• Title/Summary/Keyword: Impedance to ground

Search Result 450, Processing Time 0.033 seconds

Transient Impedance of the Ground Grid and Deeply-driven Ground Rod (그리드접지와 심매설 접지전극의 과도임피던스)

  • Lee, Bok-Hee;Lee, Su-Bong;Lee, Tae-Hyung;Jung, Hyun-Uk;Jeong, Dong-Cheol;Gil, Hyoung-Jun
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2005.05a
    • /
    • pp.240-243
    • /
    • 2005
  • This paper presents the transient behaviors of grounding system impedance against lighting impulse currents. The dynamic characteristics of the deeply driven ground rod and grounding grid subjected to the impulse current with various rise time were investigated. It was found that the transient ground impedance strongly depends on the configuration and size of grounding electrodes and the shapes of impulse currents, and the inductance of grounding electrodes has a significant affect on the transient ground impedance of grounding system in the short time domain.

  • PDF

Transient Ground Impedance of Small-sized Needle-rod Electrodes due to Underground Soil Discharge (토양의 지중방전에 따른 소형 침봉전극의 과도접지임피던스)

  • Lee, Tae-Hyung;Cho, Sung-Chul;Eom, Ju-Hong;Lee, Bok-Hee
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2008.10a
    • /
    • pp.211-215
    • /
    • 2008
  • This paper deals with the transient ground impedance of small-sized needle-rod installed in a test field, Impulse voltage generator was used to inject lightning impulse on a ground electrode and modified fall-of potential method was proposed to measure the high ground potential rise. Transient ground impedance was analysed with impedance curve and I-V curve as respects the resistivity of soil. Soil ionization near the ground electrode is activated in high resistivity soil and have an effect on the reduction of transient ground impedance significantly.

  • PDF

Characteristics for Ground Impedance of Counterpoise according to Position of Auxiliary Probe and Frequency (보조전극의 배치 및 주파수에 따른 매설지선의 접지임피던스 특성)

  • Gil, Hyoung-Jun;Kim, Dong-Woo
    • Journal of the Korean Society of Safety
    • /
    • v.27 no.4
    • /
    • pp.33-37
    • /
    • 2012
  • This paper describes the characteristics for ground impedance of counterpoise according to position of auxiliary probe and frequency using the fall-of-potential method and the testing techniques to minimize the measuring errors are proposed. The fall-of-potential method is theoretically based on the potential and current measuring principle and the measuring error is primarily caused by the position of auxiliary probes. In order to analyze the effects of ground impedance due to the distance of the current probe and frequency, ground impedances were measured in case that the distance of current probe was located from 10[m] to 100[m] and the measuring frequency was ranged in 55 [Hz], 128[Hz], 342[Hz], and 513[Hz]. The results could be help to determine the position of auxiliary probe when the ground impedance was measured at grounding system.

Theoretical analysis and measurement of Ground impedance of Ground rods (봉상전극 접지임피던스의 측정과 이론적 분석)

  • Lee, Bok-Hee;Lee, Tae-Hyung;Lee, Su-Bong;Eom, Ju-Hong
    • Proceedings of the KIEE Conference
    • /
    • 2004.07c
    • /
    • pp.1876-1878
    • /
    • 2004
  • A systematic approach of measurement, modeling and analysis of grounding system impedance is presented. The measurement and analysis system of ground impedance is based on a computer aided technique. The ground impedances of the ground rod are considerably dependent on the frequency. The ground impedance is mainly resistive in the frequency range of 3-20 kHz. At higher frequencies, the reactive components of the ground impedances are no longer negligible and the inductance of the ground rod was found to be the core factor deciding the ground impedance. As a consequence, the equivalent circuit model based on the measured data was proposed, and the calculated results were in approximately agreement with the measured data.

  • PDF

Measurement Method of the Frequency Dependent Characteristics of Ground Impedance (접지임피던스의 주파수 의존성 측정기법)

  • Eom Ju-Hong;Lee Bok-Hee
    • 한국정보통신설비학회:학술대회논문집
    • /
    • 2004.08a
    • /
    • pp.211-214
    • /
    • 2004
  • The measurement system of ground impedance is based on a computer aided technique. The magnitude and phase of ground impedance were determined by the novel measurement and analysis using the revised fall-of-potential method. The ground impedances of the ground rod of 30 m long are considerably dependent on the frequency. The ground impedance is mainly resistive in the frequency range of 3-20 kHz. At higher frequencies, the reactive components of the ground impedances are no longer negligible and the inductance of the ground rod was found to be the core factor deciding the ground impedance.

