Effect of Additional Pulse to Remove the Sulfate Film on the Charging Capacity in the Industrial Lead-Acid Battery (극판 피막 분해용 펄스파가 산업용 연축전지의 충전용량에 미치는 영향)

  • Choi, Kwang-Gyun;Yoo, Ho-seon
    • Plant Journal
    • /
    • v.16 no.4
    • /
    • pp.40-44
    • /
    • 2020
  • In this study, after supplying a pulse wave to the 2 V Industrial Lead-Acid Battery electrode plate and repeating the charging and discharging, the discharging time per voltage was analyzed. According to the result of experiment, while the lead-acid Battery that a pulse wave is not supplied decreased about 18 % of discharging capacity than the beginning, the lead-acid Battery that a pulse wave is supplied decreased a little amount much lower than 18 %, of discharging capacity and recorded the 0.56 % decrease, at a minimum, from discharging capacity at the 20 kHz frequency. This means that the sulfate on electrode plate is detached and the positive and negative charge transfer is highly activated at the 20 kHz frequency