 논문집 학회본부 A
    • /
    • pp.20-22
    • /
    • 2000
  • The transmission networks are not perfect conductors and a percentage of the power generated is therefore lost before it reaches the loads. This network loss contributes to the cost of suppling power to consumers, and must be considered if the most efficient dispatch and location of generators and loads is to be achieved. In this paper, we propose an approximate calculation of marginal loss factors to analyze characteristics of regional transmission loss. These static marginal loss factors are approximately calculated based on the KEPCO's expected summer peak load data of year 2000.

  • PDF

한계손실계수에 의한 한전 예상첨두계통 송전손실 특성 분석 (Analysis on Characteristics of Transmission Loss using Marginal Loss Factors Based on the KEPCO's Expected Peak Load Data of Year 2000)

  • 남궁재용;최흥관;문영환;오태규;임성황;한용희
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제50권7호
    • /
    • pp.333-339
    • /
    • 2001
  • The transmission networks are not perfect conductors and a percentage of the power generated is therefore lost before it reaches the loads. This network loss effects to the cost of suppling power to consumers, and must be considered if the most efficient dispatch and location of generators and loads is to be achieved. In this paper, we propose an approximate calculation of marginal loss factors to analyze characteristics of transmission loss of KEPCO power system. These static marginal loss factors are approximately calculated based on the KEPCO's expected summer peak load data of year 2000.

  • PDF

손실감소를 위한 배전계통 재구성에 관한 연구 (A Study on Distribution Network Reconfiguration for Loss Reduction)

  • 김세호;최병윤;조시형;손인배;문영현
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1996년도 하계학술대회 논문집 B
    • /
    • pp.686-688
    • /
    • 1996
  • Network reconfiguration is performed by opening/closing two types of switches, tie and sectionalizing switches. A whole feeder, or part of a feeder, may be served from another feeder by closing a tie switch linking the two while an appropriate sectionalizing switch must be opened to maintain radial structures. In loss reduction, the problem is to identify tie and sectionalizing switches that should be closed and opened, respectively, to achieve a maximum loss reduction. In this paper, it is introduced to propose the reconfiguration plan for loss reduction by using the Civanlar's loss reduction formular.

  • PDF

발전 에너지원별 한계손실계수의 비교 연구 (Comparison Analysis of Marginal Loss Factors on Generation Energy Resources)

  • 남궁재용;최흥관;문영환;임성황;한용희
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 추계학술대회 논문집 학회본부 A
    • /
    • pp.95-97
    • /
    • 2000
  • In this paper, static marginal loss factors are calculated that represent the impact of marginal network losses on nodal prices at the transmission network connection points at which generators and loads are located. These static marginal loss factors are approximately calculated based on the KEPCO's expected summer peak load data of year 2000. Based on comparison analysis of marginal loss factors on generation energy resources, we can find the characteristics of each plants according to its energy resources in KOREA.

  • PDF

장시간 충방전에 따른 VRFB-ESS의 용량 손실 회복에 대한 연구 (Study and Recovery on the Capacity Loss after the Long Charge-discharge Operation of VRFB-ESS)

  • 서혜경;박원식;박재우;김강산;최한솔
    • KEPCO Journal on Electric Power and Energy
    • /
    • 제8권2호
    • /
    • pp.181-187
    • /
    • 2022
  • As the charges/discharges of VRFB-ESS were repeated during 150cycles or more, the capacity of electrolyte in VRFB-ESS was decreased little by little. It results from the decreasing of the level of anolyte and the increasing of the valance value of the catholyte. Then, we tried to recover the capacity loss with 3 different ways. The first way was that the levels of anolyte and catholyte were allowed to be evenly equalized when the difference in the levels of two different electrolytes were severe. The second one was to lessen the valance value of the catholyte through the reduction reaction to 4-valant ions of 5-valant ions in the catholyte with the reductant, oxalic acid. The last one was that the all electrolytes of analyte and catholyte were allowed to be electro-chemically reduced to 3.5 of the valance value by oxidizing new electrolyte with 3.5 valance ions. The last way was the most effective to recover the capacity loss.

우리나라 전력계통의 공급적정도 평가에 관한 사례연구 (A Case Study on Probabilistic Adequacy Assessment of KEPCO System)

  • 전동훈;곽노홍;박상호;한경남;최재석;김건중
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2007년도 제38회 하계학술대회
    • /
    • pp.61-62
    • /
    • 2007
  • This paper evaluates probabilistic reliability of KEPCO system using TRELSS, which is a probabilistic reliability evaluation program for large-scaled power system. In order to systematically evaluate probabilistic reliability of KEPCO system, contingency cases causing load loss in (N-1) & (N-2) contingency depth was analyzed and reliability indices such as LOLP, EDLC, EENS according to change of FOR was calculated.