  • PDF

Transient Grounding Impedance Behaviors of Deeply-driven Ground Rods According to the Injection Point of Impulse Currents (임펄스전류의 인가위치에 따른 심매실 봉상 접지전극의 과도접지임피던스 특선)

  • Lee, Su-Bong;Li, Feng;Lee, Seung-Ju;Jeon, Byung-Wook;Lee, Bok-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.22 no.10
    • /
    • pp.62-68
    • /
    • 2008
  • This paper presents the transient and conventional grounding impedance behaviors of deeply-driven ground rods associated with the injection point of impulse currents. The transient grounding impedance strongly depends on the length of deeply-driven ground rod and the rise time and injection point of impulse currents, and the intrinsic inductance of ground rod has a significant affect on the transient grounding impedance of grounding system in fast rise time ranges. The reduction of inductance is decisive to improve the impulse impedance behaviors of deeply-driven ground rods. It is effective that grounding conductor is connected to the top of the ground rod as short as possible.

Transient Ground Impedances According to Shapes of Grounding Electrodes (접지전극의 형상에 따른 과도접지임피던스)

  • Lee, Bok-Hee;Lee, Su-Bong;Lee, Tae-Hyung;Jung, Hyun-Uk;Jeong, Dong-Cheol
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.20 no.1
    • /
    • pp.65-70
    • /
    • 2006
  • This paper presents the transient behaviors of grounding system impedance against lightning impulse currents. The dynamic characteristics of the deeply driven ground rod and grounding grid subjected to the impulse current were investigated. The transient ground impedance strongly depends on the configuration and size of grounding electrodes and the shapes of impulse currents, and the inductance of grounding electrodes has a significant affect on the transient ground impedance of grounding system Also, the deeply-driven ground rod was effective to reduce the transient ground impedance in time domain of miceroseconds.

Ground ing Impedance Characteristics of Ground Rods in frequency Domain (주파수 영역에서 봉상전극의 접지임피던스 특성)

  • Lee, Hyung-Soo;Shim, Keon-Bo;Kim, Kyung-Chul;Choi, Jong-Kee;Park, Sang-Man
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2005.05a
    • /
    • pp.248-253
    • /
    • 2005
  • Although DC ground resistance is a good index of grounding performance for grounding electrodes, it does not reflect the grounding performance during transient state. Besides, impulse ground impedance, which is defined by a ratio of the peak value of transient ground potential rise to the peak value of impulse current, cannot be an absolute index due to its dependence on impulse current shape. In this paper, ground impedance of various rod-type ground electrodes has been measured in frequency domain ranging from 1 Hz to hundreds of kHz. Equivalent circuit models of the ground rod have been identified from the measured values of ground impedance in frequency domain.

  • PDF

Ground Impedance and Frequency Response Characteristics of Large-scale Ground Rods (대형 봉상 접지전극의 접지임피던스와 주파수 응답특성)

  • Lee, Bok-Hee;Eom, Ju-Hong;Kim, Tai-Doo;Chung, Dong-Chul;Kil, Hyeong-Joon
    • Proceedings of the KIEE Conference
    • /
    • 2003.07c
    • /
    • pp.1791-1793
    • /
    • 2003
  • In order to analyze the dynamic characteristics of ground impedance in large grounding system for lightning and surge protections, a novel method for measuring the ground impedance as a function of frequency was proposed. The experiments were carried out in the grounding system composed of ground rods and mesh grids. The test current was injected by the variable frequency inverter whose frequency is linearly controlled in the range of $5{\sim}500$kHz. The ground impedance and frequency response of the grounding system were mainly caused by the inductive current flowing through grounding conductors over the frequency of 2002. In the combined grounding system of rods and mesh grids, inductive component of ground impedance was significantly decreased. It was fumed out that the grounding system is effective for the surge protection.

  • PDF

Measurement of Impedance of the Grounding Grid using Variable Frequency Inverter (가변주파수 인버터를 이용한 접지임피던스 측정)

  • 이복희;엄주홍;김교운
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2002.11a
    • /
    • pp.303-306
    • /
    • 2002
  • This paper presents a novel method for measuring the ground impedance in grounding systems. A square wave current was injected to the main grounding grid through auxiliary electrode, and the test current and ground potential rise(GPR) were measured using the band-pass filter. Ground impedance was calculated from the sinusoidal waveforms of the test current and GPR in frequency range of 20~2100Hz. Also the resistance and reactance component of ground impedance were analyzed.

  • PDF