• Title/Summary/Keyword: Insulation Oil

Search Result 258, Processing Time 0.027 seconds

Research of Flow Electrification Phenomena of the used Environment-Friendly Vegetable Insulating Oils (친환경 식물성절연유의 유동대전현상 연구)

  • Choi, Sun-Ho;Huh, Chang-Su
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.61 no.4
    • /
    • pp.580-584
    • /
    • 2012
  • The insulating oils perform a cooling and insulation action in electric power transformer. The mineral oil has immanent fire dangerousness and environmental contamination problem. Vegetable insulating oil has higher ignition point, flash point and more excellent biodegradability than conventional mineral oil. In a real oil-filled transformers, some of the power is dissipated in the form of heat. And transformer require the heat to be removed from the winding and insulator by forced convection of the insulating oil. The flow electrification occurs when insulating oil was forced to be circulated. In this paper, influence of temperature, velocity of flow, and insulating pipe and diameter on streaming electrification of vegetable insulating oil was investigated using forced circulation apparatus. Temperature effects were most significant, and it showed a peak in the temperature $30^{\circ}C$ to $35^{\circ}C$ at insulating and copper pipe. The change of flow electrification according to area variety could be checked by change of diameter.

A Study on the Streaming Electrification Phenomena of the Transformer Oil (변압기유의 유동대전 현상에 관한 연구)

  • 강성화;임기조;주상범;김명녕;강도열;김봉협
    • The Transactions of the Korean Institute of Electrical Engineers
    • /
    • v.39 no.6
    • /
    • pp.568-576
    • /
    • 1990
  • Recently, streaming electrification in forced oil cooled power transformer has been taken up as a serious problem. In this paper, the charging tendency of various insulation oils, such as mineral oil, polybutene and silicone oil has been measured by means of an injection type charging tendency measuring apparatus under various condition. The experimental data of the dependence of the leakage current on flow velocity and temperature of oil can be explained by considering the flow state such as laminar and turbulent flow. The effect of additives on the charging tendency of mineral oil has been investigated. BTA is regarded as the most effective retardant to electrification of oil among the additives chose for this investigation.

  • PDF

A Study on the Electric Field Analysis of Extra-High Voltage Oil-Filled Cable Accessories (초고압 지중 OF 케이블 접속재의 전계해석에 관한 연구)

  • Lee, Jong-Bum;Kang, Dong-Sik;Kang, Do-Hyun;Lee, Soo-Hyun
    • Proceedings of the KIEE Conference
    • /
    • 1989.07a
    • /
    • pp.432-435
    • /
    • 1989
  • This paper presents an algorithm for electric field analysis which is essential to insulation design of extra-high voltage oil-filled cable accessories using finite element method. Governing equation is induced by electromagnetic equation. Variational method is adopted for FEN formulation. Automatic mesh generation which saves time and labor is introduced for the input data. The application results of proposed algorithms were used for insulation design to develop 345kV cable joint.

  • PDF

Calculation of Heat Loads and Temperature Distribution for the HTS Termination Current Lead (HTS 단말 전류도입선 형상에 대한 온도분포 및 열부하 계산)

  • 조승연;사정우;김도형;김동락;김승현;양형석
    • Proceedings of the Korea Institute of Applied Superconductivity and Cryogenics Conference
    • /
    • 2003.02a
    • /
    • pp.36-39
    • /
    • 2003
  • HTS (High Temperature Superconducting) cable termination current lead has been designed based on simplified boundary conditions such as fixed temperature at both end and sdiabatic/convection in the side wall. However, in the real situation the current lead is enclosed with insulators and exposed to insulation oil and L$N_2$. Therefore it is necessary to consider them for the proper current lead design. In this paper, several important design parameters were chosen and their effect on the temperature distribution and heat loads on the current lead has been investigated. It was found that current lead has to be 2 stage to reach the minimum temperature requirement of insulation oil and insulator is required to reduce the cooling capacity of cryogenic system.

  • PDF

Ultrasonic-detection characteristics of optical-fiber sensor for insulation diagnosis (절연진단용 광섬유 센서의 초음파 검출특성)

  • Lee, S.H.;Sim, S.H.;Lee, K.S.;Kim, D.W.
    • Proceedings of the KIEE Conference
    • /
    • 2002.11a
    • /
    • pp.183-186
    • /
    • 2002
  • It is well known that a discharge in oil is the source of various physical and chemical phenomena. One of them is ultra-sonic wave, and its detection is a useful method to the diagnosis of the transformer insulation condition. Conventionally, ultra-sonic waves are detected by Piezo-electric trans-ducer(PZT), and we use optical method that has many advantages. In this paper, we constructed a Mach-Zehnder interferometer with optical fiber and investigated the principle of operation. Test of the ultrasonic-detecting ability was performed for both of PZT and fiber-optic sensor. Discharge test arrangement is based on the needle-plane electrode system in oil and applied AC high voltage. Ultrasonic waves were detected and showed time-delay characteristics. We analyzed the data with frequency domain and wavelet transform.

