• 제목/요약/키워드: Impulse voltages

검색결과 100건 처리시간 0.035초

서지전류가 입사된 ZnO 바리스터에 흐르는 누설전류의 특성 (Characteristics of leakage currents flowing through ZnO varistor exposed to surge currents)

  • 이복희;이봉;이수봉
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2006년도 춘계학술대회 논문집
    • /
    • pp.338-341
    • /
    • 2006
  • This paper presents the leakage current characteristics of ZnO varistors exposed to the $8/20{\mu}s$ lightning impulse currents as functions of the number of injection and amplitude of impulse currents. The surge simulator system ECAT that can generate $8/20{\mu}s$ impulse currents with a peak short-circuit of $5[kA_p]$ was used. Leakage currents flowing through ZnO varistors subjected to the $8/20{\mu}s$ impulse currents were measured under 60 Hz AC voltages. The trend curves of resistive leakage current of ZnO varistors were analytically calculated.

  • PDF

중첩전압(직류+교류 60Hz)에서 산화아연 피뢰기 소자의 누설전류 특성 (The characteristic of leakage current in ZnO surge arrestor elements with mixed direct and 60Hz voltage)

  • 이복희;박건영;강성만;최휘성;오성균
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 추계학술대회 논문집 전기물성,응용부문
    • /
    • pp.186-188
    • /
    • 2003
  • The ZnO surge arrester is the protective device for limiting surge voltages on equipment by diverting surge current and returning the device to its original status. The occurrence of overvoltage appears in any phase to AC power supply system and it appears in mixing AC and impulse voltages, moreover because HVDC power supply system uses converter in semiconductor, it makes mixed DC and high harmonics voltages. In this study, the various mixed AC and DC voltages was made for investigating the degradation effect of ZnO arrester according to mixed voltage. As a result, the increase of DC component to mixed voltages causes the increase of resistive component of total leakage current to ZnO block. In changing V-I curve for mixed voltages, the cross-over point acts a factor as making the proper capacitor size of an equivalent circuit for ZnO block.

  • PDF

서지전류에 의한 누전차단기의 의도하지 않은 트립에 대한 신뢰성 (Reliability on the Unintended Trips of Residual Current Operated Circuit Breakers due to Surge Currents)

  • 이복희;김상현;김유하
    • 조명전기설비학회논문지
    • /
    • 제26권5호
    • /
    • pp.79-84
    • /
    • 2012
  • As the huge economical loss and function paralysis of information technology-based systems can be caused by the misoperation of residual current devices(RCDs) due to surge voltages and currents, RCDs shall not operate by surge currents. In this paper, in order to evaluate the reliability of residual current operated circuit-breakers with integral overcurrent protection for household and similar uses((RCBOs) stressed by surges, the unintended trip characteristics of RCBOs under surge currents were experimentally investigated using the combination wave generator. Seven different types of single-phase RCBOs being present on the domestic market were investigated according to KS C IEC 61009-1 standard. As a result, all kinds of specimens were satisfied the requirements for 0.5 [${\mu}s$]/100[kHz] ring wave impulse currents. Most of specimens stressed by the 8/20[${\mu}s$] impulse current tripped at least one or more, and some of them were broken down during consecutive tests. It was found that only one type of specimens meets the L-N mode immunity to the combination wave of 1.2/50[${\mu}s$] impulse voltage and 8/20[${\mu}s$] impulse current.

뇌충격 측정시스템의 비교시험에 의한 성능평가 - 전파 뇌충격전압 인가시 - (Performance Evaluations of the Lightning Impulse Voltage Measuring System by Intercomparative Test - in case of full lightning impulse voltage -)

  • 김익수;김영배;이형호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1995년도 하계학술대회 논문집 C
    • /
    • pp.1368-1370
    • /
    • 1995
  • Lightning impulse voltage is essential to evaluate the insulation performance of electric power apparatus. Recently international standard(IEC-60) on high voltage measurement techniques are being revised. In the draft of this standard, a new calibration method is introduced and the accuracy of most industrial measuring systems is maintained by means of comparison test against the reference measuring systems. Intercomparison tests of dividers for lightning impulse measurement were carried out by KERI. The shielded resisitive divider with 700kV rating developed by KERI were done comparison test with PTB divider with 300kV rating which have the similar charateristics as that were circulated among the laboratories. This paper reports on the comparison test results with full lightning impulse voltages from 126kV to 240kV. It is demonstrated that KERI are capable of realizing the idea in the revision of the IEC standand, that is, to establish traceability.

  • PDF

Lifetime Assessment for Oil-Paper Insulation using Thermal and Electrical Multiple Degradation

  • Kim, Jeongtae;Kim, Woobin;Park, Hung-Sok;Kang, Ji-Won
    • Journal of Electrical Engineering and Technology
    • /
    • 제12권2호
    • /
    • pp.840-845
    • /
    • 2017
  • In this paper, in order to investigate the lifetime of oil-paper insulation, specimens were artificially aged with thermal and electrical multiple stresses. Accelerated ageing factors and equivalent operating years for each aging temperatures were derived from results of tensile strengths for the aged paper specimens. Also, the evaluation for the multi-stress aged specimens were carried out through the measurement of impulse breakdown voltage at high temperature of $85^{\circ}C$. The lifetimes of the oil-paper insulations were calculated with the value of 66.7 for 1.0 mm thickness specimens and 69.7 for 1.25 mm thickness specimens throughout the analysis of impulse BD voltages using equivalent operating years, which means that dielectric strengths would not be severely decreased until the mechanical lifetime limit. Therefore, for the lifetime evaluation of the oil-paper insulation, thermal aging would be considered as a dominant factor whereas electrical degradation would be less effective.

