• 제목/요약/키워드: Islanding_detection

검색결과 98건 처리시간 0.031초

계통연계형 태양광발전 인버터에 사용된 AFD기법의 다양한 부하에 따른 단독운전 불검출영역에 대한 고찰 (A Study of Non-Detection Zone using AFD Method applied to Grid-Connected Photovoltaic Inverter for a variety of Loads)

  • 고문주;최익;최주엽
    • 한국태양에너지학회 논문집
    • /
    • 제26권1호
    • /
    • pp.91-98
    • /
    • 2006
  • Islanding phenomenon of utility-connected photovoltaic power conditioning systems(PV PCS) can cause a variety of problems and must be prevented. If the real and reactive power supplied by PV PCS are closely matched to those of load, islanding detection by passive methods becomes difficult. The active frequency drift(AFD) method, called the frequency bias method, enables islanding detection by forcing the frequency of the voltage in the islanding to drift up or down. In this paper, non-detection zone(NDZ) of AFD is analyzed for the islanding detection method of utility-connected PV PCS by the simulation software tool PSIM.

불검출영역이 없는 새로운 단독운전 검출기법 (A Novel Islanding Detection Scheme without Non Detection Zone)

  • 조영민;김동균;조상윤;송승호;최익;이영권;최주엽
    • 전력전자학회논문지
    • /
    • 제20권6호
    • /
    • pp.540-549
    • /
    • 2015
  • Unintentional islanding results in safety hazards, reliability, and many other issues. Therefore, the islanding detection of a power conditioning system of a distributed generation, such as a grid-connected photovoltaic inverter, is a key function for standard compliance. Currently, many anti-islanding schemes have been examined, but existing anti-islanding schemes have poor power quality and non-detection zone issues. Therefore, this study analyzes the non-detection zone in a more deliberate manner than the existing analysis of the non-detection zone and proposes a new anti-islanding scheme, which has negligible power quality degradation and no non-detection zone. Simulation and experimental results validate that the proposed scheme shows much better performance than other existing schemes.

시간영역에서 순시 유효/무효전력을 이용한 마이크로그리드의 단독운전 판단 (Islanding Detection for a Micro-Grid based on the Instantaneous Active and Reactive Powers in the Time Domain)

  • 이영귀;김연희;정태영;김태현;강용철
    • 전기학회논문지
    • /
    • 제61권1호
    • /
    • pp.22-27
    • /
    • 2012
  • Correct and fast detection of a micro-grid (MG) islanding is essential to the MG since operation, control and protection of the MG depend on an operating mode i.e., an interconnected mode or an islanding mode. When islanding occurs, the frequency of the point of common coupling (PCC) is not the nominal frequency during the transient state owing to the frequency rise or drop of generators in the MG. Thus, the active and reactive power calculated by the frequency domain based method such as Fourier Transform might contain some errors. This paper proposes an islanding detection algorithm for the MG based on the instantaneous active and reactive powers delivered to the dedicated line in the time domain. During the islanding mode, the instantaneous active and reactive powers delivered to the dedicated line are constants, which depend on the voltage of the PCC and the impedance of the dedicated line. In this paper, the instantaneous active and reactive powers are calculated in the time domain and used to detect islanding. The performance of the proposed algorithm is verified under various scenarios including islanding conditions, fault conditions and load variation using the PSCAD/EMTDC simulator. The results indicate that the algorithm successfully detects islanding for the MG.

전압 불평형율을 이용한 분산전원의 고립운전 검출 기법 (An Islanding Detection Method for Distributed Generations Using the Voltage Unbalance)

  • 장성일;박종근;김황호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 하계학술대회 논문집 A
    • /
    • pp.42-44
    • /
    • 2004
  • This paper introduced and proposed the voltage unbalance of DC terminal output as new monitoring parameter for power islanding detection. This paper also presented a simple and novel detection algorithm, which effectively combines the detection results of the conventional parameter, voltage magnitude, and a newly proposed parameter. We tested the proposed method using several distribution network conditions including not only islanding operation conditions, but also non-islanding conditions of normal network load variations. The test results showed that the proposed parameters and algorithm are capable of correctly detecting the islanding operation not affected by variation of DG loading and also have a good selectivity for islanding conditions and non-islanding conditions.

  • PDF

고조파을 이용한 분산전원 고립운전 검출 알고리즘 (Islanding Detection Algorithm Based on a Harmonic for Distributed Generators)

  • 고철진;권영진;강상희
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 하계학술대회 논문집 A
    • /
    • pp.301-303
    • /
    • 2004
  • This paper presents an islanding detection algorithm based on the second harmonic. When the DG(distributed Generator) was connected with utility supply, for maintenance and repair of equipment, an islanding occurred. So islanding detection algorithm must be developed for safety of human. Although the DG generating power is similar to power consumption. the proposed algorithm can detect the islanding condition very successfully.