  • PDF

Characteristics of Ultra High Frequency Partial Discharge Signals from Metallic Particle Defected Oil-paper Insulation in Transformer (변압기 절연지 표면 금속 이물질 방전에 의한 극초단파 신호특성)

  • Yoon, Jin-Yul;Ju, Hyung-Jun;Goo, Sun-Geun;Park, Ki-Jun
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.22 no.10
    • /
    • pp.879-883
    • /
    • 2009
  • This paper was provided to help in detecting defects in power transformer. For this purpose, a partial discharge cell was designed and manufactured as a discharge source to simulate particle defected paper-oil insulation in power transformer. Experimental set-up for measuring PD signals was described. Magnitude of electromagnetic wave signals and corresponding amount of apparent discharge were measured simultaneously against phase of applied voltage to the discharge cell. Frequency range and pattern of PRPD(Phase Resolved Partial Discharge) of partial discharge signals were examined and analyzed. The results will be contributed to build the defect database of power transformer and to decrease the substation faults.

Chemical Properties of Insulation Paper in oil after Thermal Aging (열 열화에 따른 유입절연지의 화학적 특성)

  • Kim, Pil-Hwan;Kim, Jae-Hoon;Kim, Ju-Han;Lee, Won-Yeong;Han, Sang-Ok
    • Proceedings of the KIEE Conference
    • /
    • 2004.11d
    • /
    • pp.77-79
    • /
    • 2004
  • It is caused that insulation paper, which had got a lot of thermal stress by over-load after installation, should have been deteriorated in electrical and mechanical characteristics. Beside, insulation material is decreased the insulating property and accelerated aging of them in case of dielectric loss when transformers are manufactured with some moisture or transformers would have been them because of moisture-permeation. Therefore, in this study we experienced the influence of moisture content in case of the thermal aged insulation paper. we have measured tan 6 and breakdown voltage in the ratio of paper' moisture content before the aging and then taken the same tests again after insulation paper thermally accelerating-aged. There is a purpose to gain data for a life-design and to establish aging mechanism in order to continuously study life expectancy of the insulation paper

  • PDF

Biodegredible material application of insulation oil of OF CABLE (OF 케이블 절연유의 환경친화적 자재 적용)

  • Kim, Jong-Won;Lee, Kee-Soo;Ha, Jae-Cheong;Choi, Bong-Nam;Lee, Seung-Yol
    • Proceedings of the KIEE Conference
    • /
    • 2000.07c
    • /
    • pp.2023-2025
    • /
    • 2000
  • Globally, movements for an environmental preservation have been further extended in all the areas of industries. In the manufacturing area. environment-friendly properties for all the manufactured products are increasingly required by many national standards. For EHV oil-filled cables. Hard Alkylbenzen has been applied as an impregnated insulating oil. But as it flows into the soil during failures, such as oil leakage, the oil is not dissolved by microbes and then causes an environmental pollution. Recently some countries are increasingly requiring Soft Alkylbenzen which is dissolved by microbes. This paper describes the electrical and environmental properties of Soft Alkylbenzen. applied for a 230kV oil-filled cables at a Singapore's project.

  • PDF

Measurement of Moisture Contents using Recovery Voltage Method and Karl-Fischer Method (Karl-Fischer법과 회복전압법을 이용한 수분량 검출 비교 특성)

  • Kim, Hyung-Min;Kim, Jae-Hoon;Kim, Ju-Han;Han, Sang-Ok;Lee, Sei-Hyun
    • Proceedings of the KIEE Conference
    • /
    • 2005.07e
    • /
    • pp.76-78
    • /
    • 2005
  • Moisture contents measurement is frequently used as one of parameters for degradation diagnosis of transformer insulation. In general Karl-Fisher method is mainly used for moisture contents till now. But this method is inconvenient because of dismounting transformer for sampling oil or paper, and also partial sampling. At latest Recovery Voltage Method(RVM) is noticed for complement of this method. RVM can directly estimate moisture contents of transformer insulations in field without dismounting transformer. In this paper the accelerated aging process of oil-paper samples have been investigated at a temperature up to 140$^{\circ}C$ for 500 hours. The oil-paper insulation samples have been measured at intervals of 100 hours. Next to, we have estimated moisture contents using both Karl-Fisher Titration Method and RVM. And we have compared with Karl-Fisher Titration Method and RVM for estimating moisture contents. At last we have verified reliability of RVM which is new measurement method.

  • PDF

Analysis on the Temperature Distribution Characteristics of Insulating oil of Transformer Using the Vegetable oil and Mineral oil (식물성 절연유와 광유가 사용된 유입변압기의 온도분포 특성)

  • An, Jung-Sik;Shim, Meoung-Seop;Jung, Joong-Il;Kim, Nam-Ryul;Huh, Chang-Su
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.1215_1216
    • /
    • 2009
  • Most transformer use insulating and cooling fluids derived from petroleum crude oil, but mineral oil is some possibility of environmental pollution and fire with explosion. vegetable oil fluids extracted from seed has superior biodegradation and fire-resistant properties including an exceptionally high fire point enhancing fire safety. In this study, it is aimed at the practicality of substituting natural ester dielectric fluid for mineral oil in liquid insulation system of transformers. As a rise in coil winding temperature has a direct influence on transformer life time, it is important to evaluate the temperature rise of coil winding in vegetable oil in comparison with mineral oil. Three transformers for the test are designed with 10KVA, 13.2KV, one phase unit. The temperature are directly measured in insulating oil of these transformers with the two sorts of natural ester and mineral oil dielectric fluid respectively. Temperature of vegetable oil transformers was similar to temperature of mineral oil transformer in the same design at 80% load and above.

  • PDF