10/350 ${\mu}s$ 전류파형을 형성하기 위한 대용량 인덕터 특성 (Characteristics of High Energy Inductor to Generate Current Waveform of 10/350 ${\mu}s$)

  • 이태형;조성철;엄주홍;김기복
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2009년도 추계학술대회 논문집
    • /
    • pp.331-334
    • /
    • 2009
  • This paper presents the characteristics of external inductor for impulse current waveform with 10/350 ${\mu}s$ time parameters. Impulse generator was composed with capacitor having large capacitance and low working voltage for the safe of operator and small discharging sound. Parallel R-L-C circuits with crow-bar gaps and superposition method were proposed to make a high current lightning impulse according to IEC 62305-1. The high energy inductor with several taps for fitting half decay time T2 within the tolerance range and experimental data of inductance according to charging voltages were suggested.

  • PDF

전력용 피뢰기의 임펄스에 의한 파손과 대척 기술 (Fracture and Protection Technologies against Impulse of Power Arresters)

  • 한세원;조한구;김석수
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2001년도 하계학술대회 논문집
    • /
    • pp.190-193
    • /
    • 2001
  • ZnO varistors have been widely used to protect power system and electronic system against overvoltages based on their excellent nonlinearity. In order to increase their protection capability, the fracture and protection technologies of arresters have to study according to their applications, namely ImA DC voltage, leakage currents, impulse residual voltages, withstanding capability to impulse surge, and energy absorption capability. ZnO varistors which have nonlinear current-voltage characteristic name a number of failure mechanism when ZnO elements absorb surge energies. Failure mode by thermal stress and Pin hole are among the most common failure mechanism at the high current surge current. In this study, the fracture mechaism of power arresters are introduced and protection technologies are researched. In particular the effect of thermal stress by surge currents to ZnO elements and methods against arc surge energy through withstand structure design of arrester are discussed.

  • PDF

용량성 프로브와 광전송회로를 이용한 광대역 전압측정장치 (A Study on the Development of a Lightning Warning System by the Measurement of Electric Field at the Ground)

  • 길경석;송재용;박대원
    • 센서학회지
    • /
    • 제13권5호
    • /
    • pp.363-368
    • /
    • 2004
  • A reliable voltage measurement system is necessary to monitor status of power facilities in substations, which is easy to set up and is not influenced by electromagnetic interference in and around substation. In this paper, we described a voltage measurement system (VMS) which is composed of a capacitive voltage probe, an impedance converter, and an optical linker. To get a wide-band characteristic of the VMS, a high speed impedance converter was used, and the output impedance of the VMS was set at $50{\Omega}$ to match any types of observing instruments. The frequency bandwidth of the VMS. which was estimated by a step pulse, was ranges from 11.42 Hz to 13.65 MHz, and the VMS showed a good response characteristic in a high frequency domain such as impulse voltages as well as a commercial frequency voltage.

$SF_6$$SF_6/CO_2$ 혼합기체 중에서의 뇌임펄스 전구방전의 특성 (Characteristics of lightning impulse pre-breakdown discharge in $SF_6\;and\;SF_6/CO_2$ mixtures)

  • 이복희;오성균;백영환
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2005년도 춘계학술대회논문집
    • /
    • pp.57-60
    • /
    • 2005
  • This paper describes the experimental results of the pre-breakdown phenomena in $SF_6/CO_2$ mixtures under non-uniform electric fields caused by positive and negative lightning negative voltages. $SF_6/CO_2$ mixtures have an advantage of an environmental aspect and cost reduction, and safety aspects. In order to analyze the pre-breakdown processes in $SF_6/CO_2$ mixtures stressed by impulse voltages, pre-breakdown current and luminous signals were measured by a shunt and a photo-multiplier tube, respectively. Dielectric strengthes of $SF_6/CO_2$ mixtures were investigated. Additionally, characteristics of discharge channels were observed by high speed cameras and the physical properties were discussed. The pre-breakdown propagates with a stepwise process. The in to breakdown from the corona onset point in positive polarity was shorter than that in negative polarity. The time intervals of positive leaders are shorter than those of negative leaders, and the path of positive leader channel is zigzag.

  • PDF

뇌보호설비용 인하도선의 설치조건에 따른 전위상승 (Potential Rises of Down-conductor for Lightning Protection System according to Establishment Conditions)

  • 이복희;강성만;이승칠;이동문;안창환
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2001년도 하계학술대회 논문집 C
    • /
    • pp.1724-1726
    • /
    • 2001
  • This paper deals with the characteristics of the potential rises of down-conductor due to lightning surge currents. Direct lightning strikes can cause high impulse currents to the lightning protection system(LPS) of a building. These high impulse currents have the front time as short as 1[${\mu}s$]. In this case, the induced voltages caused in a closed circuit inside the building can be very high and cause damage or submit people to electric hazard. So, the LPS has to be designed to ensure safety condition to person and acceptable levels of induced voltages to the electrical and electronic equipments. The results of the potential rises related to the bonding conditions between the grounding conductor and metal raceway and the type of down-conductors are introduced.

  • PDF