  • PDF

Positive Feedback을 이용한 무효전력 P&O 단독운전 검출기법 (Reactive Power P&O Islanding Detection Method using Positive Feedback)

  • 이종원;박성열;이재연;최세완
    • 전력전자학회논문지
    • /
    • 제27권5호
    • /
    • pp.410-416
    • /
    • 2022
  • A grid-connected inverter with critical loads uses mode transfer control to supply stable voltage to the load. An islanding detection method should also be used to quickly detect the grid fault and disconnect the inverter from the grid. However using the existing islanding detection method to detect islanding is difficult due to the small fluctuation of the voltage and frequency of the point of common coupling. This study proposes a reactive power P&O islanding detection method by using the positive feedback technique. The proposed method always injects a small variation of reactive power. When a grid fault occurs, the injected reactive power accelerates the reactive power injection reference. As a result, the reactive power reference value and the sensed reactive power become mismatched, and islanding is detected. Reducing the amount of real-time injected reactive power results in high efficiency and power factor. The simulation and experimental results of a 3 kW single-phase inverter are provided to verify the proposed islanding detection method.

분산전원 시스템의 주파수 변동을 통한 단독운전 방지기법 분석 (Analysis of Anti-Islanding Schemes using Frequency Drift in Distributed Generation System)

  • 조영민;조상윤;송승호;최익;최주엽;이영권
    • 전력전자학회논문지
    • /
    • 제20권3호
    • /
    • pp.247-254
    • /
    • 2015
  • Unintentional islanding results in safety hazards, power quality degradation, and many other issues. Thus, islanding detection of grid-connected distributed generation system is a key function for standards compliance. Many anti-islanding schemes are currently being studied; however, existing anti-islanding schemes used in inverters have power quality degradation and non-detection zone issues. Therefore, this paper analyzes existing anti-islanding schemes by using frequency drift in accordance with both islanding detection performance and power quality. This paper also proposes a new anti-islanding scheme by using frequency drift. Both simulation and experimental results show that the proposed scheme has negligible power quality degradation and no non-detection zones compared with other existing schemes.

계통연계형 태양광발전시스템의 새로운 단독운전 검출기법 (Novel islanding detection method for grid connected PV system)

  • 정영석;소정훈;유병규;유권종;최재호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 제36회 하계학술대회 논문집 B
    • /
    • pp.1705-1707
    • /
    • 2005
  • This paper proposes a novel active frequency drift(AFD) method for the islanding prevention of grid-connected photovoltaic inverter. To detect the islanding phenomenon of grid-connected photovoltaic(PV) inverters concerning about the safety hazards and the damage to other electric equipments, many kinds of anti-islanding methods have been presented. Among them, AFD method using chopping fraction(cf) enables the islanding detection to drift up(or down) the frequency of the voltage during the islanding situation. However, the performance of the conventional AFD methods, which have a certain value of cf only, is inefficient and difficult to design the appropriate cf value analytically to meet the limit of harmonics. In this paper, the periodic chopping fraction based on an AFD method is proposed. This proposed method shows the analytical design value of cf to meet the test procedure of IEEE Std. 929-2000 with the power quality and islanding detection time. To verify the validation of the proposed method, the islanding test results are presented. It is confirmed that the proposed method has not only less harmonic distortion but also good performance of islanding detection compare with the conventional AFD method.

  • PDF

계통연계형 태양광발전 시스템의 주파수 변동에 의한 새로운 고립운전 검출기법 (Novel Islanding Detection Method using Frequency Drift for Grid-connected PV System)

  • 은석준;김흥근;최종우;이동춘
    • 대한전기학회논문지:전기기기및에너지변환시스템부문B
    • /
    • 제54권6호
    • /
    • pp.294-302
    • /
    • 2005
  • PV system's islanding occurs when the uitilty grid is removed but local sources continue to operate and provide power to local loads. Islanding is one of the serious problems in an electric power system connected with dispersed power sources. Also, this can present safety hazards and the possibility of damage to other electric equipments. If the real and reactive power of RLC load and PV system are closely matched, islanding detection by passive methods becomes difficult. This paper shows the simulation and comparision for the previous active methods and novel islanding detection method using frequency drift is proposed for grid-connected PV system.

단독운전 방지를 위한 능동적 주파수 변환 기법의 검출 성능 및 THD 분석 (Detection Performance and THD Analysis of Active Frequency Drift for Anti-Islanding)

  • 조영민;최주엽;송승호;최익;이영권
    • 한국태양에너지학회 논문집
    • /
    • 제35권2호
    • /
    • pp.11-19
    • /
    • 2015
  • Islanding is a phenomenon that EPS(Electric Power System) is continuously energized by PV PCS(Photovoltaic Power Conditioning System) even when EPS is isolated from the grid. Unintentional islanding will result in safety hazard, power quality degradation and many other issues. So, islanding protection of grid-connected PV PCS is a key function for standards compliance. Nowadays, many anti-islanding schemes are researched. But existing anti-islanding schemes used in PV PCS have power quality degradation and non-detection zone issues. This paper analyses not only detection performance of existed anti-islanding schemes using active frequency drift but also THD of PCS output current according to each value disturbance for anti-islanding. In addition, the lowest value of disturbance in each scheme was tabulated under guarantee of anti-islanding condition.