Surface Characterization of Silicone Rubber for Outdoor Insulation by Measurement of Surface Voltage Decay

  • Youn, Bok-Hee;Huh, Chang-Su;Cho, Han-Gu
    • KIEE International Transactions on Electrophysics and Applications
    • /
    • 제12C권4호
    • /
    • pp.214-219
    • /
    • 2002
  • The influence of ultraviolet (UV) irradiation and corona on the surface degradation of high temperature vulcanized (HTV) silicone rubber used for outdoor insulation through measuring surface voltage decay after corona charging, surface resistivity, contact angle and X-ray photoelectron spectroscopy (XPS) analysis was studied. The surface resistivity calculated by the surface voltage decay was compared with a value directly obtained from the three electrode method having the guard ring electrode. A good agreement between the two methods for surface resistivity was obtained. UV treated specimens showed the slower decrease of surface voltage decay, while the corona exposed specimens showed a dramatically faster decrease. Although both artificial treatments cause the same oxidative products, which was confirmed with XPS, we could distinguish the difference between the reactions of the two treatments by monitoring the surface voltage decay on corona-charged specimen. In addition, we could derive the specific surface states of the silicone rubber treated by accelerated artificial aging factors and the degradation process.

고체절연재료에서 발생하는 부분방전 특성량의 Data-Base 구축 (Data-Base of Statistical Parameters from PD generated in Solid Insulation)

  • 강성화;이흥규;박영국;김완수;이용희;박정남;임기조
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 하계학술대회 논문집 C
    • /
    • pp.1927-1929
    • /
    • 2000
  • PD indicates the inception and progress of degradation of solid insulation system, so it has been used to determine degradation of insulation. PD provides means for detection and recognition of defects. However, there is still marked difficult to recognize defects by PD methods. In this paper, we investigated properties of PD in solid insulation by using statistical method with surface discharge, electrical tree and void discharge with source of discharge, we used statistical parameters of PD distributions specified such as $H_n(q)$, $H_{an}(\phi)$, $H_n(\phi)$, $H_a(\phi)$. The parameters induced from its specified distributions are average discharge, average repetition rate, Skewness, Kurtosis, asymmetry and correlation. From the parameters, we classified PD patterns and built up DB(data-base).

  • PDF

고체절연체의 내부결함에 따른 부분방전 특성과 패턴분류 (Properties of PD and Classification of Defect Patterns in Solid Insulation)

  • 강성화;박영국;이광우;김완수;이용희;임기조
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 D
    • /
    • pp.1624-1626
    • /
    • 1999
  • PD in defect of solid insulation system is very harmful since It often leads to deterioration of insulation by the combined action of the discharge ions bombarding the surface and the action of chemical compounds that are formed by the discharge. PD can indicate incipient failure, so it has been used to determine degradation of insulation. In this paper. we investigated PD in defects of solid insulation by using statical method and classified PD patterns with surface discharge, electrical tree and void discharge by using Kohonen network. we used peak charge, average discharge power, average discharge current, repetition rate, skewness, kurtosis, QN of the max pulse height vs. repetition rate $H_q(n)$ for analysis and classification.

  • PDF

SF_6 가스와 절연지의 절연계에서 가스압력에 따른 부분방전현상 (Partial Discharge Phenomenon with $SF_6$ Gas Pressures in Insulation consisting of Insulation Paper and $SF_6$ Gas)

  • 선종호;김광화;박정후;조정수
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제50권2호
    • /
    • pp.65-71
    • /
    • 2001
  • This paper describes partial discharge phenomenon with SF6gas pressures in insulation consisting of insulation paper and SF6 gas. We made the specimens with SF6 gas gaps which exist between aramid papers and electrodes and calculated the electric field intensity in the these gaps. We measured the partial discharge inception voltages and the AC breakdown voltages with the test method of IEC 60060-2 and did the partial discharge degradation experiments with a constant voltage. According to gas pressures, the breakdown voltages in SF6gas gaps were calculated by Paschen's law. And these results showed the ability applying partial discharge inception voltages evaluation to Paschen's law and the relationship between the PD quantities occurring insulation breakdown and PD occurring area.

  • PDF

22kV CV케이블에 있어서 절연열화현상의 고찰 (A Study on Insulation Degradation Phenomena in 22kV CV Power Cable)

  • 강무성;김동식;정성룡;박대희
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1996년도 하계학술대회 논문집 C
    • /
    • pp.1797-1800
    • /
    • 1996
  • In this study, the insulation selected in degra-dated-power cable has been observed and aging process about the insulation has been investigated. Most Insulation aging process initiates in the interface of semiconducting layer and the type of the process is the fractal form that was observed between the the semiconducting layer and insulation layer. It is possible to estimate degree of the degration of cable with breakdown test and obtained data have been used to get parameters in order to use Weibull distribution. With this method it is considered to be possible to estimate situation of degration and life prediction.

