Abstract
Unintentional islanding results in safety hazards, reliability, and many other issues. Therefore, the islanding detection of a power conditioning system of a distributed generation, such as a grid-connected photovoltaic inverter, is a key function for standard compliance. Currently, many anti-islanding schemes have been examined, but existing anti-islanding schemes have poor power quality and non-detection zone issues. Therefore, this study analyzes the non-detection zone in a more deliberate manner than the existing analysis of the non-detection zone and proposes a new anti-islanding scheme, which has negligible power quality degradation and no non-detection zone. Simulation and experimental results validate that the proposed scheme shows much better performance than other existing schemes.
Keywords
Grid-connected photovoltaic inverter; Anti-islanding; NDZ(Non Detection Zone); Power quality; THD(Total Harmonic Distortion);
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 K. O. Lee, “Output power analysis for active frequency drift method,” Journal of the Korea Solar Energy Society, Vol. 29, No. 6, pp. 75-80, Dec. 2009.
2 M. J. Ko, “A study of non-detection zone using AFD method applied to grid-connected photovoltaic inverter for a variety of loads,” Journal of the Korea Solar Energy Society, Vol. 26, No. 1, pp. 91-98, Mar. 2006.
3 Z. Ye, "A new family of active anti-islanding schemes based on DQ implementation for grid-connected inverters," Power Electronics Specialists Conference, PESC 2004 IEEE 35th Annual, Vol. 1, 2004.
4 S. K, Kim, "Frequency-shift acceleration control for anti-islanding of a distributed-generation inverter," IEEE Industrial Electronics Society, Vol. 57, No 2, pp. 494-504, Feb. 2010.   DOI