Browse > Article

Effect of Additional Pulse to Remove the Sulfate Film on the Charging Capacity in the Industrial Lead-Acid Battery  

Choi, Kwang-Gyun (Korea Middleland Power co. Ltd)
Yoo, Ho-seon (Department of Mechanical Engineering, Soongsil University)
Publication Information
Plant Journal / v.16, no.4, 2020 , pp. 40-44 More about this Journal
Abstract
In this study, after supplying a pulse wave to the 2 V Industrial Lead-Acid Battery electrode plate and repeating the charging and discharging, the discharging time per voltage was analyzed. According to the result of experiment, while the lead-acid Battery that a pulse wave is not supplied decreased about 18 % of discharging capacity than the beginning, the lead-acid Battery that a pulse wave is supplied decreased a little amount much lower than 18 %, of discharging capacity and recorded the 0.56 % decrease, at a minimum, from discharging capacity at the 20 kHz frequency. This means that the sulfate on electrode plate is detached and the positive and negative charge transfer is highly activated at the 20 kHz frequency
Keywords
Industrial Lea-Acid Battery; Charging Capacity; Pulse Wave; Sulfate; Charge; Discharge;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Jo-Seob Kim, Do-hyoung Hong, Jae-eon Kim, 2011.7, Aging Characteristics Analysis of Lead-Acid Batteries According to Charging Method, The korean Institute of Electrical Engineers, pp.1358-1359
2 Youn-Ho Park, Soon-Yong Chun, Bo-Hyeok Seo, 2000.8, Algorithm for Improving the Efficiency of Storing Electricity using Experiments of Charging Characteristics for Industrial Lead-Acid Battery, The Korean Institute of Electrical Engineers, pp.432-441
3 Jae-Bum Park, Seon-Yong Kim, Jian Shen, Dae-seok Rho, 2011.10, A Study on the Charge and Discharge Characteristic of Lead-Acid Battery, The korean Institute of Electrical Engineers, pp.229-231
4 In-Hwan Lee, Myeong-Soo Kim, Soon-Chan Hong, 2011, A Study on SOC Measurement of Lead Storage Batteries, Power Electronics Annual Conference, pp.32-33