  • PDF

업무용 건축물에 적용된 단열재의 경년열화에 따른 열손실량 분석 (Analysis of Heat Loss Due to Time Dependent Aging of Insulation Applied to Office Building)

  • 이도형;나환선
    • 한국태양에너지학회 논문집
    • /
    • 제37권5호
    • /
    • pp.65-75
    • /
    • 2017
  • In this study, the change of heat loss due to the degree of deterioration of the XPS insulation in KEPCO's office buildings is analyzed. The acceleration aging test of the XPS insulation was carried out according to the test method A of KS M ISO 11561: 2009. The performance of the insulation was analyzed by applying it to the three - dimensional steady state heat transfer analysis program. The acceleration aging test of the XPS insulation, show that the thermal resistance performance decreased by 1.44% at the A regional headquarters, 0.85% at the B regional headquarters, 6.41% at the C branch office, 7.76% at the D regional headquarters, 8.51% at the E branch office, and by 8.54% at the F branch office respectively. Using simulation, we determined that the thermal resistance value of E branch office decreased by 8.04%, while its heat loss increased by 8.52%. At A regional headquarters, the thermal resistance decreased by 1.38%, and the heat loss increased by 1.51%. At D regional headquarters, these value are 6.82% and 7.17%, respectively.

전력시장 소매가격의 규제가 사회후생에 미치는 영향

  • 김현숙;이수진;이정인
    • 자원ㆍ환경경제연구
    • /
    • 제21권1호
    • /
    • pp.93-127
    • /
    • 2012
  • 본 논문에서는 전력시장에서 원가 이하로 규제되고 있는 소매요금제도의 문제점을 분석하기 위해 규제된 소매요금 대신 시간별 도매시장가격의 변동을 반영하는 실시간 요금제를 도입할 경우 사회후생에 미치는 영항과 이와 같은 소매요금제도의 변화가 한국전력의 손실 규모를 어느 정도 보전할 수 있는지를 추정한다. 전력거래소의 전력통계정보시스템(EPSIS)과 에너지경제연구원 국가에너지통계종합정보시스템(KESIS), 통계청, 한국은행, 기상청의 2008~2010년 통계자료에 기초하여 실질소매가격, 온도, 가구수, 습도 실질 GDP, 그리고 요일 및 공휴일 더미 등을 설명변수로 이용하여 상대적으로 수요가 많은 여름(6~8월)과 겨울(12~2월)의 최대 부하시간대와 최저 부하시간대의 수요패턴을 분석하였다. 회귀분석을 통해 추정된 선형수요함수와 발전기별 한계비용에 기초하여 산정된 계단식 공급함수를 이용하여 규제된 소매요금이 시장균형가격인 실시간 요금으로 전환될 경우의 사회후생 변화를 살펴본 결과, 여름기간(6~8월)에는 사회후생이 약 674억 원 증가하는 것으로 나타났다. 또한 한전손실 총액 중 7,055억 원은 소비자잉여의 이전으로, 나머지 674억 원은 시중손실의 감소로 충당될 수 있음을 확인하였다. 겨울에는 사회후생 증대가 약 2,251억 원에 이르고, 한전의 손실 중 1조 1,743억 원이 소비자잉여의 전가로 보전될 수 있는 것으로 나타나 소매요금의 규제가 사중손실의 발생을 통해 전체 사회후생을 감소시키고, 한전에게 막대한 손실을 초래하고 있다는 결과를 도출하였다.

  • PDF

지능형 원격검침시스템을 이용한 전력손실 감시방법에 대한 연구 (A Study on the Power Loss Monitoring Methods with AMI systems)

  • 명노길
    • 조명전기설비학회논문지
    • /
    • 제27권8호
    • /
    • pp.67-74
    • /
    • 2013
  • Major utilities have been focusing on R&D and nationwide business of AMI system which plays a vital role in SmartGrid whose concept is to maximize energy efficiency and optimize electric power facility management with exchanging real time information between utilities and consumers based on ICT technologies in power grid. In this paper, we suggest a power loss monitoring method using KEPCO's AMI system which is operating in fields and with the acquisition of AMI data and analyses verify the validation of a power loss monitoring method.