  • PDF

배전용 절연카바류의 경년특성 분석 (The Analysis of Ageing Characteristics of Insulation Cover Using in Distribution Line)

  • 김동명;송일근;한재홍;이병성;한용회;이태선
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2001년도 춘계학술대회 논문집 유기절연재료 전자세라믹 방전플라즈마 연구회
    • /
    • pp.76-78
    • /
    • 2001
  • In this paper insulation cover that being used in distribution line have been evaluated for aging characteristics. For evaluating its aging properties, we dismounted a variety of samples, like insulation covers for termination of deadend clamp, bushing, LA, COS and sleeve, in the fields. we performed mechanical properties test, electrical test, weathering test, etc. of these samples. And these samples are compared with virgin sample. Test results shows the bad mechanical strength in some part of samples. Especially, Insulation covers for the bushing terminations have cracks in the surface of samples.

  • PDF

동결융해 반복에 따른 건축용 단열재의 열전도 특성 (Thermal Conductivity Properties of Building Insulation Materials with Freezing and thawing Cycles)

  • 이건철;최중구;이건영;임순현
    • 한국건축시공학회:학술대회논문집
    • /
    • 한국건축시공학회 2014년도 추계 학술논문 발표대회
    • /
    • pp.190-191
    • /
    • 2014
  • The building insulation materials shall keep their thermal conductivity constant even when the freezing and thawing repeats for over a long time. But, in this condition of repeated freezing and thawing, the organic building insulation material may suffer the degradation in the thermal performance as the gas put into the insulation materials gets out slowly over a long time. Accordingly, in this study, the change in the thermal performance has been tested and evaluated when the repeated freezing and thawing cycles happen.

  • PDF

PD 분포 분석에 의한 견인전동기 고정자 코일의 열화도 분류에 관한 연구 (Classification of stator coil degradation of traction motor by PD signal distribution analysis)

  • 박성희;임종호;장동욱;박현준;강성화;임기조
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2004년도 하계학술대회 논문집 Vol.5 No.2
    • /
    • pp.1183-1186
    • /
    • 2004
  • Degradation and insulation failure of traction motor depend on the continuous stress imposed on it. And knowing on insulation condition is important thing for safety operation of EMU(electric multiple unit). In this paper, PD(partial discharge) characteristics for degradation analysis of stator coil is studied. For PD data acquisition, two models are made; one is normal condition coil, the other is aged condition coil. And PD data for discrimination were acquired from PD detector. And these data making use of a computer-aided discharge analyser, statistical and other discharge parameters is calculated to discrimination between different discharge sources. And also these parameter is applied to classify PD sources by neural networks. Neural Networks has good recognition rate for degradation of stator coil.

  • PDF

신경회로망을 이용한 절연 열화진단에 관한 연구 (A Study on Insulation Degradation Diagnosis Using a Neural Network)

  • 박재준
    • 정보학연구
    • /
    • 제2권2호
    • /
    • pp.13-22
    • /
    • 1999
  • 본 논문에서, 부분방전 메카니즘을 진단하고 그리고 신경망을 도입하여 수명을 예측하기 위한 기초연구로서, 온라인상에서 자동진단을 제안했다. 제안한 방법에서 우리는 음향방출 감지시스템과 그리고 펄스 수와 펄스진폭에 의해서 정량적인 통계파라메타를 사용하였다. 통계적인 파라메타인 가령, 무게중심(G)와 방전분포 경도(C)를 이용하였고 그리고 초기단계와 중기단계에 대해서 분석하였다. 정량적인 통계파라메타들은 신경망에 의해서 학습되어졌다. 초기단계에 의해서 수명예측과 절연열화의 진단이 이루어졌다. 열화가 진행하는 동안 신경망 학습을 통한 휼륭한 진단능력이 있음이 근본적으로 드러났고, 신경망이 부분방전에 있어서 절연진단 및 수명예측을 위해서 적절하다는 것이 증명되었다.

  • PDF

원자력 발전 원자로 용기의 열손실 설계인자에 관한 연구 (Parametric Study on the Heat Loss of the Reactor Vessel in the Nuclear Power Plant)

  • Jong-Ho Park;Seoug-Beom Kim
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제28권5호
    • /
    • pp.827-836
    • /
    • 2004
  • The design parameter of the heat loss for the pressurized water reactor has been studied. The heat loss from the reactor vessel through the air gap. insulation are analysed by using the computational fluid dynamics code, FLUENT. Parametric study has been performed on the air gap width between the reactor vessel wall and the inner surface of the insulation, and on the insulation thickness. Also evaluated is the performance degradation due to the chimney effect due to gaps left between the panels during the installation of the insulation system. From the analysis results, the optimal with of air gap and insulation thickness and the value of heat loss are obtained The results show how the heat loss varies with the air gap width and insulation thickness. The temperature and the velocity distributions are also presented. From the results of the evaluation. the optimal air gap width and the optimal insulation thickness are obtained. As the difference between the predicted heat loss and measured heat loss from the reactor vessel is construed Primarily as losses due to chimney effect. the contribution of the chimney effect to the total heat loss is quantitatively indicated.